Auxiliary Heat Ratings
Auxiliary Heat Electrical Data
Model
Supply
Circuit
Heater Amps
Min Circuit Amp
Fuse (USA)
Fuse (CAN)
CKT BRK
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
EAS(H)4A
Single
13.7
15.8
17.9
20.5
20
20
20
20
20
20
EAM(H)5A
Single
17.3
20.0
26.7
30.0
30
30
30
30
30
30
EAM(H)8A
Single
27.5
31.7
39.3
44.6
40
45
40
45
40
45
EAM(H)10A
Single
34.7
40.0
48.3
55.0
50
60
50
60
50
60
EAL(H)10A
Single
34.7
40.0
53.3
60.0
60
60
60
60
60
60
EAL(H)15A
Single
52.0
60.0
75.0
85.0
80
90
80
90
70
100
L1/L2
34.7
40.0
53.3
60.0
60
60
60
60
60
60
L3/L4
17.3
20.0
21.7
25.0
25
25
25
25
20
30
EAL(H)20A
Single
69.3
80.0
96.7
110.0
100
110
100
110
100
100
L1/L2
34.7
40.0
53.3
60.0
60
60
60
60
60
60
L3/L4
34.7
40.0
43.3
50.0
45
50
45
50
40
50
All heaters rated single phase 60 cycle and include unit blower load
All fuses type “D” time delay (or HACR circuit breaker in USA)
Supply wire size to be determined by local codes
6/11/15
Model
kW
Stages
Btu/h
Min cfm
Model Size Compatibility
208V
230V
208V
230V
012
018
022
026 - 030 036 - 042 048 - 072
EAS(H)4A
2.9
3.8
1
9,700
12,900
250
•
EAM(H)5A
3.6
4.8
1
12,300 16,300 450
•
•
•
EAM(H)8A
5.7
7.6
2
19,400 25,900 550
•
•
•
EAM(H)10A
7.2
9.6
2
24,600 32,700 650
•
EAL(H)10A
7.2
9.6
2
24,600 32,700 1100
•
•
EAL(H)15A
10.8
14.4
2
36,900 49,100 1250
•
•
EAL(H)20A
14.4
19.2
2
49,200 65,500 1500
•
Order the “H” part number when installed on horizontal and vertical rear discharge units
Air flow level for auxiliary heat (Aux) must be above the minimum cfm in this table