036-21564-002-A-0404

Unitary Products Group

13

ELECTRICAL DATA

-

Basic Unit (Belt-Drive)

MODEL

BCH

POWER SUP-

PLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

COMPRESSOR

OUTDOOR

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60
208/230-3-60
460-3-60
575-3-60

187
187
414
518

253
253
504
630

19.0

11.9

5.9
4.8

105

85
42
34

1.7
1.7
1.0
1.0

5.3
5.3
3.1
3.1

34.1
21.9

11.5
11.1

50
30
15
15

50
30
15
15

048

208/230-1-60
208/230-3-60
460-3-60
575-3-60

187
187
414
518

253
253
504
630

25.0
14.7

7.7
6.4

105
130

64
52

2.3
2.3
1.4
1.4

8.6
5.2
2.6
2.0

38.6
25.9
13.6

11.4

60
40
20
15

60
40
20
15

060

208/230-1-60
208/230-3-60
460-3-60
575-3-60

187
187
414
518

253
253
504
630

32.1
19.3
10.0

7.9

169
123

62
50

2.3
2.3
1.4
1.4

8.6
6.0
3.0
2.4

51.4
32.4
16.9
13.7

80
50
25
20

80
50
25
20

NOTES:

1. Utilization Range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.

MODEL

BCH

POWER

SUPPLY

HEATER

ACCESSORY

MODEL

NUMBER

SUPPLY

AIR

BLOWER

MOTOR

FLA

ELECTRIC HEATERS

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE
SIZE

1

AMPS

MAX.

SIZE

HACR

2

BREAKER

AMPS

KW

STAGES

TOTAL

AMPS

036

208-1-60

2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006

8.6

4.0
5.6
8.0

11.9

15.9

1
1
1
2
2

19.1
27.1
38.3
57.4
76.6

58.0
67.9
81.9

105.8
129.7

70
80
90

110

150

70
80
90

110

150

230-1-60

2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006

8.6

5.3
7.5

10.6
15.9
21.2

1
1
1
2
2

22.1
31.2
44.2
66.2
88.3

61.7
73.1
89.3

116.9

144.5

70
80
90

125
150

70
80
90

125
150

208-3-60

2CE04500525*
2CE04500725*

2CE04501025
2CE04501525
2CE04502025

5.3

4.0
5.6
8.0

11.9

15.9

1
1
1
2
2

11.0

15.6
22.1
33.1
44.2

35.7
41.4
49.5
63.3
77.1

40
45
50
70
80

40
45
50
70
80

230-3-60

2CE04500525*
2CE04500725*

2CE04501025
2CE04501525
2CE04502025

5.3

5.3
7.5

10.6
15.9
21.2

1
1
1
2
2

12.7
18.0
25.5
38.2
51.0

37.8
44.4
53.7
69.7
85.6

45
50
60
70
90

45
50
60
70
90

460-3-60

2CE04500746*
2CE04501046*
2CE04501546*
2CE04502046*

3.1

6.8

10.1
13.6
19.5

1
1
1
2

8.2

12.1
16.4
23.5

21.7
26.7
31.9
40.8

25
30
35
45

25
30
35
45

575-3-60

2CE04501058
2CE04501558
2CE04502058

3.1

10.6
15.9
21.2

1
1
1

10.2
15.3
20.4

16.6
23.0
29.4

20
25
30

20
25
30

1

Dual element, time delay type

2

Standard circuit breakers may be used in Canada and on applications

over 60 amps where the heaters are separately fused.

*

These electric heaters DO NOT include a fuse box. If a fuse box is

required to meet a local code ((eg., Chicago), the following fuse
block accessories are available for field installation.

ELECTRICAL DATA

-

Heat Pump with Supplemental Electric Heat (Belt-Drive)

Electric Heat

Correction

Factors

Nominal Voltage

Voltage

KW Cap

Multipier

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

Fuse Block

2FB04700425

208/240 Volts

2FB04700546

460 Volts

Summary of Contents for SUNLINE 2000 48

Page 1: ...DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit an...

Page 2: ...ompressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway filters The unit f...

Page 3: ...eaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by th...

Page 4: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1750 72 44 4 0 31 27 24 20 16 42 4 2 30 26 23 19 15 67 40...

Page 5: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 51 4 9 40 35 29 24 49 5 2 39 34 29 23 67 46 4 7 42...

Page 6: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 64 6 0 51 44 38 31 60 6 9 50 43 37 30 67 59 5 9 51...

Page 7: ...0 4 6 5 2 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 1600 55 MBH 12 1 17 0 22 0...

Page 8: ...NDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MODEL BCH AIR FLOW CFM Available External Static...

Page 9: ...AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower MODEL BLOWER RANGE R...

Page 10: ...PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 2 3 4 TO REMOTE SENSOR 2TH04702224 IF USED 2 1 24 volt thermostat with subbase 2TH1170022...

Page 11: ...76 6 53 8 63 7 77 7 101 6 125 5 60 70 80 110 150 60 70 80 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 4 4 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 57...

Page 12: ...2 1 1 2 10 2 15 3 20 4 24 9 30 7 37 1 25 30 40 25 30 40 060 208 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 2CE04503006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3 5...

Page 13: ...6 58 0 67 9 81 9 105 8 129 7 70 80 90 110 150 70 80 90 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 8 6 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 61 7 7...

Page 14: ...2 1 1 2 10 2 15 3 20 4 24 2 30 5 36 9 25 35 40 25 35 40 060 208 1 60 2CE04500525 2CE04500725 2CE04501025 2CE04501525 2CE04502025 2CE04503025 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3...

Page 15: ...made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet HOLE KNOCKOUT SIZE DIA USED...

Page 16: ...gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove and di...

Page 17: ...Y CORNER CORNER CORNER OPTIONS ACCESSORIES Electric Heat Nominal KW 5 7 KW 18 10 15 KW 23 20 30 KW 28 Economizer 50 Motorized Outdoor Air Damper 26 Barometric Relief Fixed Outdoor Air Intake Damper 10...

Page 18: ...ge conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 m...

Page 19: ...PLICATIONS TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT...

Page 20: ...all be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power ratin...

Page 21: ...utdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed a...

Page 22: ...me between compressor cycles 8 ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW OTHER FACTORY INSTALLED OPTIONS 1 HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHE...

Page 23: ...036 21564 002 A 0404 Unitary Products Group 23...