428546-YIM-C-1110

YCCS System Manager and Zone Coordinator Installation Instructions

8

Communication Bus

Determining the System Manager Address Switch

The System Manager address switch is always set to 0; 
therefore, you do 

not 

need to determine the System 

Manager address.

Determining the Zone Coordinator Bus Address

The Bus address switch sets a unique address for this 
controller on the System Communication Bus. The 
default address setting is 255 (all ON). You must change 
the default address.

Set consecutive addresses 8-17 for Zone Coordinator on 
the System Communication Bus. Use sequential 
addressing with no gaps in the device address range to 
ensure best Bus performance. Table 5 and Figure 7 show 
System Communication Bus address switch settings.         

Powering On the System Manager and Zone 
Coordinator

After applying 24 VAC power, the controllers require 
approximately 2 minutes to start up and become 
operational. Startup is completed and the controllers are 
operational when the home screen appears. The green 
RUN LED appears and is on steady.  

Disconnecting Power from the System Manager 
and Zone Coordinator

The System Manager and Zone Coordinator have no 
backup battery power. When the 24 VAC power supply is 
disconnected or lost, the controllers are nonoperational. 

End-of-Line (EOL) Terminations

Daisy-chained RS485 protocol networks require End-of-
Line (EOL) termination to reduce interference. 
Interference is caused by signal reflection that occurs 
when data transmissions reach the end of a bus segment 
and bounce back (Figure 8). The high baud rates on 
Master-Slave/Token-Passing (MS/TP) bus applications 
require robust EOL termination and strict adherence to 
the EOL termination rules.

Figure 6: Zone Coordinator

Address Switch Detail

8 7 6 5 4 3 2 1

ON

OFF

Front

View from bottom of 

Zone Coordinator

 

Address Switch 255 

(All switches shown in

OFF position)

12
8

64

32

16

8

4

2

1

FI

G:Z

C

_sw

tc

h

Figure 7: Zone Coordinator

Address Switch Settings

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 8

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

12
8

Address 9

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 10

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

12
8

Address 11

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 12

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 13

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

12
8

Address 14

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 15

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 16

8 7 6 5 4 3 2 1

ON

OFF

1

2

4

8

16

32

64

128

Address 17

F

IG:

Z

C

_s

w

tc

h_s

et

s

Table 5:  System Communication Bus Address 

Summary

Address

Description

8–17

Zone Coordinator on the System 

Communication Bus

IMPORTANT:

Wait for the controller to complete 

the startup sequence and the RUN LED to appear 
before initiating other actions.

No EOL = No Signal Cushioning 

(Bounce Back and Noise)

 

No

EOL

EOL

EOL Provides Signal 

Cushioning (No Bounce Back)

FI

G

:in

tr

fr

nc

Figure 8: Interference

Summary of Contents for YK-SMU2x0-0

Page 1: ...trollers have no user serviceable parts inside the housing Parts Included One System Manager or Zone Coordinator with removable mounting base Materials and Special Tools Needed three fasteners appropr...

Page 2: ...pervisory controller securely and evenly on the surface Mount the supervisory controller in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specificati...

Page 3: ...or ports modular jacks and terminal blocks Power Supply The Zone Coordinator and System Manager requires a dedicated Class 2 24 VAC 10 VA minimum power supply System Communication Zone Communication B...

Page 4: ...three Zone Communication Bus wires for the Zone Coordinator Figure 3 and Figure 4 Note When the controllers are connected to the System Communication Bus you must set the End of Line EOL switch to th...

Page 5: ...ices Supported System Manager YK SMU2xx 0 Supports up to 38 devices total on the System Communications Bus including up to 10 Zone Coordinators up to 24 factory or field mounted RoofTop Unit RTU contr...

Page 6: ...ly of the communication trunk Do this on the last unit in line 7 Use an existing hole or drill a hole and insert a sheet metal screw in the back plate below the communication connector 8 Wrap the bare...

Page 7: ...2 COM AI1 AI2 COM AI3 AI4 1 64 32 16 8 4 2 128 O N 24V COM 24V COM COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 16 8 4 2 128 O N 24V COM 24V COM Drain Wire Drain Wire Tape back Drain Wire Drain Wire Drain W...

Page 8: ...Line EOL termination to reduce interference Interference is caused by signal reflection that occurs when data transmissions reach the end of a bus segment and bounce back Figure 8 The high baud rates...

Page 9: ...re Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Scheduled Item 3 To Scheduled Item 4 Non CCS HVAC System Universal CV U...

Page 10: ...reliable partition disconnect and isolate a portion of the Bus for testing purposes and test the Bus portion connected to the System Manager and Zone Coordinator controllers Correcting Physical Commun...

Page 11: ...touch screen user interface and Ethernet port for Web browser access and optional internal modem Power Supply Requirement Dedicated nominal 24 VAC Class 2 power supply North America at 50 60 Hz 20 VA...

Page 12: ...l internal modem YK ZCU400 0 VAV Zone Coordinator with color touch screen user interface and Ethernet port for Web browser access YK ZCU410 0 VAV Zone Coordinator with color touch screen user interfac...

Reviews: