background image

9.2 Leak Test 

WARNING

Installation and Maintenance

15

Only after all the checking points have been checked 

the unit can be operated.
(A) Check and make sure that the resistance of the 
terminal to ground is more than 2M , otherwise, you 
cannot operate the unit before the electricity leakage 
point is found and repaired.
(B) Check and make sure that the stop valve has been 
opened before operating the unit.

·

Ω

The trial should be carried out according to the 
installation and maintenance manual.

Leak test all joints and valves of the indoor unit and 
outdoor unit with liquid soap. Checking of the orifice 
cap shouldn't be less than 30 seconds. Clean the 
liquid  soap  after the test in case that the color of 
the copper tube may change for erode.

9.3 Tidying Up the Piping

If the leak test turns out to be all right, preserve heat 
the joints of the indoor unit.
Straighten the connecting tubes and make them 
flush and fixed to the wall. Seal the space around the 
hole in the wall through which the pipes come out 
with gypsum.

9.4 Test Run

Make sure the power and unit run well then plug in.
Turn on the appliance and adjust it to Cooling, 
dehumidifying and Heating mode according to the 
room temperature. Check if the appliance can run 
well.

Installation of the appliance is generally finished after 
the above operations are done. If you still have any 
trouble, please contact local technical service center 
of our company for further information.

Narrow pipe

Hex wrench

Wide pipe

Service valve

Bonnet of service valve

Bonnet of narrow valve

Bonnet of wide valve

Indoor unit

Outdoor unit

Manifold 

valve

Pressure

gauge

Vacuum pump

 Fig.9.1

 Fig.9.2

9.Air purging and test run

Air and moisture remaining in the refrigerant system 
have undesirable effects. 
Therefore, they must be purged completely following the 
steps.

9.1 Air Purging with a Vacuum Pump

  (See 

Figure 9.1, Figure 9.2)
(1) Check that each pipe (both narrow and wide pipes 
between the indoor and outdoor units) have been 
properly connected and all wiring for the test run has 
been completed. Note that both narrow and wide pipe  
valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove 
the bonnet from the service valve.
(3) Connect a vacuum pump and service valve together 
tightly.
(4) Turn on the vacuum pump and  till the pressure is 
lower than 15Pa(or 1.5

×

10

-4

bar) for 5 minutes.

(5) With the vacuum pump still running,  disconnect  
pipe of vacuum pump from the service valve. Then stop 
the vacuum pump. 
(6) Replace the bonnet on the service valve and fasten it 
securely with an adjustable  wrench or box wrench. 
(7) Using an adjustable wrench or box wrench, remove 
the bonnet of both narrow and wide  valve.
(8) With the hex wrench, turn the wide and narrow pipe  
valves  stem counter clockwise to fully open the valves.
(9) Replace the bonnets on the wide and narrow valves 
and fasten it securely with an adjustable wrench or box 
wrench. 

Summary of Contents for YAKN09BZNWEUH1

Page 1: ...0Hz T1 Cooling Only Model YAKN09BZNWEUH1 YAKN12BZNWEUH1 YEKN18BZNWEUH1 YEKN24BZNWEUH1 YEKN36BZNWEUH1 YEKN42BZMWEUH1 YGKN48BZMWEUH1 YGKN55BZMWEUH1 Model YAJN09BZNWETH1 YAJN12BZNWETH1 YEJN18BZNWETH1 YEJ...

Page 2: ...ditioner 2 Special Remarks 3 Troubleshooting 3 Diagram of Refrigerant Cycle Wiring 1 Refrigerant Flow Diagram 4 2 Electrical Wiring Diagram 4 Installation and Maintenance 1 Safety Notice 5 2 The Tools...

Page 3: ...not connect the grounding of this product to various kinds of air feeding ducts drain piping lightning protection facility as well as other piping lines to avoid receiving an electric shock and damag...

Page 4: ...lected The figures are based on the external views of the standard model Operation instruction will be further specified in remote controller s manual Please read it carefully before using this applia...

Page 5: ...er reducing heating performance When this happens a defrosting system of the air conditioner will operate At the same time the fan in the indoor unit stops or runs at a very low speed in some cases to...

Page 6: ...y valve Heat exchanger Liquid piping Heating cycle Cooling cycle INDOOR UNIT OUTDOOR UNIT Heat exchanger EEV Service valve Outdoor unit Outdoor unit Indoor unit Indoor unit Terminal Terminal Power sup...

Page 7: ...nces other than the specified refrigerant such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture resulting in injury If any r...

Page 8: ...ter Hammer Churn drill Knife or wire stripper Tube expander Inner hexagon spanner Tape measure 3 1 The Initial Check When moving the unit during or after unpacking make sure to lift it by holding its...

Page 9: ...nit power supply wiring and transmission wiring must be kept at least 1 meter away from televisions and radio which prevents image interference and noise in those electrical appliances Noise may be ge...

Page 10: ...the thread locker on the suspension to prevent the nuts from loosening 1 During the installation please cover the unit with the plastic cloth to keep it clean 2 Make sure that the unit is installed le...

Page 11: ...The connection positions of the tube Fig 4 2 The pipe diameter The refrigerant gas pipe The refrigerant liquid pipe 2 As shown in Fig 4 3 screw up the nuts with 2 spanners Fig 4 3 Screw up the nut to...

Page 12: ...ould be insulated because condensation may form there and cause water leakage Drain piping passing indoors Drain sockets Referring the figure below insulate the drain socket and drain hose using the i...

Page 13: ...t The lid of the control box Fig 6 1 Remove the screws on the control box 11 Installation and Maintenance 6 Electrical Wiring When clamping the wiring use the included clamping material as shown in th...

Page 14: ...desired function code to rewrite the parameter values by pressing button and press button to confirm Press button to quit 1 2 3 4 5 V V V V V V V V M T M T M T If you still have any trouble please co...

Page 15: ...hat the wall and the supporting rack is strong enough to hold the weight of the appliance Release the set screws of the electric cover remove the electric cover if the valve cover is there either plea...

Page 16: ...e heat insulation effect Also be sure the condensed drain hose splits away from bundle and drips clear of the unit and the piping The two refrigerant tubes and electrical wire if local codes permit sh...

Page 17: ...e contact local technical service center of our company for further information Narrow pipe Hex wrench Wide pipe Service valve Bonnet of service valve Bonnet of narrow valve Bonnet of wide valve Indoo...

Page 18: ...ck Place the round crimp style terminals on the wires up to the covered part and secure in place When connecting the terminal block using a single core wire be sure to perform curing 3 When transmitti...

Page 19: ...nt possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use...

Reviews: