036-21021-003 Rev. C (0203)

12

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: 

For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 

listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H4DE030S06

INDOOR COIL MODEL NO.

G1FA036S17,21

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

900

1000

1100

ID DB

85

80

75

70

85

80

75

70

85

80

75

70

ID WB

72

67

62

57

72

67

62

57

72

67

62

57

75

T.C.

33.5

30.6

27.7

25.1

34.0

31.1

28.1

25.4

34.3

31.4

28.4

25.7

S.C.

20.3

20.3

20.4

20.4

21.2

21.2

21.3

21.3

22.0

22.0

22.2

22.1

K.W

2.43

2.36

2.29

2.23

2.49

2.42

2.35

2.28

2.53

2.46

2.39

2.32

85

T.C.

32.5

29.7

26.9

24.3

32.9

30.0

27.2

24.9

33.2

30.3

27.5

25.3

S.C.

20.4

20.5

20.6

20.6

21.4

21.4

21.6

21.9

22.4

22.4

22.6

22.8

K.W

2.61

2.54

2.46

2.38

2.67

2.59

2.51

2.45

2.71

2.63

2.55

2.49

95

T.C.

30.8

28.1

25.4

23.2

31.1

28.4

25.7

23.6

31.3

28.6

26.2

23.8

S.C.

20.3

20.2

20.4

20.5

21.3

21.3

21.5

21.6

22.4

22.3

22.7

22.5

K.W

2.87

2.78

2.69

2.61

2.92

2.84

2.74

2.67

2.96

2.88

2.79

2.71

105

T.C.

28.6

26.1

23.7

21.5

28.8

26.3

24.0

22.1

29.0

26.6

24.3

22.6

S.C.

19.8

19.8

20.0

19.8

20.9

20.9

21.0

21.1

22.0

22.1

22.0

21.6

K.W

3.11

3.02

2.92

2.83

3.17

3.07

2.98

2.90

3.21

3.12

3.02

2.96

115

T.C.

26.2

23.9

21.8

20.1

26.3

24.2

22.1

20.5

26.5

24.4

22.5

20.9

S.C.

19.0

19.0

19.1

19.2

20.0

20.1

20.2

19.6

21.2

21.0

21.5

20.0

K.W

3.35

3.24

3.14

3.05

3.42

3.31

3.19

3.12

3.45

3.35

3.26

3.18

125

T.C.

23.8

21.7

19.9

18.7

23.8

22.1

20.2

18.9

24.0

22.2

20.7

19.2

S.C.

18.2

18.2

18.2

18.6

19.1

19.3

19.4

18.1

20.4

19.9

21.0

18.4

K.W

3.59

3.46

3.36

3.27

3.67

3.55

3.40

3.34

3.69

3.58

3.50

3.40

NOTE: 

ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

N1AHB1206

G2FD036(S,H)17

1.01

1.01

1.00 

N1AHB1206

G2FD046(S,H)17

1.02

1.02

0.99

N1VSB12

G2FD036(S,H)17

1.03

1.03

0.93

N1VSB12

G2FD046(S,H)17

1.04

1.04

0.96 

F2RC/F2FC030

0.99

0.99

0.98 

F2RP/F2FP030

1.01

1.01

1.00 

F2RP/F2FP036

1.02

1.02

0.95

G1FA030S14

0.99

0.99

0.99

G1FA048S21

1.02

1.02

1.01

G1HD036

1.01

1.01

1.00

G1NA030S17H

1.00

1.00

0.99

G1UA030S14

0.99

0.99

0.99

G1UA036S17,21

1.00

1.00

1.00

G1UA048S21

1.02

1.02

1.01

G2FD030(S,H)17

0.99

0.99

0.98

G2FD035(S,H)14

1.00

1.00

0.99

G2FD036(S,H)17

1.01

1.01

1.00

G2FD036(S,H)21

1.02

1.02

1.00

G2FD046(S,H)17

1.02

1.02

0.99

G2FD048(S,H)21,24

1.02

1.02

0.96

Variable Speed 

Furnace

Coil

T.C.

S.C.

KW

P1DUA12V G1FA030S14

1.00

1.00

0.94

P1DUA12V G1UA030S14

1.00

1.00

0.94

P1DUB16V G1FA036S17

1.02

1.02

0.92

P1DUB16V G1UA036S17

1.02

1.02

0.92

P1DUB16V G1UA048S17

1.05

1.05

0.94

P1DUB16V G2FD030(S,H)17

1.01

1.01

0.90

P1DUB16V G2FD036(S,H)17

1.04

1.04

0.92

P1XUB12V G1FA036S17

1.01

1.01

0.95

P1XUB12V G1UA036S17

1.01

1.01

0.95

P1XUB12V G2FD030(S,H)17

1.01

1.01

0.91

P1XUB12V G2FD036(S,H)17

1.03

1.03

0.93

P1XUC16V G1FA036S21

1.03

1.03

0.93

P1XUC16V G1FA048S21

1.05

1.05

0.94

P1XUC16V G1UA036S21

1.03

1.03

0.93

P1XUC16V G1UA048S21

1.05

1.05

0.94

P1XUC16V G2FD036(S,H)21

1.05

1.05

0.90

P1XUC16V G2FD048(S,H)21

1.05

1.05

0.89

Summary of Contents for STELLAR 2000 H*DE024

Page 1: ...PRESSOR The compressor is inter nally protected against high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi tions occur DURABLE FINISH Cabinet is made of powder painted steel over pre primered steel The pre treated galvanized steel provides a better paint...

Page 2: ... 14 1 14 2 20 0 20 0 Rows Deep 1 1 1 1 1 1 Fin Inches 18 18 18 20 13 18 Liquid Line OD 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line OD 3 4 3 4 3 4 7 8 7 8 7 8 Unit Charge Lbs Oz 4 5 0 5 2 5 2 5 13 7 0 7 10 Charge Per Foot Oz 0 68 0 68 0 68 0 70 0 70 0 70 Operating Weight Lbs 141 143 138 148 195 208 1 Rated in accordance with ARI Standard 110 utilization range A 2 Dual element fuses or HACR circuit breaker 3...

Page 3: ...Z G1FA G1UA024S14 17 59 63 6 G1FA G1UA030S14 65 63 8 67 10 G1FA G1UA036S14 17 21 73 63 10 67 2 73 0 G1FA G1UA048S17 21 84 7013 10 75 9 7023 9 78 5 87 0 G1FA G1UA060S21 24 90 87 7 90 1 G1NA030S17H 57 63 8 G1NA030S17K 63 67 4 G1NA036S17J 67 73 0 G1NA036S21C 67 73 0 G1NA048S21D 78 75 9 7023 5 7023 0 G2FD024 S H 14 17 61 63 8 G2FD030 S H 17 65 63 10 67 2 G2FD035 S H 14 65 63 10 67 2 73 0 G2FD036 S H 1...

Page 4: ...D060 S H 24 1675 51 0 37 7 12 60 11 30 H4DE060S06 N1VSD20 10 15 18 30 24 G2FD060 S H 24 1600 58 0 42 9 11 50 10 50 1 PH 11 SEER AC F2RP RC FP FC FV4 5 H4DE024S06 F2RC FC024 5 8 10 18 800 23 4 17 3 11 00 9 80 F2RC FC030 5 8 10 15 18 800 23 4 17 3 11 00 9 85 F2RP FP024 5 8 10 18 800 23 8 17 6 11 10 9 90 F2RP FP030 5 8 10 15 18 830 24 2 17 9 11 25 11 50 10 05 H4DE030S06 F2RC FC030 5 8 10 15 18 1015 2...

Page 5: ... G2FD036 S H 17 1015 28 6 21 5 11 20 10 10 21 G2FD036 S H 21 1015 29 0 21 8 11 10 10 20 17 G2FD046 S H 17 1015 29 0 21 8 12 00 10 30 21 24 G2FD048 S H 21 24 1015 29 0 21 8 12 00 10 60 H4DE036S06 1075 1375 14 G1FA036S14 1225 34 0 25 5 11 10 9 70 17 21 G1FA036S17 21 1225 34 0 25 5 11 10 9 60 17 G1FA048S17 1225 35 6 26 7 12 00 10 10 21 24 G1FA048S21 1225 35 6 26 7 11 50 12 00 10 10 G1HD036 1225 34 4 ...

Page 6: ...D3 H4DE024S06 P1DUA12V G1FA024S14 14 820 23 2 17 2 12 00 10 85 P1DUA12V G1FA030S14 14 820 23 6 17 5 12 00 10 90 P1DUA12V G1UA024S14 14 820 23 2 17 2 12 00 10 85 P1DUA12V G1UA030S14 14 820 23 6 17 5 12 00 10 90 P1DUA12V G2FD024 S H 14 14 820 23 6 17 5 11 50 10 20 P1XUB12V G1FA024S17 17 820 23 2 17 2 12 00 10 95 P1XUB12V G1FA036S17 17 820 24 6 18 2 12 00 10 95 P1XUB12V G1UA024S17 17 820 23 2 17 2 12...

Page 7: ...UC20V G1FA048S21 21 1200 36 2 27 2 12 60 10 90 P1XUC20V G1UA036S21 21 1200 34 8 26 1 12 00 10 60 P1XUC20V G1UA048S21 21 1200 36 2 27 2 12 60 10 90 P1XUC20V G2FD036 S H 21 21 1200 35 8 26 9 12 00 10 85 P1XUC20V G2FD042 S H 21 21 1200 36 2 27 2 12 00 10 80 P1XUC20V G2FD048 S H 21 21 1200 36 2 27 2 12 60 10 90 H4DE042S06 P1DUB16V G2FD046 S H 17 17 1425 41 5 31 1 11 50 10 60 P1DUC20V G1FA048S21 21 142...

Page 8: ...P1XUC20V G1FA060S21 21 1860 58 5 43 7 11 30 10 35 P1XUC20V G1UA060S21 21 1860 58 5 43 7 11 30 10 35 P1XUD20V G1FA060S24 24 1860 59 0 43 7 11 45 10 50 P1XUD20V G1UA060S24 24 1860 59 0 43 7 11 45 10 50 P1XUD20V G2FD060 S H 24 24 1860 59 0 43 7 11 45 10 50 1 G2FD coils available with a factory installed horizontal drain pan See price pages for specific model number 2 TXV Use 1TV700 Series Kit 3 Varia...

Page 9: ...RING TO BE IN ACCORDANCE WITH ELECTRIC CODE NEC AND OR LOCAL CODES POWER WIRING 208 230 1 60 230 1 50 CONTACTOR TERMINALS COIL GND LUG C Y R G W Y R G W POWER WIRING CONTROL WIRING FACTORY WIRING 24 VOLT CONTROL WIRING MINIMUM 18 GA WIRE NEC CLASS 2 FURNACE OR AIR HANDLER TERMINAL BLOCK ROOM THERMOSTAT CONDENSING UNIT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY TERMINAL W IS...

Page 10: ...Heat Stage only manual mechanical thermostat Add sub base for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermostat 1H 1C auto manual changeover electronic programmable For the most current accessory information refer to the price book or consult factory SOUND RATINGS Rated in accordance with ARI Standard ...

Page 11: ... C 18 8 17 2 15 5 14 3 19 0 17 3 15 7 14 5 19 0 17 4 15 9 14 7 S C 14 6 14 5 14 4 13 7 15 2 15 0 15 0 13 8 15 6 15 5 15 2 14 0 K W 2 46 2 37 2 28 2 21 2 49 2 40 2 32 2 25 2 52 2 43 2 35 2 28 125 T C 15 8 14 6 13 0 12 3 16 1 14 7 13 3 12 4 16 0 14 7 13 5 12 6 S C 13 7 13 5 13 2 12 0 14 3 14 0 13 9 11 8 14 6 14 4 13 8 12 0 K W 2 49 2 41 2 31 2 25 2 52 2 44 2 36 2 29 2 56 2 47 2 39 2 31 NOTE ALL CAPA...

