background image

Exploded View

EXPLODED VIEW OUTDOOR UNIT - YE2CE240 / 300 
ALL VOLTAGES COOL / HEAT PUMP

COMMERCIAL DUCTED SPLITS

37

Summary of Contents for YE2CE 072

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL York Taurus Commercial Ducted Splits 2 ...

Page 2: ...delines Interconnection Pipes heat 09 F Guidelines Interconnection Pipes Cool 10 G Sound Pressure Data 11 F Field Wiring Guide 12 G Commissioning of Electrical Wires 14 Power Cables H Servicing of the Indoor and 15 Outdoor units General Arrangement Drawings 16 Electrical Data 21 Wiring Diagrams 25 Spare parts list 31 Exploded View 35 Trouble Shooting 38 Index ...

Page 3: ...k inside the unit or in front of the coil Make provisions for condensate drainage Do proper conducting from drain outlet of the unit to soak pit to avoid drippage Detail installation method depends on building construction and local building codes Indoor Unit Mounting Vertical Position If there is good room height Mount the unit on a MS channel frame over solid floor or level pad Refer the fig 8 T...

Page 4: ...s restrictions and practices Use 25 4mm 1 ID pipe or rubber hose to connect with GI nipple of unit to dispose the condensate water from unit to termination point Condensate drain pipe should be terminated near to recommended drain trap or soak pits While installing the unit make sure that drain slope should be away from the unit In case the termination point or drain trap far away from unit instal...

Page 5: ...ust be lifted by 2 pipe hook rigging sling in base rail use spreader bar to prevent the sling from damaging the unit A minimum clearance of 1 m on serviceable side 300 mm for air inlets on all sides and 1 5 m for air discharge unit top is required The unit must be located outdoor only and cannot be connected to duct work The metal parts of the unit if subjected to salt spray fog or mist in seacoas...

Page 6: ...maximum lift should not exceed 100 feet suction line The oil trap to be repeated every 35 feet C If indoor unit YE2EU is located above outdoor unit YE2CE the maximum lift should not exceed 70 feet liquid line Suction Line Indoor Unit Suction Line Oil Trap Indoor Unit Indoor Unit Below The ODU 100ft Max Indoor Unit In Level With ODU Fig 11 Fig 12 Fig 13 Indoor Unit Above The ODU Indoor Unit Inverte...

Page 7: ... 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 150 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 175 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 200 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 YE2EU 072 YE2CE 072 YE2CE 090 YE2CE 120 YE2CE 150 YE2CE 180 YE2CE 216 YE2CE 240 YE2CE 300 YE2EU 090 YE2EU 120 YE2EU 150 YE2EU 180 YE2EU 216 YE2EU 240 YE2EU 300 SUCTION LINE LIQUID LINE EQUIVALENT LENGTH UNIT SPE...

Page 8: ...8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 150 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 175 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 200 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 YE2EU 072 YE2CE 072 YE2CE 090 YE2CE 120 YE2CE 150 YE2CE 180 YE2CE 216 YE2CE 240 YE2CE 300 YE2EU 090 YE2EU 120 YE2EU 150 YE2EU 180 YE2EU 216 YE2EU 240 YE2EU 300 SUCTION LINE LIQUID LINE EQUIVALENT UNIT SPECIFI...

Page 9: ...R22 UNITS 1M DISTANCE INDOOR dB A OUTDOOR dB A YE2EU072 53 4 YE2CE072 61 2 YE2EU090 57 6 YE2CE090 65 0 YE2EU120 61 5 YE2CE120 70 2 YE2EU150 64 4 YE2CE150 75 1 YE2EU180 66 2 YE2CE180 77 4 YE2EU216 70 0 YE2CE216 78 2 YE2EU240 70 6 YE2CE240 80 6 YE2EU300 72 8 YE2CE300 82 1 SOUND PRESSURE LEVEL 50HZ R407C UNITS 1M DISTANCE INDOOR dB A OUTDOOR dB A YE2EU072 53 4 YE2CE072 61 2 YE2EU090 57 6 YE2CE090 65 ...

Page 10: ...HOUT NOTICE Main Power Supply High Voltage High Voltage Terminal Block Circuit Breaker Low Voltage Terminal Block Low Voltage Terminal Block High Voltage Terminal Block Main Power Supply High Voltage Circuit Breaker 24 Volts Control Voltage 24 Volts Control Voltage COMMERCIAL DUCTED SPLITS 12 ...

Page 11: ...hat the isolators are easily accessible from the unit Connect the power cables to unit from isolator through the holes provided in the electrical panel of unit Route all control wires 24v or 240v separately through the knock out holes provided in the electrical panel of the units as shown in fig 16 Connect the ground lead to the ground lug to avoid any electrical shock For detailed description ple...

Page 12: ...r wiring at compressor terminal box Use tube cutter to cut suction and discharge lines at convenient place near compressor for easy reassemble to new compressor with copper slip Couplings if provided Remove accessory crankcase heater if used from compressor base Remove compressor hold down bolts and lift compressor out Carefully un braze suction discharge line piping or stubs from compressor If oi...

Page 13: ...operly then replace it For other type of filters please refer the manufacturers instructions Condenser coil Inspect condenser coil regularly Clean it properly if found dirty or clogged A dirty or clogged coil may cause increase in operating cost due to Increase in power consumption lead to burn out or failure of compressor at premature stage The condenser coil should be cleaned with brush vacuum c...

Page 14: ...G A Drawing Indoor units VERTICAL HORIZONTAL MOUNTING POSITION YE2EU 072 TO 180 LAYOUT IS SUBJECT TO CHANGE WITHOUT NOTICE COMMERCIAL DUCTED SPLITS 16 ...

Page 15: ...G A Drawing Outdoor units YE2CE 072 SINGLE CIRCUIT UNITS COMMERCIAL DUCTED SPLITS 17 ...

Page 16: ...G A Drawing Outdoor units GA DRAWING SPACE CLEARANCE YE2CE072 R22 50HZ R22 60HZ R407C 50HZ UNITS COMMERCIAL DUCTED SPLITS 18 ...

Page 17: ...G A Drawing Outdoor units GA DRAWING SPACE CLEARANCE YE2CE090 216 R22 50HZ R22 60HZ R407C 50HZ UNITS COMMERCIAL DUCTED SPLITS 19 ...

Page 18: ...G A Drawing Outdoor units GA DRAWING SPACE CLEARANCE YE2CE240 300 R22 50HZ R22 60HZ R407C 50HZ UNITS COMMERCIAL DUCTED SPLITS 20 ...

Page 19: ... 5 14 8 25 5 0 19 3 30 7 0 22 9 30 10 0 28 4 40 12 0 32 0 40 14 0 35 6 40 20 0 46 5 60 25 0 55 5 60 30 0 64 7 70 13 8 25 2 5 18 3 30 5 0 22 8 30 7 0 26 4 40 10 0 31 9 40 12 0 35 5 50 14 0 39 2 50 20 0 50 0 60 25 0 59 0 70 30 0 68 2 80 YE2EU072G 380 420 3 50 YE2EU090G 380 420 3 50 YE2EU120G 380 420 3 50 YE2EU150G 380 420 3 50 YE2EU180G 380 420 3 50 YE2EU216G 380 420 3 50 YE2EU240G 380 420 3 50 YE2E...

Page 20: ... 20 0 46 5 60 25 0 55 5 60 10 3 20 2 5 14 8 25 5 0 19 3 30 7 0 22 9 30 10 0 28 4 40 12 0 32 0 40 14 0 35 6 40 20 0 46 5 60 25 0 55 5 60 10 3 20 2 5 14 8 25 5 0 19 3 30 7 0 22 9 30 10 0 28 4 40 12 0 32 0 40 14 0 35 6 40 20 0 46 5 60 25 0 55 5 60 30 0 64 7 70 13 8 25 2 5 18 3 30 5 0 22 8 30 7 0 26 4 40 10 0 31 9 40 12 0 35 5 50 14 0 39 2 50 20 0 50 0 60 25 0 59 0 70 30 0 68 2 80 YE2EU072G 380 420 3 ...

Page 21: ... 7 40 0 60 10 49 4 60 12 55 8 70 14 62 0 80 20 80 8 100 25 96 5 110 18 0 30 2 5 25 9 40 5 33 8 50 7 40 0 60 10 49 4 60 12 55 8 70 14 62 0 80 20 80 8 100 25 96 5 110 30 112 2 130 24 0 40 2 5 31 9 50 5 39 8 60 7 46 0 70 10 55 4 70 12 61 8 80 14 68 0 90 20 85 5 100 25 102 5 120 30 118 2 140 YE2EU072T 208 230 3 60 YE2EU090T 208 230 3 60 YE2EU120T 208 230 3 60 YE2EU150T 208 230 3 60 YE2EU180T 208 230 3...

Page 22: ... 25 0 55 8 60 8 6 15 2 5 13 4 20 5 0 18 2 25 7 0 21 9 30 10 0 27 7 40 12 0 31 4 40 14 0 35 4 50 20 0 46 7 60 25 0 55 8 60 8 6 15 2 5 13 4 20 5 0 18 2 25 7 0 21 9 30 10 0 27 7 40 12 0 31 4 40 14 0 35 4 50 20 0 46 7 60 25 0 55 8 60 30 0 64 7 70 15 0 25 2 5 19 8 30 5 0 24 5 40 7 0 28 3 40 10 0 34 0 50 12 0 37 8 50 14 0 41 7 50 20 0 53 0 70 25 0 62 5 80 30 0 72 0 80 YE2EU072E 380 3 60 YE2EU090E 380 3 ...

Page 23: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications COMMERCIAL DUCTED SPLITS 25 ...

Page 24: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications WIRING DIAGRAM FOR OUTDOOR UNITS HEAT PUMP YE2CE072 YE2CE216 COMMERCIAL DUCTED SPLITS 26 ...

Page 25: ...WIRING DIAGRAM INDOOR UNITS Unit Specifications WIRING DIAGRAM FOR INDOOR UNIT HEAT PUMP ALL MODELS COMMERCIAL DUCTED SPLITS 27 ...

Page 26: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications WIRING DIAGRAM FOR OUTDOOR UNITS COOL YE2CE240 YE2CE300 COMMERCIAL DUCTED SPLITS 28 ...

Page 27: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications WIRING DIAGRAM FOR OUTDOOR UNITS COOL YE2CE072 YE2CE216 COMMERCIAL DUCTED SPLITS 29 ...

Page 28: ...Unit Specifications WIRING DIAGRAM INDOOR UNITS WIRING DIAGRAM FOR INDOOR UNITS COOL ALL MODELS COMMERCIAL DUCTED SPLITS 30 ...

Page 29: ...U15154 3IAU15M04 3IAU15M02 3IAU15097 35 WIRING DIAGRAM 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11666 1BCO11666 Spare Parts List INDOOR UNITS 380 420V 3PH 50HZ R22 S DESCRIPTION COMMON PARTS YE2EU072G YE2EU090G YE2EU120G YE2EU150G YE2EU180G YE2EU216G YE2EU240G YE2EU300G 1 BLOWER CONTACTOR 1BCE04029 1BCE04029 1BCE04029 1BCE04029 1BCE04029 1BCE04029 1BCE04029 1BCE04027 OVER LO...

Page 30: ...S DESCRIPTION PARTS COMMON YE2CE072E YE2CE090E YE2CE120E YE2CE150E YE2CE180E YE2CE216E YE2CE240E YE2CE300E 1 COMPRESSOR SCROLL 1BCC17041 1BCC09014 1BCC08016 1BCC17041 1BCC17062 1BCC17042 1BCC17044 1BCC17043 2 COMP CONTACTOR 1BCE04027 1BCE04027 1BCE04027 1BCE04027 1BCE04025 1BCE04025 1BCE04025 1BCE04023 OVER LOAD RELAY ELEMENT 1BCE09031 1BCE09027 3 COND FAN CONTACTOR 1BCE04029 1BCE04029 4 HP SWITCH...

Page 31: ...UTDOOR UNITS 208 230V 3PH 60HZ R22 S DESCRIPTION PARTS COMMON YE2CE072T YE2CE090T YE2CE120T YE2CE150T YE2CE180T YE2CE216T YE2CE240T YE2CE300T 1 COMPRESSOR SCROLL 1BCC17019 1BCC10006 1BCC11023 1BCC17019 1BCC17064 1BCC17050 1BCC17014 1BCC17039 2 COMP CONTACTOR 1BCE04025 1BCE04025 1BCE04025 1BCE04025 1BCE04023 1BCE04023 1BCE04021 1BCE04021 OVER LOAD RELAY ELEMENT 1BCE09028 1BCE09028 3 COND FAN CONTAC...

Page 32: ...149 3IAU15019 3IAU15155 3IAU15153 3IAU15153 3IAU15M03 3IAU15M01 3IAU15096 34 COND COIL RHS 3IAU15150 3IAU15020 3IAU15156 3IAU15154 3IAU15154 3IAU15M04 3IAU15M02 3IAU15097 35 WIRING DIAGRAM 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11666 1BCO11666 S DESCRIPTION COMMON PARTS YE2EU072G YE2EU090G YE2EU120G YE2EU150G YE2EU180G YE2EU216G YE2EU240G YE2EU300G 1 BLOWER CONTACTOR 1BCE0...

Page 33: ... EXPLODED VIEW OF INDOOR UNIT YE2EU 072 090 120 150 180 216 240 ALL VOLTAGES COOL ELECTRIC HEATER HEAT PUMP EXPLODED VIEW INDOOR UNIT YE2EU 300 ALL VOLTAGES COOL ELECTRIC HEATER HEAT PUMP COMMERCIAL DUCTED SPLITS 35 ...

Page 34: ...Exploded View EXPLODED VIEW ODU YE2CE072 ALL VOLTAGES COOL HEAT PUMP EXPLODED VIEW OUTDOOR UNIT YE2CE 090 120 150 180 216 ALL VOLTAGES COOL HEAT PUMP COMMERCIAL DUCTED SPLITS 36 ...

Page 35: ...Exploded View EXPLODED VIEW OUTDOOR UNIT YE2CE240 300 ALL VOLTAGES COOL HEAT PUMP COMMERCIAL DUCTED SPLITS 37 ...

Page 36: ...ompressor Air in system Condenser coil dirty or restricted Dirty air filter Dirty condenser coil Refrigerant overcharged Air in system Condenser air restricted or air short cycling Low refrigerant charge Compressor valve leaking Restriction in liquid tube High head load Compressor valves leaking Refrigerant overcharged Check wiring and repair or replace Determine cause replace compressor Determine...

Page 37: ......

Reviews: