![York YHAU-CW Manual Download Page 104](http://html1.mh-extra.com/html/york/yhau-cw/yhau-cw_manual_4218884104.webp)
JOHNSON CONTROLS
104
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
7
Form 155.31-CL1.EN.UL
ISSUE DATE: 1
2
/
21
/201
8
PURGE AMOUNT DATA SHEET (1/1)
User:
Model:
MFG.No.:
User's machine code:
Measured Date:
Measured by:
Purge Amount from Purge Tank
Flame Reaction Test
Standard: 4.0 cc/min. or smaller
Reaction ( Strong / Weak / None )
Amount of Gas (P)
cc/min
Purge Amount from Purge Line
Elapsed time
1 hour
Consumed time for measurement (m)
min.
Total gas amount (a)
cc
Actual gas amount (b)
cc
(b) = (a) - (P) x (m)
Purge Amount from Absorber
Standard: 4.0 cc/min. or smaller
Elapsed time (T)
min.
1
2
3
5
10
15
20
30
Total gas amount (A)
cc
Increased gas amount (B)
cc
Actual gas amount (C)
cc/min.
(B) = (A) - previous(A)
(B) - (P) x { (T) - previous(T) }
(C) =
(T) - previous(T)