background image

3.2 Installation

3.2.1 Suspension bolts
(1) Consider the pipe direction, wiring and maintenance 
carefully, and choose the proper direction and location 
for installation.
(2) Install the suspension bolts as shown in Fig. 3.2 
below.

Fig. 3.2.1 Fixing the suspension bolts 

·

For the concrete

·

For the steel beam

·

For the wooden beam

150 to160mm

Screw in

100 to150kg

Steel bar

Concrete

Suspension bolts

(W3/8 or M10)

“  ” 

shaped steel beam

Wood rib 

60mm to 90mm 

Wooden beam

Nut 

Round washer

Square washer

Suspension bolts

7

3.2.2 The position of the suspension bolts and the pipes

(1) Mark the positions of the suspension bolts, the 
positions of the refrigerant pipes and the drain pipes.
(2) The dimensions are shown below.

Installation and Maintenance

·
·
·
·

·
·

·

·

·

Do

 

not

 

install

 

the

 

indoor

 

unit

 

in

 

a machinery

 

shop

Optimum air distribution is ensured.
The air path is not blocked.
Condensation can drain properly.
The ceiling is strong enough to bear the weight of the 

    indoor unit.

A false ceiling does not seem to be at an incline.
Sufficient clearance for maintenance and servicing 

is ensured.(See Fig.3.1.1,Fig3.1.2 )

Piping between the indoor and outdoor units is within 

the allowable limits.(refer to the installation of the 
outdoor unit )

The indoor unit, outdoor unit, power supply wiring 

and transmission wiring must be kept at least 1 meter 
away from televisions and radio,which prevents image 
interference and noise in those electrical appliances. 
(Noise may be generated depending on the conditions 
under which the electric wave is generated, even if a 
one-meter allowance is maintained.)

or

 

kitchen

 

where

 

vapor

 

from

 

oil

 

or

 

its

 

mist

 

flows to 

the

 

indoor

 

unit

.

The

 

oil

 

will

 

deposit

 

on

 

the

 

heat 

exchanger, thereby

 

reducing

 

the performance of the 

indoor unit, and

 

may

 

deform

 

and

 

in

 

the

 

worst

 

case, 

break

 

the

 

plastic

 

parts

 

of

 

the

 

indoor

 

unit.

·

Use suspension bolts to install the unit, check whether

or not the ceiling is strong enough to support the weight 
of the unit. If there is a risk that the ceiling is not strong 
enough, reinforce the ceiling before installing the unit. 
For bottom intake, replace the chamber lid and the 
intake-side flange in the procedure listed in fig. 
(1)Remove the intake-side flange,then remove the 

    chamber lid. Refer to Fig. 3.1.3 for the directions.

(2)Reattach the removed chamber lid in the orientation 
shown in Fig. 3.1.4, reattach the removed the intake-
side flange in the orientation shown in Fig. 3.1.4

Suspension bolts

(W3/8 or M10)

Nut 

Fig. 3.1.3

Fig. 3.1.4

Intake-side flange

Chamber lid

Intake-side flange

Chamber lid

Filter

(

invalid

 

for

Filter

(

invalid

 

for

 

some

 

models

)

some

 

models

)

.1

Air inlet

Air outlet

b

154

447

a

Model

Capacity (Btu/h)

a

b

9K/12K

937

900

18K

1207

1170

Summary of Contents for YAKN09BZNWEUH1

Page 1: ...0Hz T1 Cooling Only Model YAKN09BZNWEUH1 YAKN12BZNWEUH1 YEKN18BZNWEUH1 YEKN24BZNWEUH1 YEKN36BZNWEUH1 YEKN42BZMWEUH1 YGKN48BZMWEUH1 YGKN55BZMWEUH1 Model YAJN09BZNWETH1 YAJN12BZNWETH1 YEJN18BZNWETH1 YEJ...

Page 2: ...ditioner 2 Special Remarks 3 Troubleshooting 3 Diagram of Refrigerant Cycle Wiring 1 Refrigerant Flow Diagram 4 2 Electrical Wiring Diagram 4 Installation and Maintenance 1 Safety Notice 5 2 The Tools...

Page 3: ...not connect the grounding of this product to various kinds of air feeding ducts drain piping lightning protection facility as well as other piping lines to avoid receiving an electric shock and damag...

Page 4: ...lected The figures are based on the external views of the standard model Operation instruction will be further specified in remote controller s manual Please read it carefully before using this applia...

Page 5: ...er reducing heating performance When this happens a defrosting system of the air conditioner will operate At the same time the fan in the indoor unit stops or runs at a very low speed in some cases to...

Page 6: ...y valve Heat exchanger Liquid piping Heating cycle Cooling cycle INDOOR UNIT OUTDOOR UNIT Heat exchanger EEV Service valve Outdoor unit Outdoor unit Indoor unit Indoor unit Terminal Terminal Power sup...

Page 7: ...nces other than the specified refrigerant such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture resulting in injury If any r...

Page 8: ...ter Hammer Churn drill Knife or wire stripper Tube expander Inner hexagon spanner Tape measure 3 1 The Initial Check When moving the unit during or after unpacking make sure to lift it by holding its...

Page 9: ...nit power supply wiring and transmission wiring must be kept at least 1 meter away from televisions and radio which prevents image interference and noise in those electrical appliances Noise may be ge...

Page 10: ...the thread locker on the suspension to prevent the nuts from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed le...

Page 11: ...The connection positions of the tube Fig 4 2 The pipe diameter The refrigerant gas pipe The refrigerant liquid pipe 2 As shown in Fig 4 3 screw up the nuts with 2 spanners Fig 4 3 Screw up the nut to...

Page 12: ...ould be insulated because condensation may form there and cause water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the i...

Page 13: ...t The lid of the control box Fig 6 1 Remove the screws on the control box 11 Installation and Maintenance 6 Electrical Wiring When clamping the wiring use the included clamping material as shown in th...

Page 14: ...desired function code to rewrite the parameter values by pressing button and press button to confirm Press button to quit 1 2 3 4 5 V V V V V V V V M T M T M T If you still have any trouble please co...

Page 15: ...hat the wall and the supporting rack is strong enough to hold the weight of the appliance Release the set screws of the electric cover remove the electric cover if the valve cover is there either plea...

Page 16: ...e heat insulation effect Also be sure the condensed drain hose splits away from bundle and drips clear of the unit and the piping The two refrigerant tubes and electrical wire if local codes permit sh...

Page 17: ...e contact local technical service center of our company for further information Narrow pipe Hex wrench Wide pipe Service valve Bonnet of service valve Bonnet of narrow valve Bonnet of wide valve Indoo...

Page 18: ...ck Place the round crimp style terminals on the wires up to the covered part and secure in place When connecting the terminal block using a single core wire be sure to perform curing 3 When transmitti...

Page 19: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Reviews: