SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
91
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays information pertaining to a Vari-
able Speed Drive (VSD).
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link Gateway interface in
ISN mode, or a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Output Voltage
Displays the output voltage measured to the motor.
Output Frequency
Displays the present output frequency to the motor.
Output Current – Phase A, B, C
Displays the phase current measured to the motor.
Input Power
Displays the total kilowatts measured by the VSD or
Harmonic Filter, if installed.
KW Hours
Displays the cumulative amount of kilowatts used over
time as the VSD motor controller operates.
Pre-rotation Vane Position
Displays the Pre-rotation Vane position as a value be-
tween 0 and 100%.