413437-YTG-C-0908
28
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on Page 29.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
YCJF48S41S1
INDOOR COIL MODEL NO.
FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
44.1 45.2 43.0 47.2 47.3 44.2 45.3 43.9 47.4 47.9 44.2 45.3 44.8 47.6 48.5
S.C.
43.7 39.0 33.0 31.2 24.2 44.3 40.6 34.5 32.2 24.8 44.9 42.3 36.0 33.2 25.5
KW
2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3
75
T.C.
42.6 43.5 41.7 45.7 46.9 43.0 43.8 42.5 46.1 47.5 43.5 44.1 43.2 46.5 48.2
S.C.
42.4 39.0 33.0 31.3 24.3 43.3 40.8 34.6 32.6 25.0 44.1 42.6 36.3 33.9 25.7
KW
2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6
85
T.C.
41.0 41.9 40.4 44.1 46.5 41.9 42.4 41.0 44.8 47.2 42.7 42.9 41.6 45.4 47.9
S.C.
41.1 38.9 32.9 31.4 24.3 42.2 40.9 34.7 33.0 25.2 43.4 42.9 36.6 34.6 26.0
KW
2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9
95
T.C.
39.5 40.2 39.1 42.6 46.0 40.7 41.0 39.5 43.5 46.8 42.0 41.8 40.0 44.3 47.6
S.C.
39.8 38.9 32.8 31.5 24.4 41.2 41.1 34.8 33.4 25.3 42.6 43.2 36.9 35.2 26.3
KW
3.1 3.2 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2 3.1 3.2 3.1 3.2 3.2
105
T.C.
37.1 37.6 36.0 39.8 43.4 38.3 38.6 36.6 40.6 44.1 39.5 39.6 37.2 41.4 44.8
S.C.
37.3 36.8 31.4 30.5 23.5 38.6 38.7 33.5 32.5 24.6 40.0 40.5 35.5 34.4 25.7
KW
3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.6 3.7
115
T.C.
34.9 35.0 33.0 37.1 40.8 36.0 36.3 33.7 37.8 41.5 37.1 37.5 34.4 38.5 42.1
S.C.
34.8 34.8 30.0 29.5 22.7 36.2 36.4 32.1 31.6 24.0 37.5 37.9 34.2 33.6 25.2
KW
4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.1
125
T.C.
32.6 32.5 30.1 34.4 38.2 33.6 33.9 30.8 35.0 38.8 34.6 35.4 31.6 35.7 39.5
S.C.
32.4 32.9 28.7 28.4 21.9 33.7 34.1 30.8 30.6 23.3 34.9 35.3 32.9 32.9 24.6
KW
4.4 4.4 4.4 4.5 4.6 4.4 4.4 4.4 4.5 4.6 4.5 4.5 4.4 4.5 4.6
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC/PC48
1.00 1.00 1.00
–
FC/MC62
1.01 1.00 1.00
–
HD48
1.00 1.00 1.00
–
HD60
1.02 1.02 1.00
AHP/SHP60
–
0.95 0.94 0.97
AV/SV48
–
0.95 0.94 0.96
AV/SV60
–
0.95 0.94 0.96
F4FV060
–
0.95 0.94 0.96
F5FP048
–
1.01 1.04 0.97
F5FP060
–
0.95 0.95 0.98
MA16C
FC/MC48C
1.00 1.00 1.00
MA20D
FC/MC48D
1.00 1.00 1.00
MV16C
FC/MC48C
1.01 1.01 0.96
MV20D
FC/MC48D
1.01 1.01 0.96
MA16C
FC/MC60C
1.00 1.00 1.00
MA20D
FC/MC60D
1.00 1.00 1.00
MV20D
FC/MC60D
1.01 1.01 0.96
MA20D
FC/MC62D
1.01 1.00 1.00
MV20D
FC/MC62D
1.02 1.01 0.96