246695-YTG-C-0708
Johnson Controls Unitary Products
15
TABLE 11: ADDITIONAL STATIC RESISTANCE
CFM
Cooling Only
1
Economizer
2
3
Electric Heat KW
2
18
24
36
54
3700
0.20
0.04
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.37
0.41
0.43
0.49
5500
0.45
0.06
0.40
0.44
0.46
0.53
5700
0.48
0.06
0.43
0.47
0.49
0.56
5900
0.52
0.07
0.46
0.50
0.53
0.59
6100
0.56
0.07
0.49
0.53
0.56
0.62
6300
0.60
0.07
0.53
0.56
0.59
0.65
1
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 12: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM
HEATER
UNIT NOMINAL TONS
kW
VOLTAGE
12.5
MINIMUM SUPPLY AIR CFM
18
208/230
3750
24
36
54
18
480
3750
24
36
54
18
600
3750
24
36
54
TABLE 13: INDOOR BLOWER SPECIFICATIONS
MODEL
MOTOR
MOTOR SHEAVE
BLOWER SHEAVE
BELT
HP
RPM
Eff.
SF
Frame
Datum Dia. (in.)
Bore (in.)
Model
Datum Dia. (in.)
Bore (in.)
Model
DJ150
3
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.0
1
AK74
A54
5
1725
87%
1.15
184T
4.3 - 5.3
1 1/8
1VP56
6.7
1
BK77
BX55
TABLE 14: POWER EXHAUST SPECIFICATIONS
POWER EXHAUST
MODEL
VOLT
PHASE
MOTOR
ELECTRICAL
FUSE
SIZE
CFM@
0.1 ESP
HP
RPM
1
1
Motors are multi-tapped and factory wired for high speed.
QTY
LRA
FLA
MCA
2PE0473125
208/230
1
0.75
1075
1
24.9
5.0
6.3
10
3,800
2PE0473146
460
1
N/A
2.2
2.8
5
2PE0473158
575
1
1050
1.5
1.9
4