background image

835959-UIM-D-0814

6

Johnson Controls Unitary Products

SECTION V: EVACUATION

During this process, it is necessary to evacuate the system to 500
microns or less. If a leak is suspected, a dry nitrogen charge is used to
locate leak(s). After repairing any leaks, another leak test is to be per-
formed.

To verify that the system has no leaks, the system is held under a vac-
uum by closing the valve to the vacuum pump suction isolating the
pump. The micron gauge is observed for a few minutes. If the micron
gauge indicates a steady and continuous rise, it is an indication of a
leak. If the gauge shows a rise, then levels off after a few minutes and
remains fairly constant above 500 microns, it is an indication that the
system is leak free but still contains moisture and may require further
evacuation. Proper system evacuation requires the micron gauge to
indicate a vacuum holding below 500 microns for several minutes. 

SECTION VI: SYSTEM CHARGE

To ensure that your unit performs at the published levels, it is important
that the indoor airflow is determined and refrigerant charge added
accordingly.

MEASURE INDOOR AIR FLOW

To determine rated air flow for a specific match, consult the technical lit-
erature at www.upgnet.com. When attempting to match this air flow,
select the lowest possible speed tap, measure the actual flow, and
adjust as necessary. 

To measure actual air flow, it is not an acceptable method to just
check the jumper pin setting tables and to assume 0.5” static pres-
sure drop.

To determine indoor air flow, first measure the static pressure with a
manometer between the filter and blower. On a single-piece air handler,
take a second reading after the coil. On a furnace or modular air han-
dler, take the second reading after the heat exchanger, but before the
indoor coil. Add the negative return static to the positive supply static to
determine the system total static pressure. Treat the negative return
static as a positive pressure (even though it is a negative reading). If
there is static pressure on the blower (i.e. -.10) return, add it to a supply
static (.40) which equals a (.50) total system static pressure. Compare
this value to the table for the indoor unit's static pressure vs. CFM or to
a curve chart.

CHARGING THE UNIT

The factory charge in the outdoor unit includes enough charge for the
unit, 15 ft. (4.6 m) of refrigerant piping, and the smallest indoor coil/air
handler match-up. Some indoor coil/air handler matches may require
additional charge. 

See Tabular Data Sheet provided in unit Customer Booklet for charge
requirements. 

The “TOTAL SYSTEM CHARGE” must be permanently marked on the
unit data plate.

TOTAL SYSTEM CHARGE DETERMINED 

1. Determine outdoor unit factory charge from Tabular Data Sheet.

2. Determine indoor coil adjustment (if any) from Tabular Data Sheet.

3. Calculate the additional charge for refrigerant piping using the Tabu-

lar Data Sheet if line length is greater than 15 feet (4.6 m).

4. Total system charge = item 1 + item 2 + item 3.

5. Permanently mark the unit data plate with the total amount of refrig-

erant in the system.

CHARGING IN COOLING MODE

The unit includes heating charging charts and cooling charging charts. 
All units include a subcooling charging chart for cooling. If a charging 
chart is not on the unit, then it can be obtained at www.upgnet.com 
under the Heating Service Condenser Guide.

Cooling charts should not be used to charge the unit. They are ref-
erence charts for servicing the unit. 

After the unit has been serviced, collect the charge and weigh it
back in according to the directions.

When charging a unit in cooling mode, the charge MUST be weighed in.
Charging by any other method, such as superheat, subcooling, cooling
charging charts, feeling the line set, etc is not acceptable. Most heat
pumps are sensitive to charge in heating, requiring more charge, so
charging by an unacceptable method will cause the unit to perform
poorly in heating mode. 

Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.

R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the Upright Posi-
tion.
 Always charge the system slowly with the tank in the upright
position.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Do not leave the system open to the atmosphere. Unit damage
could occur due to moisture being absorbed by the POE oil in the
system. This type of oil is highly susceptible to moisture absorp-
tion.

DO NOT attempt to pump “Total System Charge” into outdoor unit for
maintenance, service, etc. This may cause damage to the compres-
sor and/or other components. The outdoor unit only has enough vol-
ume for the factory charge, not the “Total System Charge”.

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS-
CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR,
SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS
UNIT.

This method is for systems that only have interconnecting lines. If
any other objects that adjust the charge levels are placed between
the indoor and outdoor units (example: a refrigerant flow meter), then
before adding charge, the device must first be removed. Follow the
steps above. Run the system in both cooling and heating mode and
record the high side pressure in each mode. Then insert the device
and charge the system by matching the same high side pressure in
both heating and cooling as that value recorded without the device. It
is not acceptable to add a pre-determined charge amount listed by
the device manufacturer nor is it acceptable to use any other method.

NOTICE

Summary of Contents for YHJF60

Page 1: ...al line lengths Refer to Appli cation Data covering General Piping Recommendations and Refriger ant Line Length Part Number 247077 SECTION II SAFETY This is a safety alert symbol When you see this sym...

Page 2: ...er of hot air into the outdoor unit Provide adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoor unit...

Page 3: ...eet The charge given is applicable for total tubing lengths up to 15 feet See Application Data Part Number 247077 for installing tubing of longer lengths and elevation differences PRECAUTIONS DURING L...

Page 4: ...er grommet from the vapor connection at the indoor coil Braze the vapor line to the evaporator vapor connection After the connection has cooled place the rubber grommet back into the mounting position...

Page 5: ...al 1 3 turn to seal 8 Install the TXV bulb to the suction line near the equalizer line using the bulb clamp s furnished with the TXV assembly kit Ensure the bulb is making maximum contact a Install th...

Page 6: ...coil adjustment if any from Tabular Data Sheet 3 Calculate the additional charge for refrigerant piping using the Tabu lar Data Sheet if line length is greater than 15 feet 4 6 m 4 Total system charge...

Page 7: ...itches and over current protection must be supplied by the installer Wire size should be sized per NEC requirements The complete connection diagram and schematic wiring label is located on the inside...

Page 8: ...he recommended air flow settings for each size condensing unit Set the cooling speed per the instructions for the air handler or furnace by selecting the correct COOL and ADJUST or ADJ taps Verify the...

Page 9: ...4 Volt Hot W3 Third Stage Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energ...

Page 10: ...uxiliary Heat COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L...

Page 11: ...energized only when the unit is not running If the main switch is disconnected for long peri ods of shut down do not attempt to start the unit until 8 hours after the switch has been connected This wi...

Page 12: ...GRN GREEN GRY GREY ORG ORANGE PUR PURPLE RED RED WHT WHITE YEL YELLOW Y B YEL BLK LEGEND AS AMBIENT SENSOR CAP CAPACITOR COMP COMPRESSOR CC CONTACTOR COIL CCH CRANKCASE HEATER DS DISCHARGE SENSOR HPS...

Page 13: ...plicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connecte...

Page 14: ...p Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board install...

Page 15: ...plain operation of system to equipment owner Explain the importance of regular filter replacement and equipment maintenance Owner Education Provide owner with the owner s manual Explain thermostat use...

Page 16: ...change without notice Published in U S A 835959 UIM D 0814 Copyright 2014 by Johnson Controls Inc All rights reserved Supersedes 835959 UIM C 0614 York International Corp 5005 York Drive Norman OK 73...

Reviews: