YCCS System Manager and Zone Coordinator Installation Instructions 

9

428546-YIM-C-1110

On a YCCS System bus or Zone bus, only one EOL 
termination is required due to the fewer number of 
devices on one bus and the shorter wiring length. 
Specifically, the System bus must always have a 
System Manager as the EOL device, and the Zone bus 
must always have a Zone Coordinator as the EOL 
device. Figure 9 shows a YCCS EOL wiring example.

Operation

For information on heating and cooling modes, zone 
voting, and other Zone Coordinator and System 
Manager functions, refer to the 

York

 

Commercial 

Comfort System (YCCS) Operation Overview Technical 
Guide (643517)

For information on creating setpoints and configuring 
operating modes, refer to the 

York Commercial 

Comfort System (YCCS) System Manager and Zone 
Coordinator Userís Guide (428516)

.

Figure 9: System Manager and Zone Coordinator EOL Wiring

Input

Output

Module

24V

COM

COM

-

+

BI-1

COM

BI-2

COM

AI-3

COM

AI-4

Monitored Contact

To Temperature, 

RH%,  CO

2

 Sensor, 

Building Pressure, 

Light Sensor, 

Refrigerant Sensor

To 24VAC

BO-3

BO-2

BO-1

BO-4

COM

Monitored Contact

To Scheduled Item 1

To Scheduled Item 2

To Scheduled Item 3

To Scheduled Item 4

Non-

CCS

HVAC

System

Universal

CV Unit

Controller

24V

COM

Zone Sensor

COM

-

+

AI-1

COM

AI-2

1

2

3

4

BO-1

BO-2

BO-3

BO-4

BO-5

C

R

G

Y1

Y2

W1

W2

COM

AI-6

COM

AI-7

COM

AI-8

COM

AI-4

COM

AI-5

COM

BI-2

SAT Sensor

RAT Sensor

OAT Sensor

To Zone RH% Sensor

To Zone CO

2

 Sensor

APS

Zone Sensor

COBP Zone Coordinator

System 

Bus

CO

M

SB

-

SB

+

EOL

O
N

?

Zone

Bus

CO

M

ZB-

ZB+

EOL

O
N

?

COM

24V

LAN

To 24VAC

System Manager

System 

Bus

COM

SB-

SB+

EOL

O
N

Zone

Bus

COM

ZB

-

ZB

+

EOL

O
N

COM

24V

Modem

LAN

To 24VAC

To Phone Line

To Ethernet Hub

VAV Zone Coordinator

System 

Bus

COM

SB-

SB+

EOL

O
N

Zone

Bus

COM

ZB

-

ZB

+

EOL

O
N

COM

24V

LAN

To 24VAC

tape

off

CV Unit Controller

CO

M

-

+

Simplicity Board

Binary

&

ModBus

This end of the Drain Wire 
connected to cabinet ground

Other System Bus Devices

AI-1

COM

AI-2

1

2

3

4

Other System Bus Devices

Other System Bus Devices

To COBP Zone 
Bus Devices

To VAV Zone 
Bus Devices

Zone Coordinator must be end of line for zone bus

System Manager must be end of line for system bus

FI

G

:SM

-Z

C

_EOL

Zone Coordinator must be end of line for zone bus

Summary of Contents for YK-SMU2x0-0

Page 1: ...trollers have no user serviceable parts inside the housing Parts Included One System Manager or Zone Coordinator with removable mounting base Materials and Special Tools Needed three fasteners appropr...

Page 2: ...pervisory controller securely and evenly on the surface Mount the supervisory controller in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specificati...

Page 3: ...or ports modular jacks and terminal blocks Power Supply The Zone Coordinator and System Manager requires a dedicated Class 2 24 VAC 10 VA minimum power supply System Communication Zone Communication B...

Page 4: ...three Zone Communication Bus wires for the Zone Coordinator Figure 3 and Figure 4 Note When the controllers are connected to the System Communication Bus you must set the End of Line EOL switch to th...

Page 5: ...ices Supported System Manager YK SMU2xx 0 Supports up to 38 devices total on the System Communications Bus including up to 10 Zone Coordinators up to 24 factory or field mounted RoofTop Unit RTU contr...

Page 6: ...ly of the communication trunk Do this on the last unit in line 7 Use an existing hole or drill a hole and insert a sheet metal screw in the back plate below the communication connector 8 Wrap the bare...

Page 7: ...2 COM AI1 AI2 COM AI3 AI4 1 64 32 16 8 4 2 128 O N 24V COM 24V COM COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 16 8 4 2 128 O N 24V COM 24V COM Drain Wire Drain Wire Tape back Drain Wire Drain Wire Drain W...

Page 8: ...Line EOL termination to reduce interference Interference is caused by signal reflection that occurs when data transmissions reach the end of a bus segment and bounce back Figure 8 The high baud rates...

Page 9: ...re Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Scheduled Item 3 To Scheduled Item 4 Non CCS HVAC System Universal CV U...

Page 10: ...reliable partition disconnect and isolate a portion of the Bus for testing purposes and test the Bus portion connected to the System Manager and Zone Coordinator controllers Correcting Physical Commun...

Page 11: ...touch screen user interface and Ethernet port for Web browser access and optional internal modem Power Supply Requirement Dedicated nominal 24 VAC Class 2 power supply North America at 50 60 Hz 20 VA...

Page 12: ...l internal modem YK ZCU400 0 VAV Zone Coordinator with color touch screen user interface and Ethernet port for Web browser access YK ZCU410 0 VAV Zone Coordinator with color touch screen user interfac...

Reviews: