FORM 150.67-EG1 (219)
JOHNSON CONTROLS
13
Selection Data
GUIDE TO SELECTION
Capacity ratings for the YCAL Packaged Air-Cooled Liquid Chillers, shown on
pages 20
through 37
cover the majority of design applications for these units. For unusual appli-
cations or uses beyond the scope of this catalog, please consult your nearest Johnson
Controls Office or sales representative.
SELECTION RULES
1.
Ratings
– Ratings may be interpolated, but must not be extrapolated. The
Ratings
on page 20
and the
Design Parameters on page 17
indicate the limits of ap-
plication for these chillers.
2.
Cooler Water
– Ratings are based upon 2.4 GPM per ton which is equal to a 10°F
chilled water range and a 0.0001 fouling factor for the cooler at sea level. Tables on
pages 20 through 37
give capacity, compressor kW required, cooler GPM and unit
EER.
3.
Condenser
– Ratings are given in terms of air on condenser in degrees Fahrenheit.
4.
Copper Fin Condenser Ratings
– Since the thermal conductivity of copper is
slightly higher than aluminum, apply the following corrections to the standard rat-
ings. Tons x 0.97 and compressor kW x 0.99.
5.
Performance Data Correction Factors
– Ratings are based on 0.0001 cooler foul-
ing factor, 10°F chilled water range and at sea level. For operation at different condi-
tions, apply the appropriate correction factor from the following table.
FOULING FACTOR
ALTITUDE
TEMP SPLIT
0.0001
0.0003
TONS
COMPR KW
TONS
COMPR KW
SEA LEVEL
8
0.990
0.998
0.979
0.996
10
1.000
1.000
0.991
0.998
12
1.012
1.003
1.002
1.001
14
1.021
1.005
1.012
1.003
2000 FT.
8
0.987
1.005
0.978
1.003
10
0.997
1.008
0.988
1.006
12
1.009
1.010
1.000
1.008
14
1.018
1.012
1.009
1.010
4000 FT.
8
0.983
1.014
0.975
1.012
10
0.994
1.016
0.985
1.014
12
1.005
1.019
1.111
1.017
14
1.014
1.021
1.006
1.019
6000 FT.
8
0.980
1.023
0.971
1.021
10
0.990
1.025
0.982
1.023
12
1.002
1.028
0.993
1.026
14
1.011
1.030
1.002
1.028
Summary of Contents for YCAL Series
Page 4: ...JOHNSON CONTROLS FORM 150 67 EG1 219 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 47: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 47 Unit Dimensions Cont d YCAL0028 LD18674...
Page 55: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 55 45 1 8 18 1 2 LD18682 Unit Dimensions Cont d YCAL0052...
Page 57: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 57 Unit Dimensions Cont d YCAL0056 45 1 8 16 3 4 LD18684...
Page 63: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 63 Unit Dimensions Cont d YCAL0022 SI LD18692...
Page 73: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 73 Unit Dimensions Cont d YCAL0052 SI 424 LD18702...
Page 88: ...JOHNSON CONTROLS FORM 150 67 EG1 219 88 Power Wiring Single Circuit ld18707...
Page 89: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 89 Power Wiring Single Circuit Cont d...
Page 90: ...JOHNSON CONTROLS FORM 150 67 EG1 219 90 Power Wiring Single Circuit Cont d...
Page 91: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 91 LD18746 Power Wiring Dual Circuit...