Page 12: ... 20 0 20 1 20 2 19 6 21 2 21 0 21 5 20 0 K W 3 35 3 24 3 14 3 05 3 42 3 31 3 19 3 12 3 45 3 35 3 26 3 18 125 T C 23 8 21 7 19 9 18 7 23 8 22 1 20 2 18 9 24 0 22 2 20 7 19 2 S C 18 2 18 2 18 2 18 6 19 1 19 3 19 4 18 1 20 4 19 9 21 0 18 4 K W 3 59 3 46 3 36 3 27 3 67 3 55 3 40 3 34 3 69 3 58 3 50 3 40 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler...

Page 13: ...4 97 4 96 5 22 5 11 5 02 4 98 5 27 5 14 5 09 5 07 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1AHB1206 G2FD036 S H 17 1 03 1 03 1 01 N1AHB1206 G2FD046 S H 17 1 04 1 04 0 99 N1VSB12 G2FD036 S H 17 1 01 1 01 0 91 N1VSB12 G2FD046 S H 17 1 05 1 05 0 94 F2RC F2FC036 0 99 0 99 0 93 F2RP F2FP036 1 04 1 04 0 94 G1FA036S14 1 00 1 00 0...

Page 14: ...T C 39 8 36 7 33 7 30 9 40 0 36 9 33 9 31 2 40 1 37 1 34 1 31 5 S C 28 1 28 2 28 7 28 8 29 2 29 4 29 8 30 0 30 3 30 4 30 8 30 9 K W 5 02 4 97 4 90 4 84 5 07 5 02 4 95 4 89 5 12 5 06 5 00 4 95 125 T C 37 7 34 7 31 9 29 1 37 8 34 8 32 0 29 5 37 8 35 1 32 2 29 8 S C 27 4 27 4 27 9 27 7 28 5 28 7 29 0 29 2 29 6 29 7 30 0 29 9 K W 5 48 5 44 5 36 5 30 5 53 5 49 5 41 5 34 5 59 5 52 5 46 5 41 NOTE ALL CAP...

Page 15: ...S C 32 0 32 1 32 8 32 7 33 6 33 8 34 1 34 3 35 0 35 3 35 6 36 7 K W 6 01 5 88 5 73 5 62 6 07 5 94 5 82 5 69 6 16 6 01 5 89 5 82 125 T C 43 5 40 1 36 9 33 6 44 0 40 6 37 2 34 0 44 0 40 8 37 4 36 1 S C 31 2 31 2 32 0 31 4 32 9 33 0 32 8 33 1 33 9 34 3 34 3 36 2 K W 6 57 6 43 6 25 6 14 6 63 6 48 6 37 6 21 6 74 6 55 6 43 6 39 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BT...

Page 16: ... 42 8 42 7 43 3 43 9 44 4 44 3 44 6 45 7 46 0 K W 5 81 5 73 5 64 5 55 5 88 5 80 5 71 5 63 5 94 5 86 5 78 5 69 105 T C 58 9 54 6 50 1 46 1 59 3 54 9 50 7 46 6 59 5 55 3 51 0 46 9 S C 40 1 40 4 41 0 41 3 41 7 42 0 43 0 43 2 43 3 43 7 44 3 44 5 K W 6 46 6 38 6 30 6 21 6 56 6 45 6 36 6 28 6 60 6 51 6 43 6 35 115 T C 55 3 51 1 47 1 43 3 55 5 51 4 47 5 43 7 55 8 51 8 47 9 44 2 S C 39 0 38 9 39 8 40 1 40...

Page 17: ...OSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UPFLOW G1FA FULL CASED AIR HANDLERS FOR NON FURNACE APPLICATIONS N1AH OR N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F2RC F2FC OR F2RC F2FP FAN COIL UNITS UPFLOW HORIZONTAL G2FD COIL ...

Page 18: ...036 21021 003 Rev C 0203 18 Unitary Products Group NOTES ...

Page 19: ...036 21021 003 Rev C 0203 Unitary Products Group 19 ...

Page 20: ...hange without notice Printed in U S A 036 21021 003 Rev C 0203 Copyright by York International Corp 2003 All rights reserved Supersedes 036 21021 003 Rev B 0702 Unitary 5005 Norman Product York OK Group Drive 73069 ...

Reviews: