Installation Procedure
13
2. Piping size for single split
3. Limitations for one way piping length and vertical height difference for single split
Precautions for refrigerant piping
Do not twist or crush piping.
Be sure that no dust is mixed in piping.
Bend piping with as wide angle as possible.
Keep insulating both gas and liquid piping.
Check flare-connected area for gas leakage.
Apply refrigerant oil to the joint and the flange.
To bend a pipe, give the roundness as possible not to crush
the pipe.
When connecting pipe, hold the pipe centre to centre and then
screw nut on by hand, refer to Fig.
Be careful not to let foreign matters, such as sands enter
the pipe.
4. Piping connection method
Forced fastening without centering may damage the threads and cause a gas leakage.
Model
One way piping length
Vertical height difference
(between indoor and outdoor)
Install the removed flare nuts to the pipes
to be connected, then flare the pipes.
Gas pipe
15.88x1.0mm
Liquid pipe
Gas pipe
9.52x0.8mm
19.05x1.0mm
Liquid pipe
9.52x0.8mm
5. For the allowable pipe length and height difference for maxi split system, please see the table in the page 2 of
this manual.
Piping Connection
90+0.5
48K 60K
24K 28K 36K
Pipe diameter
Fastening torque (N.m)
Liquid pipe 6.35mm
Gas pipe 15.88mm
Liquid pipe 9.52mm
Gas pipe 19.05mm
14.2-17.2
61.8-75.4
32.7-39.9
97.2-118.6
Gas pipe 12.7mm
49.5-60.3
1. Piping diagram for single split
Outdoor
unit
Gas pipe
Liquid
pipe
Flare connection
Indoor
unit
3-way stop valve
3-way stop valve
less than 30 m
less than 20 m
less than 50 m
less than 30 m
24K 28K 36K
48K 60K
24K 28K 36K 48K 60K
Spanner
Spanner
Nut
Joint