SECTION 6 – COMMISSIONING
FORM 201.26-NM1
ISSUE DATE: 1/19/2018
JOHNSON CONTROLS
113
6
FORM 201.26-CL1
ISSUE DATE: 3/28/2013
D. CHECKING SUPERHEAT AND SUBCOOLING
The subcooling temperature of each system can
be calculated by recording the temperature of the
liquid line at the outlet of the condenser and sub-
tracting it from the liquid line saturation tempera-
ture at the liquid stop valve (liquid line saturation
temp. is converted from a temperature/pressure chart).
Example:
Liquid line pressure =
325 PSIG converted to temp. 101 °F
Minus liquid line temp. -86 °F
Subcooling = 15 °F
The subcooling should be adjusted to 15 °F at design
conditions.
1. Record the liquid line pressure and its corresponding
temperature, liquid line temperature and subcooling
below: ......................................................................
SYS 1 SYS 2
Liq Line Press = ––––––– ––––––– PSIG
Saturated Temp = ––––––– ––––––– °F
Liq Line Temp = ––––––– ––––––– °F
Subcooling = ––––––– ––––––– °F
After the subcooling is verified, the suction super
-
heat should be checked. The superheat should be
checked only after steady state operation of the chill-
er has been established, the leaving water tempera-
ture, and the unit is running in a fully loaded condition.
Correct superheat setting for a system is 10°F - 15°F
(5.56°C - 8.33 °C) 18" (46 cm) from the heat exchanger.
Superheat should typically be set for not less than
10°F with only a single compressor running on a
circuit.
The superheat is calculated as the difference
between the actual temperature of the returned refriger-
ant gas in the suction line entering the compressor and
the temperature corresponding to the suction pressure
as shown in a standard pressure/temperature chart.
Example:
Suction Temp = 46 °F
minus Suction Press
105 PSIG converted to Temp -34 °F
Superheat = 12 °F
When adjusting the expansion valve (TXV only), the
adjusting screw should be turned not more than one
turn at a time, allowing sufficient time (approximately
15 minutes) between adjustments for the system and
the thermal expansion valve to respond and stabilize.
Assure that superheat is set at a minimum of 10°F (5.56
°C) with a single compressor running on each circuit.
2. Record the suction temperature, suc-
tion pressure, suction saturation tempera-
ture, and superheat of each system below:
SYS 1 SYS 2
Suction Temp = ––––––– ––––––– PSIG
Suction Pressure = ––––––– ––––––– °F
Saturation Temp = ––––––– ––––––– °F
Superheat = ––––––– ––––––– °F
E. LEAK CHECKING
Leak check compressors, fittings, and piping to en
-
sure no leaks. ...............................................................
If the unit is functioning satisfactorily during the ini-
tial operating period, no safeties trip and the compres-
sors cycle to control water temperature to setpoint,
the chiller is ready to be placed into operation.
P.O. Box 1592, York, Pennsylvania USA 17405-1592
800-861-1001
Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2013
www.johnsoncontrols.com
ALL RIGHTS RESERVED
Form 201.26-CL1 (313)
Issue Date: March 28, 2013
Supersedes:201.26-CL1 (409)
Summary of Contents for YCWL0056SE
Page 4: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 30 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 146: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 146 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 154: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 154 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 168: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 168 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 186: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 186 NOTES...