3.2 Heating Mode
3.2.1 Four-way valve opens at once, while defrosting process closes.
3.2.2 Condition for the compressor action: (Ts = set temperature, Ta = room temperature)
Condition
Compressor
Outdoor
fan
Ta> Ts+4
Off
Off
Room temp. up
Ta<Ts+4 On
On
Ta< Ts+3
On
On
Room temp. down
Ta>Ts+3 Off
Off
3.2.3 Indoor Fan Action
3.2.3.1 Anytime remote switchover for fan speed among high/low/auto, (anti-cold air function takes priority).
3.2.3.2 Anti-cold air:
Switchover between fan speed and fine tune can be set according to temperature of evaporator pipe .
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<25°C Off
25°C <T<32°C
Breeze
Indoor exchanger temp. up
T>32°C
Setting fan speed
T> 30°C
Setting fan speed
15°C <T<30°C
Breeze
Indoor exchanger temp. down
T<15°C Off
During anti-cold air period, if indoor fan is shut down, then pre-heating/defrosting lamp is on. Once indoor
fan starts, pre-heating/defrosting lamp will be off.
3.2.3.3 Auto fan of indoor fan under heating mode.
Condition (T =Indoor Temp.-Setting Temp.)
Indoor fan speed
T<3°C High
Room temp. up
T>3°C Low
T> 1°C
Low
Room temp. down
T<1°C High
Summary of Contents for YKHC 18
Page 24: ...22 Part8 Wiring diagram 1 YKHC 12 18 Indoor unit Outdoor unit...
Page 25: ...23 2 YKHC 24 Indoor unit Outdoor unit XT1 XT2 RT3 XS1 XP1 KM1 CAP1 FAN COMP CAP2 XT3 VALVE...
Page 35: ...33 4 Relocate the air in grid in the procedure of reversed order install the air in grid...
Page 40: ...38...
Page 45: ...43 Part12 Exploded view Indoor unit 1 YKHC 12 18...
Page 53: ...www johnsoncontrols com SM YKHC 18 48GB 03 07...