background image

12

ENGLISH

  Indoor Unit Fixing

•  Thread the indoor unit piping and cable through the hole.

•  Hang the top of the unit onto the upper ridge of them in mounting plate.

•  Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.

•  Press the bottom left and bottom right hand corners of the unit against the mounting plate until the  fixing prongs click 

into place in the retainers provided to that effect.

Drainage line

Interconnection cable

Note: The  condensate  evacuation  line  should  be  taped  to  the 

refrigerant lines with vinyl tape.

a)  Access  plate  for  the 

condensate  drainage 

pump detection

 

(condensate pump is 

available as an 

 

accessory).

Condensate

drainage line

Vinyl tape

a

OUTDOOR UNIT

  Fixing and Piping

•  Piping  must  be  performed  by  qualified  personnel

  according to good refrigeration systems practices.

•  Piping  materials  and  insulation  materials  must  be  of

  refrigerant quality.

•  Select the pipe diameters according to the size of unit

  and cut the pipe to design length by using pipe cutter.

•  Install the  flare nuts and   are the end of the pipes.

•  Check that no foreign bodies are inside the piping.

•  Align  the  central  of  the  connecting  pipes  and  tighten

  the  flare nut.

• Fix  piping  with  pipe  clamps  and  check  that  any  pipe

  vibrations cannot be transmitted to the building structure.

NOTES

•  Connect the pipe correctly.

•  Do not apply the excessive torque.

•  Use an appropriate bending tool to form curves and  

  avoid over-tightening the refrigerant tubes.

•  To prevent heat loss, the two lines must be insulated  

  separately.

  Maximum Piping Length

The  suction  line  must  have  a  2%  gradient  up  to  the

compressor on horizontal sections.

Where  piping  lengths  are  unusually  long  and  include  a

large number of oil traps, it may be necessary to adjust

to compressor charge.

  Refrigerant piping connections

 

(FLARE connections)

To  avoid  alteration  of  unit  capacities,  check  that  piping

lengths  and  changes  in  elevation  are  kept  to  a  strict 

minimum.

Before  connecting  the  refrigerant  lines,  follow  the

procedures  below  (if  pre-charged  connection  lines  are

not supplied):

•  Select copper pipe diameters according to the size of

  unit to be installed.

•  Install  the  refrigeration  lines,  checking  that  no  foreign

  bodies get inside the piping.

•  Install  the  flare  connectors  and   flare  the  ends  of  the

  pipes.

• Evacuate the piping. This operation, which should last

  at least 15 minutes if there are large piping lengths and

  changes in elevation, should be followed by a leak test.

Refrigerant charge to be added per extra meter 

of piping length when more than 7 meters.

Note: Where the difference in elevation between the indoor 

unit and the outdoor unit is greater than 5 meters, install 

an oil trap every 5 meters.

J440-EN.indd   12

2/18/08   2:50:03 PM

Max. refrigerant 

pipe length

Max. difference 

in level

Unit size

m

m

09

12

18

25

10

20

20

8

8

Unit size

MODELS

g/m

09

12

18

30

30

30

Summary of Contents for TVHC09-18DSAAAR

Page 1: ...ion and operation Make sure that it is well kept for later reference Read this manual before installation and operation Make sure that it is well kept for later reference Mini Split Air Conditioner TV...

Page 2: ...18 Operation tips 19 Troubleshooting guide 20 Please read this installation manualcarefullybeforestarting the installation It will tell you necessary information Quality POLICY Wewillcontinuouslystriv...

Page 3: ...m should only be car ried out by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the power su...

Page 4: ...r unit would look like one of the following For cooling only models f 21000Btu h unit 2 indicator light is FAN ONLY 1 AUTO indicator This indicator illuminates when the air conditioner is in AUTO oper...

Page 5: ...oller operation use the remote controller directly CAUTION 1 If air conditioner is used outside of the above conditions certain safety protection features may come into operation and cause the unit to...

Page 6: ...ATIC OPERATION When you set the air conditioner in AUTO mode it will automatically select cooling heating cooling heating models only or fan only operation depending on what temperature you have selec...

Page 7: ...direction to which you adjusted the louver by pressing the AIR DIRECTION button To set the horizontal air flow direction left right Adjust the vertical louver manually using the lever on the left or r...

Page 8: ...the extension cables In the case extended cables are needed use the terminal block SELECTION OF THE LOCATION Select a place which provides the space around the units as shown in the diagram below IND...

Page 9: ...EN 9 ENGLISH OUTDOOR UNIT PICTURES TVHC09 18 Models W H D L1 L2 L3 07 09 685 430 276 460 300 445 12 700 522 250 458 275 537 18 780 530 275 549 290 545 J440 EN indd 9 2 14 08 1 26 40 PM...

Page 10: ...Aminimum pipe run of 3 metres is required to minimise vibration excessive noise Theindoorunitshouldbeinstalledonthewallataheight of 1 7 metres or more from the floor but less than 2 3 metres from the...

Page 11: ...o avoid flattening or obstructing them if the pipes are bent incorrectly the indoor unit may be unstable on the wall Carefully arrange pipes so that pipes do not stick out of the rear plate of the ind...

Page 12: ...the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To prevent heat loss the two lines must be insulate...

Page 13: ...meters Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor unit Indoor unit Gas line Liquid line R 22 R407C R410A Outdoor heat pump unit...

Page 14: ...rmally the required impedance reaches at a 32 A fusing point 2 No other equipment has to be connected with this power line 3 For detailed installation acceptance please refer to your contract with the...

Page 15: ...SFORMER 3 11 ORANGE OR A NGE CAPACITOR 3 4 3 FILTER HL1 HL2 HN1 HN2 S N L 2 4 P_1 OPTIONAL OPTIONAL 3 3 5 2 4 CHOOSE ONE BY THE TRANSFORMER R S C BLUE U V W RY3 4 CN6 CN7 CN28 CN26 CN10 N B RED YELLOW...

Page 16: ...airgapcontact separation of at least 3 mm in each active phase conductors CAUTIONS Air and moisture in the refrigerant system have undesirable effects as indicated below Pressure in the system rises O...

Page 17: ...keep compressor running 2 Condition to stop defrosting Units will switch back to heating mode when either of the following conditions is met a Unit has been running at defrosting mode for 10 minutes...

Page 18: ...the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourself Contact your dealer or servicer n Checks before operation Check that the wiring...

Page 19: ...rmal condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell come out from the indoor unit This is caused by the indoor unit giving off...

Page 20: ...repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs continuously 1 Thermostat adjustment too low in heating mode or too hi...

Page 21: ...nd dispose of according to local laws and regulations governing disposal of oily wastes 3 Packaged unit can generally be removed in one piece after disconnection as above Any xing down bolts should be...

Page 22: ...www johnsoncontrols com Form No 035M000340 002 2008 Johnson Controls Inc Johnson Controls reserve the right to change product features without prior notice...

Reviews: