Unit Specification
MODEL
V-Ph-Hz
Electric Heater
MCA
MOCP
Kw
Amps
Amps
MODEL
V-Ph-Hz
CURRENT
MCA
MOCP
NOTE: KW: Kilo watts Electric heating. FLA: Full Load Amps MCA: Minimum Circuit Amps. MOCP: Maximum Over Current Protection
ELECTRICAL DATA INDOOR UNITS 407C (50HZ - "G" VOLTAGE)
…
3.4
10
2.5
7.9
10
5.0
12.4
15
7.0
16.0
20
10.0
21.5
25
12.0
26.4
30
…
3.4
10
2.5
7.9
10
5.0
12.4
15
7.0
16.0
20
10.0
21.5
25
12.0
26.4
30
14.0
28.8
30
…
5.9
10
2.5
10.4
15
5.0
14.9
20
7.0
18.5
25
10.0
24.0
30
12.0
27.6
30
14.0
31.3
40
20.0
42.2
50
…
5.9
10
2.5
10.4
15
5.0
14.9
20
7.0
18.5
25
10.0
24.0
30
12.0
27.6
30
14.0
31.3
40
20.0
42.2
50
…
10.3
20
2.5
14.8
25
5.0
19.3
30
7.0
22.9
30
10.0
28.4
40
12.0
32.0
40
14.0
35.6
40
20.0
46.5
60
25.0
55.5
60
…
10.3
20
2.5
14.8
25
5.0
19.3
30
7.0
22.9
30
10.0
28.4
40
12.0
32.0
40
14.0
35.6
40
20.0
46.5
60
25.0
55.5
60
…
10.3
20
2.5
14.8
25
5.0
19.3
30
7.0
22.9
30
10.0
28.4
40
12.0
32.0
40
14.0
35.6
40
20.0
46.5
60
25.0
55.5
60
30.0
64.7
70
…
13.8
25
2.5
18.3
30
5.0
22.8
30
7.0
26.4
40
10.0
31.9
40
12.0
35.5
50
14.0
39.2
50
20.0
50.0
60
25.0
59.0
70
30.0
68.2
80
YE2EU072G
380 - 420/3/50
YE2EU090G
380 - 420/3/50
YE2EU120G
380 - 420/3/50
YE2EU150G
380 - 420/3/50
YE2EU180G
380 - 420/3/50
YE2EU216G
380 - 420/3/50
YE2EU240G
380 - 420/3/50
YE2EU300G
380 - 420/3/50
ELECTRICAL DATA OUTDOOR UNITS R407C ( 50HZ- "G" VOLTAGE )
YE2CE072G
380 - 420 / 3 / 50
22.1
40
YE2CE090G
380 - 420 / 3 / 50
25.7
40
YE2CE120G
380 - 420 / 3 / 50
30.2
40
YE2CE150G
380 - 420 / 3 / 50
43.9
60
YE2CE180G
380 - 420 / 3 / 50
45.9
60
YE2CE216G
380 - 420 / 3 / 50
50.2
70
YE2CE240G
380 - 420 / 3 / 50
55.9
80
YE2CE300G
380 - 420 / 3 / 50
73.7
100
COMMERCIAL DUCTED SPLITS
22
Summary of Contents for YE2CE 072
Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL York Taurus Commercial Ducted Splits 2 ...
Page 15: ...G A Drawing Outdoor units YE2CE 072 SINGLE CIRCUIT UNITS COMMERCIAL DUCTED SPLITS 17 ...
Page 23: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications COMMERCIAL DUCTED SPLITS 25 ...
Page 37: ......