Engineering Guide Speci

fi

 cations

Affinity & Affinity Advanced Series

1 - 6 Tons 60Hz

SD2500AK6      06/21 

62 

Page _____ of _____

General

Furnish and install York Water Source Heat Pumps, as indicated 
on the plans. Equipment shall be completely assembled, piped 
and internally wired. Capacities and characteristics as listed in 
the schedule and the specifications that follow. The reverse cycle 
heating/cooling units shall be either suspended type with horizontal 
air inlet and discharge or floor mounted type with horizontal air 
inlet and vertical upflow, downflow, or rear air discharge. Units 
shall be AHRI/ISO 13256-1 certified and listed by a nationally 
recognized safety-testing laboratory or agency, such as ETL 
Testing Laboratory. Each unit shall be computer run-tested at the 
factory with conditioned water and operation verified to catalog 
data. Each unit shall be mounted on a pallet and shipped in a 
corrugated box or stretch-wrapped. The units shall be designed to 
operate with entering liquid temperature between 20°F and 120°F 
[-6.7°C and 48.9°C].

Casing and Cabinet

The cabinet shall be fabricated from heavy-gauge galvanized 
steel and finished with corrosion-resistant powder coating. This 
corrosion protection system shall meet the stringent 1000 hour 
salt spray test per ASTM B117. The interior shall be insulated with 
1/2-inch thick, multi-density, cleanable aluminum foil coated glass 
fiber with edges sealed or tucked under flanges to prevent the 
introduction of glass fibers into the discharge air. Standard cabinet 
panel insulation must meet NFPA 90A requirements, air erosion 
and mold growth limits of UL-181, stringent fungal resistance 
test per ASTM-C1071 and ASTM G21, and shall meet zero level 
bacteria growth per ASTM G22. Unit insulation must meet these 
stringent requirements or unit(s) will not be accepted. 

One (horizontal) to two (vertical) blower and three compressor 
compartment access panels shall be ‘lift-out’ removable with supply 
and return ductwork in place. The front access panel shall be lift-out 
to provide easy access to the electrical/compressor section. The 
control box shall be hinged and removable to allow easy access 
to the compressor. The internal component layout shall provide for 
service access from the front side for restricted installations.

A duct collar shall be provided on the supply air opening. Standard 
size 2 in. [5.1 cm] MERV 11 pleated filters shall be provided with 
each unit. Vertical units shall have a return air filter rack/duct collar; 
the horizontal units shall have a filter bracket each field convertible 
from 2 in. [5.1 cm] to 1 in. [2.5 cm]. The upflow vertical (022-072) 
units shall have a removable insulated divider panel between the 
air handling section and the compressor section to minimize the 
transmission of compressor noise and to permit operational service 
testing without air bypass. Vertical units shall be supplied with 
left or right horizontal air inlet and top, bottom (022-072), or rear 
vertical (042-072) air discharge. Horizontal units shall be supplied 
with left or right air inlet and side or end air discharge.

The compressor shall be double isolation mounted using selected 
durometer grommets to provide vibration free compressor mounting.

The drain pan shall be of plastic construction to inhibit corrosion 
and bacterial growth. Drain outlet shall be located on pan as 
to allow complete and unobstructed drainage of condensate. 

The unit as standard will be supplied with solid-state electronic 
condensate overflow protection. Mechanical float switches WILL 
NOT be accepted. Vertical units shall be furnished with a PVC 
slip condensate drain connection and an internal factory installed 
condensate trap. 

Refrigerant Circuit

All units shall contain a sealed refrigerant circuit including a 
hermetic motor-compressor, discharge line muffler (022-072), 
bidirectional thermostatic expansion valve, finned tube air-to-
refrigerant heat exchanger, reversing valve, coaxial tube water-
to-refrigerant heat exchanger, optional hot water generator coil 
(018-072), and service ports.

Compressors shall be high-efficiency single speed rotary or 
scroll, or dual capacity scroll type designed for heat pump duty 
and mounted on vibration isolators. Compressor motors shall 
be single-phase PSC with overload protection. The finned tube 
air-to-refrigerant heat exchanger will be aluminum tube/fin or 
copper tube/aluminum fin and shall be sized for low-face velocity 
and constructed of lanced aluminum fins bonded to performance 
enhanced tubes in a staggered pattern not less than three rows 
deep for superior performance. The aluminum tube and fin air-to-
refrigerant heat exchanger has as optional to be electro-coated 
with AlumiSeal. The copper tube aluminum fin air-to-refrigerant 
heat exchanger will be constructed of patented 11 element fin 
and double electro-coated for corrosion protection. Models 022-
072 shall include discharge mufflers to help quiet compressor 
discharge gas pulsations. Refrigerant to air heat exchangers shall 
utilize enhanced tube construction rated to withstand 600 psig (4135 
kPa) refrigerant working pressure.

The coaxial water-to-refrigerant heat exchanger shall be designed 
for low water pressure drop and constructed of a convoluted copper 
(cupronickel option) inner tube and a steel outer tube. Refrigerant to 
water heat exchangers shall be of copper inner water tube and steel 
refrigerant outer tube design, rated to withstand 600 psig (4135 kPa) 
working refrigerant pressure and 450 psig (3101 kPa) working water 
pressure. The thermostatic expansion valve shall provide proper 
superheat over the entire liquid temperature range with minimal 
“hunting.” The valve shall operate bidirectionally without the use of 
check valves.

All units shall have the source coaxial tube refrigerant-to-water 
heat exchanger and the optional hot water generator coil shall 
be coated with ThermaShield. Refrigerant suction lines shall be 
insulated to prevent condensation at low liquid temperatures.

Blower Motor and Assembly

The blower shall be a direct drive centrifugal type with a 
dynamically balanced wheel. The housing and wheel shall be 
designed for quiet low outlet velocity operation. The blower 
housing shall be removable from the unit without disconnecting 
the supply air ductwork for servicing of the blower motor. The 
blower motor shall be a 3-speed PSC, 5-speed ECM, or variable-
speed ECM type. The variable speed ECM blower motor shall be 
soft starting, shall maintain constant cfm over its operating static 
range, and shall provide 12 cfm settings. An optional constant 

Summary of Contents for YAFS012-018

Page 1: ...NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www york geothermal com Additional rating information can found at www ahr...

Page 2: ...tory Installed Pump No IntelliStart1 3 No HWG IntelliStart1 4 HWG with Factory Installed Pump IntelliStart1 Vintage Factory Use Only Controls D Aurora Performance and Refrigeration Package Air Coil Op...

Page 3: ...2 000 6 1 22 200 29 7 17 500 4 9 21 000 26 0 16 400 4 5 038 Full 9 1300 36 500 17 0 43 300 5 5 40 000 24 4 35 000 4 9 38 200 19 7 28 500 4 2 038 Part 8 1150 26 500 19 0 31 300 6 4 29 900 32 1 24 900 5...

Page 4: ...Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Cooling EWT 86 F Heating EWT 68 F Cooling EWT 59 F Heating EWT 50 F Cooling Brine Full Load 77 F Part Load 68 F Heating Brine Full Load 32...

Page 5: ...water source heat pumps to be Energy Star rated they must meet or exceed the minimum efficiency requirements listed below Tier 3 represents the current minimum efficiency water source heat pumps must...

Page 6: ...5 34 0 41 7 24 4 17 5 23 9 29 7 16 0 1 8 35 6 35 6 6 9 5 8 55 9 45 7 5 1 022 030 in 22 5 26 5 48 5 2 0 7 0 13 5 16 5 10 2 1 in Swivel 1 2 in Female 9 5 12 1 14 3 6 1 0 8 14 0 14 0 4 4 1 7 22 2 26 0 1...

Page 7: ...ate Supply Width Supply Depth Return Depth Return Height 022 030 in 22 5 26 5 52 5 35 3 40 2 46 7 49 7 3 6 1 in Swivel 1 2 in Female 41 9 43 6 45 1 8 6 6 0 9 3 10 5 1 0 2 2 22 2 26 0 5 6 cm 57 2 67 3...

