JOHNSON CONTROLS
FORM 201.23-EG1 (1013)
55
REFRIGERANT R-134A
HIGH EFFICIENCY
MODEL NUMBER (YCIV____ E/V)
GENERAL UNIT DATA
60Hz
0267
0287
0327
0357
NUMBER OF INDEPENDENT REFRIGERANT CIRCUITS
3
3
3
3
REFRIGERANT CHARGE, R-134A, CKT.-1/CKT.-2, KG.
84 / 84 / 77
84 / 84 / 105
84 / 84 / 105
105 / 105 / 105
OIL CHARGE, CKT.-1/CKT.-2, LITERS
19 / 19 / 15
19 / 19 / 19
19 / 19 / 19
19 / 19 / 19
GLYCOL CHARGE (43% CONCENTRATION), LITERS
0
0
0
0
COMPRESSORS, SEMIHERMETIC SCREW QTY PER CHILLER
3
3
3
3
CONDENSERS, HIGH EFFICIENCY FIN/TUBE WITH INTEGRAL SUBCOOLER
TOTAL CHILLER COIL FACE AREA, M
2
38
44
44
49
NUMBER OF ROWS
3
3
3
3
FINS PER METER
669
669
669
669
CONDENSER FANS
NUMBER, CKT.-1/CKT.-2
05/05/04
05/05/06
05/05/06
06/06/06
LOW NOISE FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
TOTAL CHILLER AIRFLOW, L/SEC.
85904
98176
98176
110448
ULTRA QUIET FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
TOTAL CHILLER AIRFLOW, L/SEC.
85904
98176
98176
110448
DUAL SPEED FANS - NORMAL SPEED
FAN, KWI
1.5
1.5
1.5
1.5
TOTAL CHILLER, M
3
/S
73
83
83
93
DUAL SPEED FANS - LOWER SPEED
FAN, KWI
1.5
1.5
1.5
1.5
TOTAL CHILLER, M
3
/S
56
63
63
71
HIGH STATIC FANS
FAN, KWI
3.7
3.7
3.7
3.7
TOTAL CHILLER, M
3
/S
92
117
117
129
EVAPORATOR, DIRECT EXPANSION
WATER VOLUME, LITERS
764.6
764.6
893.3
893.3
MAXIMUM WATER SIDE PRESSURE, BAR
10
10
10
10
MAXIMUM REFRIGERANT SIDE PRESSURE, BAR
16
16
16
16
MINIMUM CHILLED WATER FLOW RATE, L/SEC.
16
16
19
19
MAXIMUM CHILLED WATER FLOW RATE, L/SEC.
76
76
76
76
WATER CONNECTIONS, INCHES
10
10
10
10
Contact your nearest Johnson Controls Sales Office for weight data.
Summary of Contents for YCIV0157E/V
Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...