1.03 DELIVERY AND HANDLING
G. Unit shall be delivered to job site fully assembled, and charged with refrigerant and oil
by the Manufacturer. (Contractor is responsible for providing and installing the refriger-
ant charge including the charge required for the field installed interconnecting piping.
Chiller components shall ship with a dry nitrogen holding charge – Remote Evaporator
option).
H.
Unit shall be stored and handled per Manufacturer’s instructions.
PART 2 - PRODUCTS
2.01 CHILLER MATERIALS AND COMPONENTS
A. General: Install and commission, as shown on the schedules and plans, factory assem-
bled, charged, and tested air cooled scroll compressor chiller(s) as specified herein.
Chiller shall be designed, selected, and constructed using a refrigerant with Flamma-
bility rating of “1”, as defined by ANSI/ASHRAE STANDARD - 34 Number Designation
and Safety Classification of Refrigerants. Chiller shall include, but is not limited to a
complete system with a single refrigerant circuit 35 tons (123kW) and below, and not
less than two refrigerant circuits above 35 tons (123kW), scroll compressors, direct
expansion type evaporator, air-cooled condenser, refrigerant, lubrication system, inter-
connecting wiring, safety and operating controls including capacity controller, control
center, motor starting components, and special features as specified herein or required
for safe, automatic operation.
B. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTM B117, 1000
hour, 5% salt spray test, yields minimum ASTM 1654 rating of “6”. Add Wire Panels
of heavy gauge, welded wire-mesh, coated to resist corrosion, to protect condenser
coils from incidental damage and restrict unauthorized access to internal components.
Factory installed.
2.02 COMPRESSORS
Compressors: Shall be hermetic, scroll-type, including:
1. Compliant design with axial and radial sealing.
2.
Refrigerant flow through the compressor with 100% suction cooled motor.
3. Large suction side free volume and oil sump to provide liquid handling capability.
4. Compressor crankcase heaters to provide extra liquid migration protection.
5. Annular discharge check valve and reverse vent assembly to provide low pressure
drop, silent shutdown and reverse rotation protection.
6. Initial Oil charge.
7. Oil Level sight glass.
8. Vibration isolator mounts for compressors.
9. Brazed-type connections for fully hermetic refrigerant circuits.
Guide Specifications (Cont'd)
Summary of Contents for YCAL Series
Page 4: ...JOHNSON CONTROLS FORM 150 67 EG1 219 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 47: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 47 Unit Dimensions Cont d YCAL0028 LD18674...
Page 55: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 55 45 1 8 18 1 2 LD18682 Unit Dimensions Cont d YCAL0052...
Page 57: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 57 Unit Dimensions Cont d YCAL0056 45 1 8 16 3 4 LD18684...
Page 63: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 63 Unit Dimensions Cont d YCAL0022 SI LD18692...
Page 73: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 73 Unit Dimensions Cont d YCAL0052 SI 424 LD18702...
Page 88: ...JOHNSON CONTROLS FORM 150 67 EG1 219 88 Power Wiring Single Circuit ld18707...
Page 89: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 89 Power Wiring Single Circuit Cont d...
Page 90: ...JOHNSON CONTROLS FORM 150 67 EG1 219 90 Power Wiring Single Circuit Cont d...
Page 91: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 91 LD18746 Power Wiring Dual Circuit...