99
Dry Contact
A dry contact may also be used to offset temperature.
This allows a single offset whenever the contact is closed.
The offset is determined by the adjustment of the R11
potentiometer on the Remote Reset Board. Adjust the
potentiometer as needed to obtain the desired offset.
Jumper JU1 must be IN. All other jumpers must be OUT.
Program the REMOTE RESET TEMP SETPOINT
RANGE (page 84) for 40°F which will allow the R11 pot
to be adjusted for an offset of as much as 20°F when the
contact is closed.
The dry contact should be connected directly to the P1-1
(J1-1) and P1-2 (J1-2) terminals on the Remote Reset
Board (Fig. 35).
NOTE: The coil of the controls used for reset must be
suppressed. Use YORK PIN 031-00808-000 sup-
pressor.
The Remote Setpoint Reset will not operate when
a Remote Control Center Option is connected
to the Micropanel. The Remote Control Center
will always determine the setpoint.
FIG. 35
REMOTE RESET BOARD
LD02360