Page 8: ...ate Power Supply Ext Pump Low Voltage Supply Width Supply Depth Return Depth Return Height 042 049 in 25 6 31 6 54 4 2 3 7 3 15 9 18 9 10 6 1 Swivel 1 2 female 9 5 12 1 14 3 13 3 13 6 39 4 9 1 8 1 1 7...

Page 9: ...11 7 1 8 10 5 9 5 8 2 2 2 21 8 16 5 1 5 cm 57 2 134 6 49 0 5 8 13 5 35 1 42 7 20 3 17 5 24 1 29 7 4 6 26 7 24 1 20 8 5 6 55 4 41 9 3 8 022 030 in 22 5 63 0 19 3 2 0 7 0 13 5 16 5 0 8 1 in Swivel 1 2...

Page 10: ...n a 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 n a n a PSC n a n a 9 x 7 229 x 178 9 x 7 229 x 178 10 x 10 254 x 254 10 x 10 254 x 254 10 x 10 254 x 254 n a n a Coax and Water Piping Water...

Page 11: ...254 11 x 10 279 x 254 5 Spd ECM 9 x 7 229 x 178 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 11 x 10 279 x 254 High Static Blower Wheel Size Dia x W in mm VS ECM n a 11 x 10 279 x 254 11 x 10...

Page 12: ...e 34 7 40 0 53 3 60 0 60 60 60 60 60 60 EAL H 15A Single 52 0 60 0 75 0 85 0 80 90 80 90 70 100 L1 L2 34 7 40 0 53 3 60 0 60 60 60 60 60 60 L3 L4 17 3 20 0 21 7 25 0 25 25 25 25 20 30 EAL H 20A Single...

Page 13: ...Blower Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA LRA 022 208 230 60 1 187 253 14 0 9 0 48 0 17 0 0 4 5 4 4 1 18 9 21 1 30 030 208 230 60 1 187 253 20 0 12 8 58 3 21 0 0 4 5 4 4 1...

Page 14: ...5 4 7 0 28 0 31 8 50 049 208 230 60 1 187 253 33 0 21 1 104 0 37 0 0 4 5 4 4 0 30 9 36 2 50 049 208 230 60 1 187 253 33 0 21 1 104 0 37 0 0 4 5 4 7 0 33 9 39 2 60 064 208 230 60 1 187 253 42 3 27 1 15...

Page 15: ...75 800 950 1100 1300 1500 1750 1950 2100 2300 2325 G L H Aux Factory settings are at recommended G L H Aux speed settings L H settings MUST be located within boldface cfm range Aux is factory setting...

Page 16: ...2 Med Low 2 Y1 1575 1560 1540 1520 1502 1487 1471 1448 1424 1409 1393 1351 1308 1266 Low 1 G 1454 1406 1358 1333 1308 1285 1261 1239 1217 1198 1179 1072 1002 988 048 High 5 11 x 10 1 1934 1910 1886 18...

Page 17: ...1659 1617 Med High 4 1799 1783 1767 1744 1720 1693 1666 1649 1631 1617 1603 1560 1530 1492 Med 3 Y2 1694 1680 1666 1642 1617 1592 1567 1552 1537 1519 1500 1453 1421 1372 Med Low 2 Y1 1575 1560 1540 1...

Page 18: ...0 1130 1100 1060 1020 930 060 H 11 x 10 1 2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330 M 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1...

Page 19: ...6 66 2 27 19 68 20 0 Max Entering Air db wb 110 83 43 28 3 80 26 7 Water Limits Min Entering Water 30 1 1 20 6 7 Normal Entering Water 50 110 10 43 3 30 70 1 1 Max Entering Water 120 48 9 90 32 2 NOTE...

Page 20: ...987 1 018 475 119 1 017 1 099 1 037 1 022 1 018 0 984 1 025 500 125 1 020 1 132 1 052 1 027 1 022 0 982 1 031 520 130 1 022 1 159 1 064 1 030 1 025 0 979 1 034 5 30 06 Air Flow Corrections Dual Capaci...

Page 21: ...he corrected heating and cooling performance at 30 F and 90 F respectively as well as pressure drop at 30 F for a Affinity Series Single Speed Model 022 ECM The corrected cooling capacity at 90 F woul...

Page 22: ...1 1 0 1 0 0 9 0 8 9 2 3 2 1 2 0 1 9 1 7 12 3 9 3 7 3 4 3 2 3 0 16 6 7 6 3 5 9 5 5 5 1 060 9 2 4 2 2 2 1 2 0 1 8 12 3 9 3 6 3 4 3 2 2 9 15 5 7 5 3 5 0 4 7 4 3 20 9 5 8 9 8 3 7 8 7 2 070 12 3 0 2 8 2 6...

Page 23: ...9 50 1 5 0 3 0 7 10 6 0 83 7 8 92 5 3 75 15 0 10 0 0 66 0 61 17 1 24 6 2 5 1 0 2 3 11 0 0 83 8 2 93 5 3 86 15 2 9 9 0 65 0 56 17 1 27 3 3 5 1 7 3 8 11 4 0 84 8 5 94 4 3 97 15 5 9 9 0 64 0 51 17 2 30...

Page 24: ...0 65 0 95 23 3 21 3 0 9 4 0 2 9 6 6 17 5 1 37 12 8 95 0 3 75 1 7 20 4 13 1 0 64 0 86 23 3 23 8 0 9 5 0 4 2 9 6 17 9 1 38 13 2 95 7 3 81 1 8 20 7 13 1 0 63 0 77 23 3 27 0 0 9 60 3 0 1 5 3 5 19 0 1 42 1...

Page 25: ...66 0 99 27 7 25 7 1 2 4 5 1 6 3 8 19 7 1 36 15 0 96 0 4 25 2 0 25 7 16 9 0 66 0 95 28 0 27 1 1 1 6 0 2 7 6 2 20 0 1 36 15 4 96 5 4 30 2 1 26 0 16 9 0 65 0 93 28 2 28 1 1 1 60 3 0 0 8 1 9 21 2 1 36 16...

Page 26: ...71 1 29 35 1 23 8 1 5 6 0 2 5 6 6 26 8 1 75 20 8 97 6 4 49 2 7 30 8 21 9 0 71 1 25 35 0 24 7 1 4 8 0 4 2 11 1 27 4 1 76 21 3 98 1 4 55 2 8 31 2 21 9 0 70 1 22 35 3 25 5 1 4 60 4 0 1 2 3 1 29 1 1 80 23...

Page 27: ...71 1 53 38 7 23 7 1 7 7 0 1 9 4 5 32 0 2 08 24 9 93 7 4 51 3 3 36 4 26 0 0 72 1 48 38 8 24 6 1 6 9 0 3 3 7 5 32 6 2 10 25 5 94 2 4 56 3 4 36 8 26 0 0 71 1 45 39 2 25 5 1 6 60 5 0 0 9 2 1 34 7 2 11 27...

Page 28: ...2 01 45 7 21 6 2 6 8 0 2 1 4 8 37 3 2 57 28 5 95 6 4 26 4 8 43 8 31 0 0 71 1 93 46 2 22 7 2 5 11 0 4 1 9 4 38 0 2 58 29 3 96 1 4 33 5 0 44 2 31 0 0 70 1 88 46 6 23 5 2 4 60 5 0 0 7 1 7 39 3 2 57 30 5...

Page 29: ...54 9 22 3 3 1 9 0 2 1 4 9 48 1 3 32 36 7 99 7 4 25 6 4 53 1 37 1 0 70 2 26 55 5 23 5 2 9 12 0 3 7 8 4 49 0 3 33 37 7 100 3 4 31 6 5 53 6 37 1 0 69 2 20 56 0 24 4 2 8 60 6 0 1 0 2 3 50 8 3 33 39 5 101...

Page 30: ...8 4 1 12 0 3 6 8 4 60 4 4 39 45 5 98 0 4 04 7 7 71 4 51 0 0 71 3 38 73 9 21 1 3 9 15 0 5 3 12 3 61 5 4 43 46 4 98 5 4 07 7 9 72 2 51 0 0 71 3 23 74 6 22 3 3 7 60 9 0 2 2 5 0 65 4 4 47 50 1 100 3 4 29...

Page 31: ...5 15 0 4 0 9 3 70 9 5 04 53 7 99 9 4 13 9 2 79 5 55 7 0 70 3 41 81 9 23 3 4 3 18 0 5 5 12 7 71 6 5 06 54 3 100 1 4 14 9 4 80 3 56 0 0 70 3 38 82 7 23 8 4 1 60 12 0 2 7 6 2 77 1 5 15 59 5 102 4 4 39 10...

Page 32: ...94 22 4 20 5 1 1 4 0 2 8 6 6 500 18 8 1 34 14 3 102 9 4 11 2 1 500 18 9 11 4 0 60 0 81 21 7 23 2 1 0 600 19 4 1 37 14 8 98 0 4 16 2 0 600 19 4 12 6 0 65 0 88 22 4 22 2 1 1 5 0 4 1 9 5 500 19 2 1 36 1...

Page 33: ...0 1 4 4 5 1 6 3 7 600 21 2 1 27 16 9 102 7 4 89 2 4 600 24 8 16 1 0 65 0 88 27 8 28 3 1 2 700 21 8 1 26 17 5 98 8 5 05 2 3 700 25 3 17 5 0 69 0 91 28 5 27 7 1 3 6 0 2 6 6 0 600 21 6 1 29 17 2 103 3 4...

Page 34: ...23 7 1 8 6 0 2 4 6 4 700 28 9 1 69 23 1 108 2 5 01 3 3 700 29 6 19 1 0 65 1 16 33 5 25 4 1 6 900 29 7 1 69 23 9 100 6 5 16 3 0 900 30 5 21 3 0 70 1 23 34 7 24 7 1 7 8 0 4 0 10 7 700 29 5 1 71 23 6 10...

Page 35: ...9 4 3 1050 34 5 2 01 27 6 100 4 5 03 4 0 1050 35 4 24 1 0 68 1 40 40 2 25 4 1 9 1250 35 5 2 01 28 6 96 3 5 18 3 7 1250 36 5 27 0 0 74 1 48 41 6 24 7 2 0 9 0 3 1 7 3 1050 35 2 2 04 28 2 101 0 5 06 4 2...

Page 36: ...4 6 1150 39 2 2 39 31 0 101 6 4 80 5 9 1150 43 0 28 0 0 65 1 70 48 8 25 4 2 8 1350 40 0 2 32 32 1 97 4 5 06 5 4 1350 44 7 31 4 0 70 1 78 50 8 25 1 3 0 11 0 3 9 9 1 1150 40 1 2 41 31 9 102 3 4 87 6 1...

Page 37: ...8 1300 51 3 3 28 40 1 106 5 4 59 7 8 1300 50 6 32 4 0 64 2 13 57 9 23 7 3 3 1500 52 3 3 18 41 5 102 3 4 83 7 2 1500 52 6 36 4 0 69 2 24 60 2 23 5 3 6 12 0 3 5 8 2 1300 52 5 3 31 41 2 107 4 4 65 8 0 13...

Page 38: ...9 4 16 50 7 110 0 4 57 9 4 1500 68 7 46 4 0 68 2 93 78 7 23 4 4 4 2000 65 8 4 21 51 4 100 5 4 57 8 7 2000 70 4 49 3 0 70 3 24 81 4 21 7 4 8 15 0 5 2 11 9 1500 66 3 4 23 51 9 110 9 4 59 9 7 1500 69 4 4...

Page 39: ...5 16 59 5 112 0 4 38 11 2 1700 72 6 47 0 0 65 3 22 83 5 22 6 4 8 2200 79 1 5 12 61 6 103 3 4 53 10 3 2200 76 4 53 8 0 70 3 62 88 8 21 1 5 2 18 0 5 3 12 3 1700 78 0 5 20 60 2 112 5 4 39 11 5 1700 73 5...

Page 40: ...6 2 96 3 5 37 1 9 700 23 7 16 0 0 68 0 77 26 4 31 0 1 0 5 0 1 8 4 1 500 20 2 1 08 16 5 107 4 5 50 2 1 500 23 3 14 6 0 63 0 73 25 8 31 8 0 9 700 20 7 1 08 17 0 97 3 5 60 2 0 700 24 0 16 1 0 67 0 75 26...

Page 41: ...8 32 9 22 3 1 6 900 26 8 1 59 21 4 97 6 4 94 2 9 900 29 9 19 9 0 67 1 34 34 4 22 3 1 7 6 0 2 5 5 8 700 27 2 1 63 21 6 105 9 4 90 3 2 700 29 2 18 1 0 62 1 22 33 3 24 0 1 5 900 28 1 1 64 22 5 98 9 5 02...

Page 42: ...1 3 1050 28 8 1 68 23 1 95 4 5 03 2 6 1050 31 3 23 1 0 74 1 06 35 0 29 7 1 4 6 0 1 5 3 6 900 29 3 1 67 23 6 100 1 5 15 3 0 900 30 8 21 0 0 68 1 01 34 2 30 5 1 3 1050 29 9 1 68 24 2 96 4 5 24 2 7 1050...

Page 43: ...1250 40 0 2 48 31 5 99 6 4 72 3 8 1250 41 3 28 7 0 70 2 09 48 4 19 8 2 4 7 0 2 0 4 6 1050 40 5 2 54 31 8 105 7 4 68 4 3 1050 40 4 26 1 0 65 1 90 46 8 21 3 2 2 1250 41 8 2 55 33 1 100 9 4 80 4 0 1250 4...

Page 44: ...50 34 9 2 22 27 3 93 9 4 61 4 8 1350 40 7 27 5 0 67 1 76 46 8 23 1 2 4 8 0 1 8 4 0 1150 36 5 2 29 28 6 99 3 4 67 5 4 1150 40 2 23 5 0 59 1 50 45 3 26 8 2 1 1350 37 9 2 26 30 2 96 0 4 91 5 0 1350 41 4...

Page 45: ...0 3 24 36 9 98 7 4 34 7 0 1550 54 1 34 3 0 63 2 90 64 0 18 7 3 9 9 0 2 2 5 0 1350 50 1 3 34 38 7 104 4 4 40 7 8 1350 53 4 29 3 0 55 2 47 61 8 21 6 3 4 1550 52 1 3 30 40 8 101 1 4 62 7 2 1550 55 0 34 5...

Page 46: ...7 6 2 89 37 8 99 4 4 84 5 7 1500 53 0 33 7 0 64 2 06 60 0 25 8 3 0 10 0 2 4 5 5 1250 48 1 2 96 38 0 105 6 4 76 6 3 1250 51 6 30 1 0 58 1 90 58 1 27 2 2 6 1500 48 9 2 92 38 9 100 2 4 90 5 8 1500 53 2 3...

Page 47: ...0 2 103 2 4 52 8 0 1800 70 0 45 9 0 66 3 51 81 9 19 9 5 1 12 0 3 4 7 8 1500 66 0 4 18 51 7 110 7 4 62 9 0 1500 68 9 42 6 0 62 3 23 79 9 21 3 4 5 1800 67 4 4 24 53 0 104 7 4 66 8 3 1800 70 7 46 3 0 66...

Page 48: ...0 4 02 48 3 103 8 4 52 6 9 1700 59 8 41 3 0 69 2 66 68 9 22 5 3 4 13 0 3 2 7 3 1400 61 1 4 15 47 0 110 4 4 32 7 7 1400 58 3 36 9 0 63 2 46 66 7 23 7 3 0 1700 63 6 4 07 49 7 104 6 4 57 7 1 1700 60 1 4...

Page 49: ...5 4 24 10 3 2200 75 5 52 0 0 69 4 26 90 1 17 7 5 6 15 0 4 1 9 6 1850 80 6 5 49 61 9 110 3 4 30 11 5 1850 74 7 48 6 0 65 3 93 88 1 19 0 4 9 2200 83 2 5 58 64 2 105 0 4 37 10 6 2200 76 2 52 5 0 69 4 17...

Page 50: ...FRIGERATION OPTION PERFORMANCE OPTION White White Purple Purple Gray Gray GND OUT 5DC 3 2 4 White 3 2 4 FLOW METER Brown Green PRESSURE TRANSDUCER PRESSURE TRANSDUCER Black White 5 Run Winding Active...

Page 51: ...uit 2 NOTE 2 208 230 60 1 208 230 60 1 Green Connects to variable speed ECM motor only P11 2 3 4 5 1 NOTE 6 With optional EA Series 20kW Auxiliary Electric Heat shown Place auxiliary heat schematic fr...

Page 52: ...n Critical Communication Error Flash Code 18 Future Use Flash Code 12 Non Critical AXB Sensor Error Flash Code 13 Critical AXB Sensor Error Flash Code 14 Future Use Flash Code 9 Compressor Monitoring...

Page 53: ...ff On N A RS485 NET NO COM K6 Relay Connects to L2 and NO on AXB Board L2 Figure 1 Optional Internal Hot Water Generation Pump Wiring Schematic DHW Pump Blue Blue Cabinet HW Switch 3 2 1 Purple VS GND...

Page 54: ...RIGERATION OPTION PERFORMANCE OPTION White White Purple Purple Gray Gray GND OUT 5DC 3 2 4 White 3 2 4 FLOW METER Brown Green PRESSURE TRANSDUCER PRESSURE TRANSDUCER Black White 5 Gray White 4 CT Blac...

Page 55: ...1 2 3 4 Brown Orange P1 4 1 2 3 C G G To PB2 TB ER 4 N O G ER 3 N O G Gray Gray Black Black Black Gray Gray Black NOTE 3 Connects to variable speed ECM motor only With optional EA Series 10kW Auxilia...

Page 56: ...de 9 Compressor Monitoring Flash Code 10 Fault FP1 6HQVRU UURU Flash Code 11 Reserved Flash Code 6 Condensate Overflow Lockout Flash Code 7 Over Under Voltage Shutdown Flash Code 8 Future Use Flash Co...

Page 57: ...us AURORA BASE CONTROL RV K1 CC2 CC K2 CC Hi K3 Fan K4 Alarm K5 Acc K6 ACC no ACC nc O B C R LO G Y1 Y2 W DH 3A Fuse O B C R LO G Y1 Y2 W DH LO G HI CCG CC FG F R HP HP LP FP2 FP2 FP1 REV REV CFM PWM...

Page 58: ...1 5A 5A DHW Pump Blue Hot Water Limit Switch 130 F Blue 1 2 3 Purple Traditional Thermostat Communicating Thermostat AID Tool Cabinet HW Switch NOTE 7 H M L P3 PSC Blower Motor Grn Wht Brn Cap 3 Airfl...

Page 59: ...efore repeating Slow Flash Fast Flash Flash Code Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Future Use Future Use Load Shed ESD OFF ON Slow Flash Fast Flash F...

Page 60: ...ue 16 Blue 18 CC T2 T1 Compressor C R S Blue G L1 L2 208 230 60 1 Unit Power Supply Violet 7 Tan 6 Black 3 Black 2 Cap Ext Pump 1 2 hp Total 208 230 60 1 Pump G 1 2 PB1 1 2 Pump Violet 8 NOTE 2 Gray W...

Page 61: ...econds off with a 2 second pause before repeating Slow Flash Fast Flash Flash Code Normal Mode Control is Non Functional Test Mode Lockout Active Dehumidification Mode Future Use Future Use Load Shed...

Page 62: ...bypass Vertical units shall be supplied with left or right horizontal air inlet and top bottom 022 072 or rear vertical 042 072 air discharge Horizontal units shall be supplied with left or right air...

Page 63: ...on inputs to drive dedicated alarms for sump pump security system and smoke CO2 or dirty air filter sensors Optional Refrigerant and Performance Monitoring kits to provide real time data including ref...

Page 64: ...atic Air Cleaner field installed A 1 in 25 mm electrostatic air cleaner cleanable 90 efficiency shall be provided in lieu of the standard throwaway filter The initial pressure drop across the filter s...

Page 65: ...the equipment is acceptable under the provisions of the job specification Statements and other information contained herein are not express warranties and do not form the basis of any bargain between...

Page 66: ...tements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely the manufacturer s opinion or commendation of its...

Reviews: