Page 100
5.10 Overload current protection diagnosis and solution
Description
: An abnormal current rise is detected by checking the specified current detection circuit.
Recommended parts to prepare:
• Power supply problems.
• System blockage
• Faulty PCB
• Wiring mistake
• Compressor malfunction
Troubleshooting and repair:
C heck the pow er supply
.
D o any exist
?
A re they w ithin acceptable
param eters
?
A re they properly connected
?
Is it in w orking order
?
Replace the outdoor unit
.
Is it in w orking order
?
C heck system for blockages
.
Y ES
Stop the unit
.
N O
C lear the blockage
.
N O
C heck the com pressor resistance values
.
Y ES
Replace the com pressor
.
N O
C heck the connections and w ires
.
Y ES
Ensure proper connections or
replace the w ires
.
N O
C heck the reactor
.
Y ES
Y ES
Replace the outdoor
electronic control box
.
N O