Subject to change without notice. Printed in U.S.A.
413437-YTG-C-0908
Copyright
©
2008 by Johnson Controls, Inc. All rights reserved.
Supersedes: 413437-YTG-B-0608
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
YCJF60S41S1
INDOOR COIL MODEL NO.
FC/MC/PC62
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
54.5 57.8 56.7 62.8 68.7 55.3 59.1 58.5 64.7 69.7 56.1 60.4 60.2 66.6 70.7
S.C.
54.0 49.2 40.9 40.7 32.5 56.2 52.4 43.1 42.9 34.1 58.5 55.7 45.3 45.1 35.8
KW
2.7 2.7 2.6 2.7 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
75
T.C.
52.7 55.6 54.4 60.5 66.0 54.8 56.8 56.1 62.1 66.9 56.9 58.0 57.7 63.7 67.9
S.C.
52.3 48.1 39.9 39.8 31.5 54.3 51.1 42.2 41.9 33.1 56.4 54.2 44.4 44.1 34.7
KW
3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1
85
T.C.
50.8 53.5 52.2 58.1 63.3 54.3 54.5 53.7 59.5 64.2 57.7 55.6 55.2 60.8 65.1
S.C.
50.6 47.1 38.9 38.9 30.5 52.4 49.9 41.2 41.0 32.1 54.3 52.7 43.6 43.0 33.6
KW
3.5 3.6 3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5
95
T.C.
49.0 51.4 50.0 55.8 60.5 53.7 52.3 51.3 56.8 61.4 58.4 53.2 52.6 57.9 62.3
S.C.
48.9 46.0 37.9 38.1 29.5 50.5 48.6 40.3 40.0 31.0 52.2 51.2 42.7 41.9 32.6
KW
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
105
T.C.
46.4 48.2 46.9 52.5 57.0 50.0 49.3 48.1 53.3 58.0 53.7 50.4 49.3 54.2 59.0
S.C.
46.5 44.6 36.7 36.5 28.1 48.0 47.0 39.0 38.5 29.6 49.5 49.3 41.2 40.5 31.1
KW
4.8 4.8 4.8 4.7 4.7 4.8 4.8 4.8 4.7 4.7 4.7 4.8 4.8 4.7 4.7
115
T.C.
43.8 45.2 43.9 49.3 53.6 46.5 46.4 45.0 50.0 54.7 49.1 47.6 46.1 50.7 55.9
S.C.
44.1 43.3 35.5 35.0 26.8 45.5 45.4 37.6 37.1 28.3 46.9 47.5 39.8 39.2 29.7
KW
5.6 5.6 5.7 5.4 5.4 5.5 5.5 5.6 5.4 5.3 5.5 5.5 5.5 5.4 5.3
125
T.C.
41.3 42.2 40.8 46.0 50.2 42.9 43.5 41.9 46.6 51.5 44.5 44.9 42.9 47.2 52.7
S.C.
41.8 41.9 34.3 33.5 25.5 43.1 43.8 36.3 35.7 26.9 44.4 45.6 38.3 37.8 28.3
KW
6.4 6.4 6.5 6.1 6.0 6.3 6.3 6.4 6.1 6.0 6.2 6.2 6.3 6.1 6.0
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC/PC60
0.96 0.98 1.00
–
HC60
0.96 0.98 1.00
AV/SV60
–
0.97 0.99 0.97
MV20D
FC/MC60D
0.97 0.99 0.98
MA20D
FC/MC62D
1.00 1.00 1.00
MV20D
FC/MC62D
1.01 1.01 0.98
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P(C,V)9*D20
HC60D
0.95 0.93 0.97
PV8*C20
HD60
0.99 0.99 0.99
P(C,V)9*C20
HD60
0.99 0.99 0.98
P(C,V)9*D20
HD60
0.98 0.97 0.97
PV8*C20
FC/MC62D
1.00 1.00 0.99
P(C,V)9*C20
FC/MC62D
0.98 0.97 0.98
P(C,V)9*D20
FC/MC62D
0.99 0.96 0.97
Y*(8,L)C*C20
FC/MC62D
0.99 0.97 0.95
Y*9C*C20
FC/MC62D
0.98 0.96 0.98
Y*9C*D20
FC/MC62D
0.99 0.97 0.97
Y*9C*D20
HC60
0.96 0.92 0.97
Y*(8,L)C*C20
HD60
0.99 0.98 0.96
Y*9C*C20
HD60
1.00 0.98 0.98
Y*9C*D20
HD60
0.99 0.96 0.98
G*9V*C20
FC/MC62D
0.98 0.96 0.98
G*9V*D20
FC/MC62D
0.99 0.97 0.97
G*9V*D20
HC60
0.96 0.92 0.97
G*9V*C20
HD60
1.00 0.98 0.98
G*9V*D20
HD60
0.99 0.96 0.98