3.3 Installation

Fig. 3.3.1 Fixing the suspension bolts 

Fig. 3.2.1  

·

For the concrete

(Unit:mm)

·

For the steel beam

·

For the wooden beam

150 to160mm

Screw in

100 to150kg

Steel bar

Concrete

Suspension bolts

(W3/8 or M10)

  

 shaped steel beam

Wood rib 

60mm to 90mm 

Wooden beam

Nut 

Round washer

Square washer

Suspension bolts

12

3.3.2 The position of the suspension bolts and the 

s

tube

(1) Mark the positions of the suspension bolts, the 
positions of the refrigerant pipes and the drain 

s.

tube

(2) The dimension are shown below.

Installation and Maintenance

Suspension bolts

(W3/8 or M10)

Nut 

3.2 Installation location

Space for installation and service

Fig. 3.3.2 Suspension bolts

Ceiling Installation

Floor standing Installation

100mm or more

150mm or more

4000~5000mm or more

5mm or more

Obstacle

3

0

0

m

m

o

r

m

o

re

Floor

Wall

1

5

0

m

m

o

r

m

o

re

Blowout opening

100mm or more

4000~5000mm

150mm or more

1

5

0

m

m

o

r

m

o

re

floor

wall

Capacity(Btu/h)

A

B

18K

,

24K

990

912

36K

1285

1207

 48K

,

55K

1580

1502

·

·
·
·

·

 

is ensured. (See Fig. 3.2.1 )

·

·

·

·

Select the suitable areas to install the unit under

    approval of the user.

If there are 2 units of wireless type, keep them  

away for more than 6 m to avoid malfunction due to 
cross communication.

The air path is not blocked.
Condensate can drain properly.
The ceiling is strong enough to bear the weight of 

the indoor unit.

Sufficient clearance for maintenance and servicing

Tubing between the indoor and outdoor units is 

within the allowable limits. (refer to the installation of 
the outdoor unit ).

The indoor unit, outdoor unit, power supply wiring 

and transmission wiring is at least 1 meter away from 
televisions and radio, to prevents interference and 
noise in those electrical appliances. (Noise may be 
generated depending on the conditions under which 
the electric wave is generated, even if a one-meter 
allowance is maintained).

·

Use suspension bolts to install the unit, check

whether or not the ceiling is strong enough to support 
the weight of the unit. If there is a risk that the ceiling 
is not strong enough, reinforce the ceiling before 
installing the unit. 

When several indoor units are installed nearby, keep 

them away for more than 4-5m.

According to the actual installation space,  installation

 

can

 

be

 

done

 

at

 

in the ceiling

 

or

 

on

 

the

 

floor

.  

3.3.1 Suspension bolts
(1) Consider the pipe direction, wiring and maintenance 
access carefully, and choose the proper direction and 
location for installation.
(2) Install the suspension bolts as shown in Fig. 3.3.1 
below.

AUV-18HR4SSA1
AUV-24HR4SFA1
AUV-36HR6SDB1
AUV-48HR6SEC1
AUV-60HR6SPC1

RPFC-2.0UNZ1NH
RPFC-3.0UNZ1NH
RPFC-4.0UNZ1NH
RPFC-6.0UNZ1NH
RPFC-6.5UNZ1NH

YFGN18BZNRZUH1
YFGN24BZNRZUH1
YFGN36BZMRZUH1
YFGN48BZMRZUH1
YFGN55BZMRZUH1

RAS-2.0UNZGNH1
RAS-3.0UNZGNH1
RAS-4.0UNZGMH1
RAS-6.0UNZGMH1
RAS-6.5UNZGMH1

Blowing out the surviwal heating air

When

 

stoping

 

the

 

air

 

conditioner

 

in

 

normal

 

operation

the

 

fan

 

motor

 

would

 

run

 

with

 

low

 

speed

 

for

 

a

 

while

 

to

 

blow

     

out

 

the

 

residual

 

heating

 

air

.

Summary of Contents for YFGN24BZNRZUH1

Page 1: ...ir Conditioner R 410A 50Hz T1 Heat Pump R 410A 50Hz T1 Cooling Only Model YFGN18BZNRZUH1 YFGN24BZNRZUH1 YFGN36BZMRZUH1 YFGN48BZMRZUH1 YFGN55BZMRZUH1 Model YFFN18BZNRZTH1 YFFN24BZNRZTH1 YFFN36BZMRZTH1...

