Dual Capacity Unit with Variable Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
026
208-230/60/1
187/253
18.2
11.6
58.3
21.0
0.4
5.4
4.0
21.4
24.4
35
038
208-230/60/1
187/253
23.8
15.2
83.0
30.0
0.4
5.4
4.0
25.0
28.8
40
038*
208-230/60/1
187/253
23.8
15.2
83.0
30.0
0.4
5.4
7.0
28.0
31.8
50
049
208-230/60/1
187/253
33.0
21.1
104.0
37.0
0.4
5.4
4.0
30.9
36.2
50
049*
208-230/60/1
187/253
33.0
21.1
104.0
37.0
0.4
5.4
7.0
33.9
39.2
60
064
208-230/60/1
187/253
42.3
27.1
152.9
54.0
0.4
5.4
7.0
39.9
46.6
70
072
208-230/60/1
187/253
46.3
29.6
179.2
63.0
0.4
5.4
7.0
42.4
49.8
70
9/1/15
* With optional 1 hp variable speed ECM motor
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Dual Capacity Unit with 5-Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
026
208-230/60/1
187/253
18.2
11.6
58.3
21.0
0.4
5.4
4.1
21.5
24.5
35
038
208-230/60/1
187/253
23.8
15.2
83.0
30.0
0.4
5.4
4.1
25.1
28.9
40
049
208-230/60/1
187/253
33.0
21.1
104.0
37.0
0.4
5.4
7.6
34.5
39.8
60
064
208-230/60/1
187/253
42.3
27.1
152.9
54.0
0.4
5.4
7.6
40.5
47.2
70
072
208-230/60/1
187/253
46.3
29.6
179.2
63.0
0.4
5.4
7.6
43.0
50.4
80
9/1/15
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Electrical Data cont.
Affinity & Affinity Advanced Series
1 - 6 Tons 60Hz
SD2500AK6 06/21
14