FORM 150.67-EG1 (219)
JOHNSON CONTROLS
101
P. Power Factor Correction Capacitors: Provided to correct unit compressor factors to a
0.90-0.95.
Q. Condenser Coil Environmental Protection:
1.
Pre-Coated: Epoxy coated aluminum fin stock to guard from corrosive agents and
insulate against galvanic potential. For mild seashore or industrial locations.
2.
Copper Fin: Provide copper fins in lieu of aluminum.
3. Post-Coated Dipped: Dipped-cured coating on condenser coils for seashore and
other corrosive applications (with the exception of strong alkalis, oxidizers, and wet
bromine, chlorine and fluorine in concentrations greater than 100ppm).
R. Protective Chiller Panels (Factory or Field Mounted)
1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabi-
net, over external condenser coil faces.
2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, PVC-coated to resist cor-
rosion, to protect condenser coils from incidental damage and restrict unauthorized
access to internal components.
3. Louvered Panels (full unit): Painted steel as per remainder of unit cabinet, to protect
condenser coils from incidental damage, visually screen internal components, and
prevent unauthorized access to internal components.
4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces,
painted as per remainder of unit cabinet. Heavy gauge, welded wire-mesh, coated
to resist corrosion, around base of machine to restrict unauthorized access.
S. Flow Switch (Field-mounted): Vapor proof SPDT, NEMA 4X switch ( ___150 PSIG or
___300 PSIG), -20°F to 250°F.
T.
Differential Pressure Switch: Alternative to an above mentioned flow switch. Pretemp
-
co model DPS300A-P40PF-82582-5 (300 psi max. working pressure) SPDT 5 amp
125/250VAC switch, Range 3-45 PSIG (0.2-3 barg), deadband 0.5 - 0.8 psi, with 1/4”
NPTE Pressure Connections.
U. Evaporator options:
1. Provide 1½" cooler insulation in lieu of standard ¾".
2. Provide DX Cooler with 300 PSIG water-side design working pressure in lieu of
standard 150 PSIG.
3.
Provide Raised Face Flanges for field installation on cooler nozzles and field piping:
a. 150 PSIG, welded Flanges.
b. 300 PSIG, welded Flanges.
V. Service Isolation valves: Service suction and discharge (ball type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve
in compliance with ASHRAE 15. (Factory-mounted.)
Guide Specifications (Cont'd)
Summary of Contents for YCAL Series
Page 4: ...JOHNSON CONTROLS FORM 150 67 EG1 219 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 47: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 47 Unit Dimensions Cont d YCAL0028 LD18674...
Page 55: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 55 45 1 8 18 1 2 LD18682 Unit Dimensions Cont d YCAL0052...
Page 57: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 57 Unit Dimensions Cont d YCAL0056 45 1 8 16 3 4 LD18684...
Page 63: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 63 Unit Dimensions Cont d YCAL0022 SI LD18692...
Page 73: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 73 Unit Dimensions Cont d YCAL0052 SI 424 LD18702...
Page 88: ...JOHNSON CONTROLS FORM 150 67 EG1 219 88 Power Wiring Single Circuit ld18707...
Page 89: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 89 Power Wiring Single Circuit Cont d...
Page 90: ...JOHNSON CONTROLS FORM 150 67 EG1 219 90 Power Wiring Single Circuit Cont d...
Page 91: ...FORM 150 67 EG1 219 JOHNSON CONTROLS 91 LD18746 Power Wiring Dual Circuit...