Page 2: ...t Tubing 15 4 1 The Tubing Material 15 4 2 Tubing Connection 15 16 5 Drain Tubing 6 Electrical wiring 17 7 Attaching the Air Return Grille 17 8 The Installation of the Outdoor Unit 18 8 18 1 Installat...

Page 3: ...rature 25 60 Humidity 30 80 Heating and electric heating function are not available for cooling only models The symbol refers to a hazard which can result in severe personal injury or death The symbol...

Page 4: ...duct is installed is supposed to have the independent leakage protective device and the electric current over load protection device which are provided for this product If not it will caus an eleectri...

Page 5: ...ribed in this instruction manual Never use gasoline or other inflammable gas near the air conditioner which will cause fire hazards When the air conditioner operation is abnormal such as burnt smell d...

Page 6: ...ontal Louver 4 Composition of the Air conditioner Indoor Unit Outdoor Unit 48K 55K 18K 24K 36K Notes Figures in the manual are only simple representation of the appliance it may not comply with the ap...

Page 7: ...roller or wireless remote controller It is used for power ON OFF setting the operating mode temperature fan speed and other functions There are different types of remote controllers which can be used...

Page 8: ...nless you use remote control switch to turn off the unit all indoor unit can be turned off by user The fan of the indoor unit will never stop running in cooling operation It remains running even if th...

Page 9: ...long period of time Clean the air filter and panels or allow a good ventilation Sound from Deforming Parts Steam from Outdoor Heat Exchanger When the cooling operation continues for a long period of...

Page 10: ...nit Terminal Terminal SI L N SI L N Power connecting cord N R S T 36K 48K 55K Outdoor unit Indoor unit Terminal Terminal N N 1L 3L 2L 1L 3L 2L Power connecting cord N L 18K 24K Gas piping Wide service...

Page 11: ...es other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture resulting in injury If a...

Page 12: ...8 9 10 11 12 13 14 Tool Knife or wire stripper Gradienter Hammer Churn drill Tube expander Inner hexagon spanner Tape measure 3 1 Before installation When moving the unit during or after unpacking ma...

Page 13: ...t Piping Connection For Drain Tube Connection For Joint Socket Connection For Drain Hose Connection For Drain Hose Cover 1 1 1 1 2 2 1 10 8 1 For Drain Hose Connection 1 For Drain Hose And Piping Conn...

Page 14: ...more than 6 m to avoid malfunction due to cross communication The air path is not blocked Condensate can drain properly The ceiling is strong enough to bear the weight of the indoor unit Sufficient c...

Page 15: ...outlet Right outlet Rear outlet Drain outlet rear right Drain outlet rear left Drain outlet right Drain outlet left Fig 3 3 3 Fig 3 3 4 Fig 3 3 5 1 Remove the air return grille Slide stoppers 4 place...

Page 16: ...wo screws M5 1 each on the left and right sides Floor standing type installation 1 Select the suspension bolt locations and the tube hole location Use enclosed paper pattern as a reference and drill t...

Page 17: ...outed through the back Cut the removed top cover and install to the rear panel instead of rear cover Gas piping Liquid piping Drain piping right Drain piping left Use the R410A refrigerant When carryi...

Page 18: ...eas below should be insulated because condensation may form there causing water to leak Drain ing passing indoors tub Drain sockets Referring the figure below insulate the drain socket and drain hose...

Page 19: ...grille When clamping the wiring use the included clamping material as shown in the Fig 6 1 to prevent outside pressure being exerted on the wiring connections and clamp firmly When doing the wiring m...

Page 20: ...ew at least 4 About 40cm About 10cm Indoor unit Tube length L Height difference H Outdoor unit 20 m 15 m 15 g m 30 m 15 m 35 g m 30 m 20 m 35 g m 50 m 30 m 35 g m Max Tube length L Model 24K 36K 48K 5...

Page 21: ...eat insulation effect Also be sure the condensed drain hose splits away from bundle and drips clear of the unit and the tubing The two refrigerant tubes and electrical wire if local codes permit shoul...

Page 22: ...se contact local technical service center of our company for further information Narrow tube Hex wrench Wide tube Service valve Bonnet of service valve Bonnet of narrow valve Bonnet of wide valve Indo...

Page 23: ...ard EN60335 1 Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord code designation H07RN F When connecting the terminal block using flexible cord make sure to...

Page 24: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Reviews: