SUPPLY AIR BLOWER PERFORMANCE

- BCH036, 048 & 060 with Direct-Drive

SUPPLY AIR BLOWER PERFORMANCE

- BCH060 with Belt-Drive

MODEL

BCH

AIR FLOW

CFM

Available External Static Pressure - IWG*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

060

2500

1059

1560

1077

1590

1095

1630

1114

1650

1134

1660

1158

1685

1181

1720

2400

1032

1405

1054

1470

1074

1525

1094

1560

1116

1595

1140

1620

1167

1640

2300

1005

1260

1024

1275

1049

1370

1069

1440

1090

1475

1116

1505

1142

1535

2200

980

1160

1002

1170

1022

1190

1044

1250

1066

1350

1090

1410

1117

1440

2100

930

1060

957

1070

983

1080

1010

1100

1039

1160

1064

1260

1092

1340

2000

877

950

908

975

941

1000

976

1020

1009

1050

1040

1100

1070

1225

1900

-

-

-

-

894

885

940

940

980

980

1014

1020

1047

1095

1800

-

-

-

-

855

815

903

860

950

905

988

940

1022

970

1700

-

-

-

-

-

-

884

815

925

850

964

880

1001

910

1600

-

-

-

-

-

-

864

770

908

805

948

835

987

870

1500

-

-

-

-

-

-

-

-

882

740

926

780

965

830

BCH060 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)

MODEL

BCH

AIR FLOW

CFM

Available External Static Pressure - IWG*

0.90

1.00

1.10

1.20

1.30

1.40

1.50

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

060

2500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2400

1193

1665

-

-

-

-

-

-

-

-

-

-

-

-

2300

1170

1580

1202

1620

-

-

-

-

-

-

-

-

-

-

2200

1148

1480

1180

1530

-

-

-

-

-

-

-

-

-

-

2100

1121

1385

1155

1425

1190

1475

-

-

-

-

-

-

-

-

2000

1100

1285

1133

1340

1169

1385

1205

1445

-

-

-

-

-

-

1900

1079

1180

1110

1240

1143

1280

1178

1330

1222

1375

-

-

-

-

1800

1058

1060

1090

1135

1122

1190

1158

1240

1196

1295

-

-

-

-

1700

1035

960

1071

1030

1103

1100

1134

1140

1164

1175

1197

1205

-

-

1600

1020

900

1056

965

1088

1035

1118

1065

1145

1105

1170

1130

1198

1150

1500

1004

860

1038

880

1070

925

1101

980

1130

1045

1158

1075

1184

1110

NOTE:  FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*

INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER
THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

MOTOR AND DRIVE DATA

-

Belt-Drive Blower

MODEL

BLOWER

RANGE

(RPM)

MOTOR*

ADJUSTABLE

MOTOR PULLEY

FIXED

BLOWER PULLEY

BELT

HP

RPM

FRAME

SIZE

SERVICE

FACTOR

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

LENGTH

(in.)

DESIG-

NATION

BCH 036

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

1

37.3

A36

BCH 048

790 - 1120

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.7

1

37.3

A36

BCH 060

850 - 1220

1-1/2

1725

56

1.15

2.4 - 3.4

7/8

5.2

1

37.3

A36

*

All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any
heating device.

MODEL

BCH

MOTOR

SPEED

Available External Static Pressure - IWG*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts

036

HI

MED
LOW

-

1660
1470

-

850
750

-

1630
1440

-

820
725

-

1590
1410

-

780
700

1720
1550
1370

825
750
675

1665
1500
1330

795
720
650

1600
1450
1290

765
690
625

1540
1400
1250

735
665
610

1490
1360
1220

700
650
600

1380
1270

1130

670
610
560

048

HI

MED
LOW

-

1810
1635

-

910
810

-

1780
1610

-

880
780

2000
1740
1580

1010

850
760

1950
1700
1555

975
825
740

1905
1665
1540

945
800
730

1840
1620
1510

910
775
715

1770
1560
1460

825
740
690

1660
1480
1400

825
700
660

1530
1390
1300

775
660
615

060

HI

MED
LOW

-

2390
2270

-

1350
1320

-

2350
2230

-

1300
1270

2500
2300
2190

1400
1255
1220

2420
2245
2145

1350
1210

1170

2340
2190
2090

1300

1165

1110

2260
2130
2030

1250

1120

1070

2160
2065
1960

1190

1075
1020

2060
1990
1890

1135

1030

970

1925
1900
1810

1065

970
920

NOTE:  FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*

INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER
THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.

230 / 460 / 575 VOLTS - SIDE DUCT APPLICATIONS

Summary of Contents for SUNLINE 2000 48

Page 1: ...DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit an...

Page 2: ...ompressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway filters The unit f...

Page 3: ...eaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by th...

Page 4: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1750 72 44 4 0 31 27 24 20 16 42 4 2 30 26 23 19 15 67 40...

Page 5: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 51 4 9 40 35 29 24 49 5 2 39 34 29 23 67 46 4 7 42...

Page 6: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 64 6 0 51 44 38 31 60 6 9 50 43 37 30 67 59 5 9 51...

Page 7: ...0 4 6 5 2 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 1600 55 MBH 12 1 17 0 22 0...

Page 8: ...NDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MODEL BCH AIR FLOW CFM Available External Static...

Page 9: ...AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower MODEL BLOWER RANGE R...

Page 10: ...PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 2 3 4 TO REMOTE SENSOR 2TH04702224 IF USED 2 1 24 volt thermostat with subbase 2TH1170022...

Page 11: ...76 6 53 8 63 7 77 7 101 6 125 5 60 70 80 110 150 60 70 80 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 4 4 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 57...

Page 12: ...2 1 1 2 10 2 15 3 20 4 24 9 30 7 37 1 25 30 40 25 30 40 060 208 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 2CE04503006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3 5...

Page 13: ...6 58 0 67 9 81 9 105 8 129 7 70 80 90 110 150 70 80 90 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 8 6 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 61 7 7...

Page 14: ...2 1 1 2 10 2 15 3 20 4 24 2 30 5 36 9 25 35 40 25 35 40 060 208 1 60 2CE04500525 2CE04500725 2CE04501025 2CE04501525 2CE04502025 2CE04503025 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3...

Page 15: ...made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet HOLE KNOCKOUT SIZE DIA USED...

Page 16: ...gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove and di...

Page 17: ...Y CORNER CORNER CORNER OPTIONS ACCESSORIES Electric Heat Nominal KW 5 7 KW 18 10 15 KW 23 20 30 KW 28 Economizer 50 Motorized Outdoor Air Damper 26 Barometric Relief Fixed Outdoor Air Intake Damper 10...

Page 18: ...ge conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 m...

Page 19: ...PLICATIONS TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT...

Page 20: ...all be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power ratin...

Page 21: ...utdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed a...

Page 22: ...me between compressor cycles 8 ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW OTHER FACTORY INSTALLED OPTIONS 1 HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHE...

Page 23: ...036 21564 002 A 0404 Unitary Products Group 23...

Page 24: ...Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A 035 21564 002 A 0404 Copyright 2004 by York International Corporation All Rights Reserved Supersedes 036...

Reviews: