background image

EN

19

ENGLISH

OPERATION TIPS

The following events may occur during normal operation.

1.  Protection of the air conditioner.

 Compressor 

protection

 

•  The compressor cannot restart for 3 minutes after it stops.

 

 

Anti-cold air (Cooling and heating models only)

 • The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following  

 

three situations and the set temperature has not been reached.

 

 

A)   When heating has just starting.

 

 

B)   Defrosting.

 

 

C)   Low temperature heating.

 

•  The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).

 

 

Defrosting (Cooling and heating models only)

 

•  Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low and humidity is  
 

high resulting in lower heating ef

fi

 ciency of the air conditioner.

 

•  During this condition air conditioner will stop heating operation and start defrosting automatically.

 

•  The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and the amount of frost  
 

buildup on the outdoor unit.

2.  A white mist coming out from the indoor unit.

 

•  A white mist may generate due to a large temperature difference between air inlet and air outlet on COOL mode  
 

in an indoor environment that has a high relative humidity.

 

•  A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts  
 

in HEAT mode operation after defrosting.

3.  Low noise of the air conditioner

.

 

•  You may hear a low hissing sound when the compressor is running or has just stopped running.

 

 

This sound is the sound of the refrigerant 

fl

 owing or coming to a stop.

 

•  You can also hear a low “squeak” sound when the compressor is running or has just stopped running. This is  
 

caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.

 

•  A noise may be heard due to louver restoring to its original position when power is 

fi

 rst turned on.

4.  Dust in blown out from the indoor unit.

 

This is a normal condition when the air conditioner has not been used for a long time or during 

fi

 rst use of the unit.

5.  A peculiar smell come out from the indoor unit.

 

This is caused by the indoor unit giving off smells permeated from building material, from furniture, or smoke.

6.  The air conditioner turns to FAN only mode from COOL or HEAT (for cooling and heating models only) mode.

 

When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically, 
and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises 
on COOL mode or falls on HEAT mode (For cooling and heating models only) to the set point.

7.

  Dripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative humidity 

higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.

8.  Heating mode (for cooling and heating models only)

 

The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating operation. 
When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time, 
heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a 
comfortable temperature cannot be achieved by the air conditioner, we suggest you use a supplementary heating 
device.

9. Auto-restart function

 

Power failure during operation will stop the unit completely.

 

For the unit without Auto-restart feature, when the power restores, the OPERATION indicator on the indoor unit starts 

fl

 ashing. To restart the operation, push the ON/OFF button on the remote controller. For the unit with Auto-restart 

feature, when the power restores, the unit restarts automatically with all the previous settings preserved by the memory 
function.

10. Lightning or a car wireless telephone operating nearby may cause the unit to malfunction.

 

Disconnect the unit with power and then re-connect the unit with power again. Push the ON/OFF button on the remote 
controller to restart operation.

J440-EN.indd   25

J440-EN.indd   25

2/14/08   1:27:02 PM

2/14/08   1:27:02 PM

Summary of Contents for TVHC09-18DSAAAR

Page 1: ...ion and operation Make sure that it is well kept for later reference Read this manual before installation and operation Make sure that it is well kept for later reference Mini Split Air Conditioner TV...

Page 2: ...18 Operation tips 19 Troubleshooting guide 20 Please read this installation manualcarefullybeforestarting the installation It will tell you necessary information Quality POLICY Wewillcontinuouslystriv...

Page 3: ...m should only be car ried out by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the power su...

Page 4: ...r unit would look like one of the following For cooling only models f 21000Btu h unit 2 indicator light is FAN ONLY 1 AUTO indicator This indicator illuminates when the air conditioner is in AUTO oper...

Page 5: ...oller operation use the remote controller directly CAUTION 1 If air conditioner is used outside of the above conditions certain safety protection features may come into operation and cause the unit to...

Page 6: ...ATIC OPERATION When you set the air conditioner in AUTO mode it will automatically select cooling heating cooling heating models only or fan only operation depending on what temperature you have selec...

Page 7: ...direction to which you adjusted the louver by pressing the AIR DIRECTION button To set the horizontal air flow direction left right Adjust the vertical louver manually using the lever on the left or r...

Page 8: ...the extension cables In the case extended cables are needed use the terminal block SELECTION OF THE LOCATION Select a place which provides the space around the units as shown in the diagram below IND...

Page 9: ...EN 9 ENGLISH OUTDOOR UNIT PICTURES TVHC09 18 Models W H D L1 L2 L3 07 09 685 430 276 460 300 445 12 700 522 250 458 275 537 18 780 530 275 549 290 545 J440 EN indd 9 2 14 08 1 26 40 PM...

Page 10: ...Aminimum pipe run of 3 metres is required to minimise vibration excessive noise Theindoorunitshouldbeinstalledonthewallataheight of 1 7 metres or more from the floor but less than 2 3 metres from the...

Page 11: ...o avoid flattening or obstructing them if the pipes are bent incorrectly the indoor unit may be unstable on the wall Carefully arrange pipes so that pipes do not stick out of the rear plate of the ind...

Page 12: ...the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To prevent heat loss the two lines must be insulate...

Page 13: ...meters Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor unit Indoor unit Gas line Liquid line R 22 R407C R410A Outdoor heat pump unit...

Page 14: ...rmally the required impedance reaches at a 32 A fusing point 2 No other equipment has to be connected with this power line 3 For detailed installation acceptance please refer to your contract with the...

Page 15: ...SFORMER 3 11 ORANGE OR A NGE CAPACITOR 3 4 3 FILTER HL1 HL2 HN1 HN2 S N L 2 4 P_1 OPTIONAL OPTIONAL 3 3 5 2 4 CHOOSE ONE BY THE TRANSFORMER R S C BLUE U V W RY3 4 CN6 CN7 CN28 CN26 CN10 N B RED YELLOW...

Page 16: ...airgapcontact separation of at least 3 mm in each active phase conductors CAUTIONS Air and moisture in the refrigerant system have undesirable effects as indicated below Pressure in the system rises O...

Page 17: ...keep compressor running 2 Condition to stop defrosting Units will switch back to heating mode when either of the following conditions is met a Unit has been running at defrosting mode for 10 minutes...

Page 18: ...the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourself Contact your dealer or servicer n Checks before operation Check that the wiring...

Page 19: ...rmal condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell come out from the indoor unit This is caused by the indoor unit giving off...

Page 20: ...repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs continuously 1 Thermostat adjustment too low in heating mode or too hi...

Page 21: ...nd dispose of according to local laws and regulations governing disposal of oily wastes 3 Packaged unit can generally be removed in one piece after disconnection as above Any xing down bolts should be...

Page 22: ...www johnsoncontrols com Form No 035M000340 002 2008 Johnson Controls Inc Johnson Controls reserve the right to change product features without prior notice...

Reviews: