036-21021-003 Rev. C (0203)
2
Unitary Products Group
All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request.
PHYSICAL AND ELECTRICAL DATA
MODELS
H4DE024
H4DE030
H4DE036
H4DE042
H4DE048
H4DE060
Unit Supply Voltage
208/230-1-60
Normal Voltage Range
1
187 TO 252
Minimum Circuit Ampacity
15.3
16.1
20.4
27.7
28.9
37.6
Max. Overcurrent Device Amps
2
20
25
35
45
40
50
Compressor Type
3
Recip
Recip
Scroll
B
Scroll
C
Scroll
C
Scroll
C
Compressor Amps
Rated Load
11.5
12.8
16.6
19.8
21.8
28.8
Locked Rotor
60.0
68.0
96.7
104.0
131.0
169.0
Crankcase Heater
No
No
No
No
No
No
Fan Motor Amps
Rated Load
0.9
0.9
0.9
1.4
1.6
1.6
Fan Diameter Inches
18
18
18
18
24
24
Fan Motor
Rated HP
1/8
1/8
1/8
1/4
1/4
1/4
Nominal RPM
1075
1075
1075
1100
850
850
Nominal CFM
2050
2050
2050
2300
3100
3100
Coil
Face Area Sq. Ft.
14.1
14.1
14.1
14.2
20.0
20.0
Rows Deep
1
1
1
1
1
1
Fin / Inches
18
18
18
20
13
18
Liquid Line OD
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line OD
3/4
3/4
3/4
7/8
7/8
7/8
Unit Charge (Lbs. - Oz.)
4
5 - 0
5 - 2
5 - 2
5 - 13
7 - 0
7 - 10
Charge Per Foot, Oz.
0.68
0.68
0.68
0.70
0.70
0.70
Operating Weight Lbs.
141
143
138
148
195
208
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker.
3. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add
or subtract the amount of refrigerant, using the difference in length multiplied by the per foot valve.
48" OVERHEAD
CLEARANCE
C
B
A
5-1/2
2-3/8
3-1/8
VAPOR
CONNECTION
LIQUID CONNECTION
AIR IN
4 SIDES
DIMENSIONS
UNIT
MODEL
HDE
DIMENSIONS
REFRIGERANT
CONNECTION
LINE SIZE
A
B
C
LIQUID VAPOR
024
30-1/8
24
24
3/8
3/4
030
30-1/8 24
24
036
30-1/8 24
24
042
30-1/8
24
24
7/8
048
31-7/8
35
35
060
31-7/8
35
35