JOHNSON CONTROLS
FORM 201.23-EG1 (1013)
11
TEMPERATURE AND FLOWS
(SI Units)
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(L/S)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
60 HZ
0157(S/P)
4.4
15.6
8.8
42.6
-17.8
51.7
0157(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0177(S/P)
4.4
15.6
10.1
47.3
-17.8
51.7
0177(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0187(S/P)
4.4
15.6
10.1
47.3
-17.8
51.7
0187(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0197(E/V)
4.4
15.6
11.4
47.3
-17.8
51.7
0207(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0207(E/V)
4.4
15.6
11.4
47.3
-17.8
51.7
0227(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0227(E/V)
4.4
15.6
11.4
47.3
-17.8
51.7
0247(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0247(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0267(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0267(E/V)
4.4
15.6
11.4
50.5
-17.8
51.7
0287(S/P)
4.4
15.6
15.8
75.7
-17.8
51.7
0287(E/V)
4.4
15.6
15.8
75.7
-17.8
51.7
0307(S/P)
4.4
15.6
18.9
75.7
-17.8
51.7
0327(E/V)
4.4
15.6
18.9
75.7
-17.8
51.7
0357(S/P)
4.4
15.6
18.9
75.7
-17.8
51.7
0357(E/V)
4.4
15.6
18.9
75.7
-17.8
51.7
0397(S/P)
4.4
15.6
18.9
75.7
-17.8
51.7
0457(P)
4.4
15.6
25.2
88.2
-17.8
51.7
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
Summary of Contents for YCIV0157E/V
Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...