SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
151
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen allows definition of general parameters
having to do with the operation of the chiller.
DISPLAY ONLY
Chiller Run Time
(Flash Memory Card version C.MLM.01.04 or later)
Displays the amount of time the chiller has been run-
ning since the last start signal was received. Value
is reset to zero when the chiller enters coastdown. It
remains at zero while shutdown and during System
Prelube.
For fields requiring access level of SER
-
VICE. Service Technicians refer to the
OptiView Control Center - Service Instruc
-
tions (Form 160.54-M1) for operation
instructions and explanation of all pro-
grammable setpoints and displayed values.
PROGRAMMABLE
Control Source
Access Level Required: OPERATOR
Define whether the control of the chiller will be Lo-
cal, Digital Remote, Analog Remote, Modem Remote
or ISN Remote.
Number of Starts
Access Level Required: ADMIN
Displays the number of the starts the chiller has initi-
ated. This may be reprogrammed to a desired value,
(generally when this value has been reset due to a
Microboard replacement), but should not be done so
arbitrarily.
Operating Hours
Access Level Required: ADMIN
Displays the total accumulated run time of the chiller.
This may be reprogrammed to a desired value (gener-
ally when this value has been reset due to a Microboard
replacement), but should not be done so arbitrarily.
OPERATIONS SCREEN
LD09578a
FIGURE 51 -
OPERATIONS SCREEN