JOHNSON CONTROLS
103
SECTION 5 - COMMISSIONING
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
5
JOHNSON CONTROLS
6
FORM 155.31-CL1
.EN.UL
ISSUE DATE:
12/14/2018
DOUBLE EFFECT STEAM ABSORPTION CHILLER COMMISSIONING DATA SHEET (2/2)
User:
Model:
MFG.No.:
User's machine code:
Running Data
Date:
Measured by
Specification
Standard
:
:
:
Steam
Steam
control
v
alve or
steam drain control valve
position
%
Control panel
Steam primary pressure
Pressure gauge
≤
116PSI
Steam secondary pres-
sure
Pressure gauge
Steam temperature
°
F
Thermometer
≤
347
°
F
Drain outlet (back)
pressure
Pressure gauge
Drain temperature
°
F
Thermometer
≤
203
°
F
Steam consumption
Flow meter
Chilled
Water
Inlet temperature
°
F
Control panel
Outlet temperature
°
F
Control panel
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[3] Pressure drop
DPG or calculation
[4]
[1] Flow rate
FM or calculation
[2]
Cooling
Water
Inlet temperature
°
F
Control panel
68
.0~
89
.
6
°
F
Outlet temperature
°
F
Control panel
68
.0~
99
.5°
F
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[7] Pressure drop
DPG or calculation
[8]
[5] Flow rate
FM or calculation
[6]
Absorption
Cycle
HG pressure (Gauge)
PSIG
Compound gauge
≤ -0.
4
P
SIG
HG pressure (Sensor)
mmHg
Control panel
≤
720
mmHg
HG temperature
°
F
Control panel
≤
329
°
F
HG solution concentra-
tion
%
Control panel
Absorber temperature
°
F
Control panel
Refrigerant temperature
°
F
Control panel
Liquid
Level
HG
Level gauge
LG
Level gauge
Absorber
Level gauge
Evaporator (Lower)
Level gauge
Evaporator (Upper)
Level gauge
NOTES:
Operating hours
hours
Number of purge times times
Fill out each specification pressure drop according to the factory inspection report (actual value).
If differential pressure gauge (DPG) is not available, calculate each pressure drop.
If flow meter (FM) is not available, calculate each flow rate as below.
[1] = [2] x √[3]/[4] [5]=[6] x √[7]/[8]
LD20020
Same
Height
Waterbox
OUT
P
P
IN
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
PSIG
ft3/h
ft3/h
ft3/h