246695-YTG-C-0708

Johnson Controls Unitary Products

11

TABLE 5: DJ 150 (12 1/2 TON) COOLING CAPACITY

Air On

Evap. Coil

Temperature of Air on Condenser Coil 85°F

Temperature of Air on Condenser Coil 95°F

CFM

WB
(°F)

Tot.

Cap.

1

(MBH)

Tot.

Input

2

(kW)

Sensible Capacity (MBH)

1

Return Dry Bulb (°F)

Tot.

Cap.

1

(MBH)

Tot.

Input

2

(kW)

Sensible Capacity (MBH)

1

Return Dry Bulb (°F)

86

83

80

77

74

71

68

86

83

80

77

74

71

68

3750

72 173

10.9

102

92

81

70

60

49

38

168

11.8

101

90

79

69

58

47

37

67 160

10.6

127

116

105

95

84

73

63

154

11.6

124

114

103

92

81

71

60

62 148

10.5

148

141

131

120

109

99

88

143

11.4

143

138

127

116

106

95

84

57 147

10.5

147

144

133

123

112

101

91

141

11.5

141

137

126

116

105

94

84

4375

72 177

10.9

112

100

87

74

62

49

37

170

11.8

111

98

85

73

60

47

35

67 163

10.7

138

126

113

101

88

75

63

156

11.7

136

123

110

98

85

72

60

62 151

10.6

151

148

141

128

115

103

90

145

11.5

145

142

136

124

111

98

86

57 150

10.5

150

149

143

131

118

106

93

143

11.5

143

141

136

123

110

98

85

5000

72 180

11.0

122

108

93

79

64

49

35

173

11.9

120

106

91

76

62

47

33

67 167

10.7

150

136

121

107

92

77

63

158

11.8

147

132

118

103

89

74

60

62 154

10.6

154

154

150

136

121

107

92

147

11.6

147

147

146

131

116

102

87

57 154

10.6

154

154

154

139

124

110

95

145

11.6

145

145

145

130

116

101

87

5625

72 184

11.0

133

116

100

83

66

50

33

176

12.0

131

114

98

81

65

48

31

67 170

10.8

162

146

129

113

96

80

63

161

11.8

155

143

127

110

93

77

60

62 157

10.7

157

157

155

139

122

106

89

150

11.7

150

150

149

132

116

99

83

57 157

10.6

157

157

157

140

123

107

90

147

11.7

147

147

147

131

114

98

81

6250

72 188

11.1

143

125

106

87

69

50

32

179

12.1

142

123

105

86

67

49

30

67 173

10.8

173

156

138

119

101

82

63

164

11.9

164

154

135

117

98

79

61

62 161

10.7

161

161

161

142

123

105

86

152

11.7

152

152

152

134

115

96

78

57 160

10.6

160

160

160

141

122

104

85

150

11.8

150

150

150

131

113

94

75

Temperature of Air on Condenser Coil 105°F

Temperature of Air on Condenser Coil 115°F

3750

72 158

13.0

99

88

77

67

56

45

34

148

14.3

96

86

75

64

54

43

32

67 145

12.9

120

110

99

88

78

67

56

136

14.2

116

106

95

84

74

63

52

62 134

12.7

134

129

119

108

97

87

76

125

14.0

125

121

110

100

89

78

67

57 134

12.8

134

130

119

109

98

87

77

128

14.2

128

123

112

102

91

80

70

4375

72 160

13.1

109

96

83

71

58

45

33

150

14.4

107

94

81

69

56

43

31

67 147

13.0

132

119

107

94

81

69

56

138

14.2

128

116

103

90

78

65

52

62 136

12.8

136

134

128

115

103

90

77

127

14.1

127

125

120

107

94

82

69

57 136

12.9

136

134

129

116

103

91

78

130

14.2

130

127

122

109

97

84

71

5000

72 162

13.2

119

104

89

75

60

46

31

152

14.4

117

102

88

73

58

44

29

67 149

13.0

144

129

114

100

85

71

56

140

14.3

140

126

111

96

82

67

53

62 138

12.8

138

138

137

123

108

93

79

129

14.1

129

129

129

114

100

85

70

57 138

12.9

138

138

138

124

109

94

80

131

14.3

131

131

131

117

102

88

73

5625

72 165

13.2

129

112

96

79

63

46

29

155

14.5

127

111

94

77

61

44

28

67 152

13.1

149

139

123

106

90

73

56

143

14.3

143

135

119

102

86

69

53

62 140

12.9

140

140

140

123

107

90

74

131

14.1

131

131

131

114

98

81

65

57 141

13.0

141

141

141

124

107

91

74

134

14.3

134

134

134

117

100

84

67

6250

72 168

13.3

140

121

102

84

65

47

28

157

14.5

138

119

100

82

63

44

26

67 154

13.1

154

150

131

113

94

75

57

145

14.3

145

145

127

108

90

71

53

62 143

12.9

143

143

143

124

106

87

68

133

14.2

133

133

133

115

96

77

59

57 143

13.0

143

143

143

124

106

87

68

136

14.3

136

136

136

117

99

80

61

Temperature of Air on Condenser Coil 125°F

3750

72 137

15.6

94

83

73

62

51

41

30

67 127

15.5

112

102

91

80

70

59

48

62 116

15.3

116

113

102

91

81

70

59

57 121

15.5

121

116

105

95

84

73

63

4375

72 139

15.7

105

92

79

67

54

41

29

67 129

15.5

125

112

99

87

74

61

49

62 118

15.3

118

116

111

99

86

73

61

57 123

15.5

123

120

115

102

90

77

64

5000

72 141

15.7

115

100

86

71

57

42

28

67 131

15.5

131

122

108

93

78

64

49

62 120

15.3

120

120

120

106

91

77

62

57 125

15.6

125

125

125

110

95

81

66

5625

72 144

15.7

125

109

92

75

59

42

26

67 133

15.5

133

131

115

99

82

65

49

62 122

15.4

122

122

122

106

89

72

56

57 127

15.6

127

127

127

110

94

77

60

6250

72 146

15.7

135

117

98

80

61

42

24

67 136

15.6

136

136

123

104

86

67

48

62 124

15.4

124

124

124

105

87

68

49

57 129

15.6

129

129

129

110

92

73

54

1

These capacities are gross ratings. For net 
capacity, deduct air blower motor, MBh = 3.415 
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air 
blower motor.

2

These ratings include condenser fan motors 
(total 1 kW)  and the compressor motors but 
not the supply air blower motor.

Summary of Contents for PREDATORTM MAGNUM DJ 150

Page 1: ...cations and can be easily installed on a roof curb slab or frame All Predator Magnum units are self contained and assembled on rigid full perimeter base rails allowing for 3 way forklift access and overhead rigging Every unit is completely charged wired piped and tested at the factory to provide a quick and easy field installation All units are convertible between side and down airflow Inde penden...

Page 2: ...OMIZER DOWNFLOW W POWER EXHAUST 22 15 SLAB ECONOMIZER END RETURN W POWER EXHAUST 22 16 COOLING UNIT WITH GAS HEAT WIRING 230 V DIAGRAM 23 17 COOLING UNIT W WO ELECTRIC HEAT WIRING DIAGRAM 24 18 COOLING UNIT WITH GAS HEAT WIRING 460 575 50 HZ DIAGRAM 25 LIST OF TABLES Tbl Pg 1 ACCESSORIES 8 2 PHYSICAL DATA 10 3 DJ 150 12 1 2 TON CAPACITY RATINGS 10 4 UNIT VOLTAGE LIMITATIONS 10 5 DJ 150 12 1 2 TON ...

Page 3: ...ard ization removes any confusion on which filter sizes are needed for replacement The non corrosive drain pan slides out of the unit to per mit easy cleaning The drain pan is accessed by remov ing the drain pan cover plate on the rear of the unit Once the plate is removed the drain pan slides out through the rear of the unit All Predator Magnum units have a second model name plate located inside ...

Page 4: ...ou re out philosophy The high and low pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor On Board Diagnostics Each alarm will energize a trouble light on the thermostat if so equipped and flash an alarm code on the control board LED Each high and low pressure switch alarm as well as each freezestat alar...

Page 5: ...gulated by the standard single enthalpy input There is an optional input dual dry bulb available To meet regulated air standards the economizer control accepts an optional CO2 input for demand ventilation With single enthalpy input the economizer control monitors outdoor air The dual enthalpy kit provides a second input used to mon itor the return air With a dual input kit installed the economizer...

Page 6: ...BAS Control The Novar ETC 3 building automation system controller is factory installed Incudes supply air sensor return air sensor dirty filter indicator switch and air proving switch Johnson Controls BAS Control The Johnson Control YK UNT 1126 building automation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switc...

Page 7: ...y interfere with proper exhausting of furnace combustion products this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes 60 F Gas Heat Kit For installations which require gas heat units to perform in low ambient temperatures a gas section heating kit is available This kit provides electric heat in the gas heat controls section to ensure the gas valve and contr...

Page 8: ...Slab Downflow Incl Dampers only no Hoods or Barometric Relief 2PE04703225 Power Exhaust Downflow 230V For Units with Economizer only 2PE04703246 Power Exhaust Downflow 460V For Units with Economizer only 2PE04703258 Power Exhaust Downflow 580V For Units with Economizer only 2EC04700924 Dual Enthalpy Control Use with Single Enthalpy Economizer 1EH0407 Hood Kit Downflow Economizer Included with all ...

Page 9: ...tion 1 C Option 2 D Options 1 2 E Option 3 F Option 4 G Options 1 3 H Options 1 4 J Options 1 2 3 K Options 1 2 4 L Options 1 3 4 M Options 1 2 3 4 N Options 2 3 P Options 2 4 Q Options 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S A 4 Smoke Detector ...

Page 10: ... lb oz 20 8 Compressors Quantity 2 Type Scroll Air Filters Size Wd x Ht x Thickness in 25x20x2 Number Per Unit 4 TABLE 3 DJ 150 12 1 2 TON CAPACITY RATINGS Size Tons Model Cooling Capacity ARI Ratings1 CFM Sound Rating dB 2 Nominal Electric Heat Capacity3 kW Gas Heat Capacity Gas Line Size in OD MBH EER IPLV Input MBH Output MBH Seasonal Efficiency Temp Rise F 150 12 1 2 Cooling Only 150 11 35 12 ...

Page 11: ...0 100 89 78 67 57 134 12 8 134 130 119 109 98 87 77 128 14 2 128 123 112 102 91 80 70 4375 72 160 13 1 109 96 83 71 58 45 33 150 14 4 107 94 81 69 56 43 31 67 147 13 0 132 119 107 94 81 69 56 138 14 2 128 116 103 90 78 65 52 62 136 12 8 136 134 128 115 103 90 77 127 14 1 127 125 120 107 94 82 69 57 136 12 9 136 134 129 116 103 91 78 130 14 2 130 127 122 109 97 84 71 5000 72 162 13 2 119 104 89 75 ...

Page 12: ...5 0 0 Maximum HACR breaker of the same AMP size is applicable 6 7 60 0 0 6 4 1 6 0 1 8 MCA w Power Exhaust Amps Max Fuse Size Amps Max Fuse Size w Power Exhaust Amps FLA Pwr Conv Outlet Heater Amps Min Circuit Ampacity Amps FLA 208 20 0 146 0 1 5 230 460 575 Voltage Compressors OD Fan Motors Supply Blower Motor FLA 1 1 TABLE 7 ELECTRICAL DATA DJ150 12 1 2 TON WITH PWRD CONVENIENCE OUTLET RLA LRA F...

Page 13: ...3 75 3496 1221 3 93 3659 1265 4 20 3916 4800 870 2 46 2291 935 2 69 2508 991 2 96 2755 1033 3 09 2879 1078 3 35 3126 1125 3 58 3335 1164 3 72 3467 1201 3 90 3635 1229 4 09 3810 1273 4 38 4080 4900 887 2 58 2406 952 2 81 2622 1007 3 09 2883 1048 3 23 3011 1092 3 50 3265 1138 3 73 3473 1175 3 87 3605 1211 4 05 3779 1237 4 26 3967 1282 4 56 4250 5000 903 2 71 2527 968 2 94 2744 1022 3 24 3016 1062 3 ...

Page 14: ...1046 2 95 2749 1090 3 14 2925 1132 3 33 3103 1173 3 52 3281 1212 3 71 3459 1251 3 90 3634 1289 4 08 3807 1325 4 27 3977 4600 972 2 72 2536 1019 2 91 2708 1063 3 10 2886 1106 3 29 3066 1148 3 48 3247 1188 3 68 3428 1227 3 87 3606 1266 4 06 3782 1303 4 24 3955 1338 4 43 4125 4700 991 2 86 2667 1036 3 05 2846 1081 3 25 3029 1123 3 45 3212 1164 3 64 3396 1204 3 84 3578 1242 4 03 3758 1280 4 22 3933 13...

Page 15: ...hown in the respective Blower Performance Table 3 The pressure drop through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer operation TABLE 12 ELECTRIC HEAT MINIMUM SUPPLY AIR CFM HEATER UNIT NOMINAL TONS kW VOLTAGE 12 5 MINIMUM SUPPLY AIR CFM 18 208 230...

Page 16: ... LEFT FRONT 60 25 LEFT FRONT FIGURE 4 UNIT WITH 6 POINT LOAD TABLE 16 6 POINT LOAD WEIGHT Model Locations lbs A B C D E F DJ150 184 210 246 323 275 242 TABLE 17 UNIT WEIGHTS Model DJ150 Shipping Weight lb Operating Weight lb Cooling Unit Only 1495 1480 w Economizer 85 84 w Power Exhaust 150 148 w Gas Heat1 1 8 Tube Heat Exchanger 110 110 w Electric Heat2 2 54 kW heater 49 49 A B C F E D LEFT FRONT...

Page 17: ...Units must be installed outdoors Overhanging structure or shrubs should not obstruct condenser air discharge outlet 72 Right 12 Front 36 Left 36 Rear2 2 To remove the slide out drain pan a rear clearance of 60 is required If space is unavailable the drain pan can be removed through the front by separating the corner wall 36 Bottom3 3 Units may be installed on combustible floors made from wood or c...

Page 18: ... S U L A T E D D E C K U N D E R C O M P R E S S O R S E C T I O N I N S U L A T E D D E C K U N D E R C O N D E N S E R S E C T I O N F R O N T R I G H T S U P P L Y R E T U R N FIGURE 7 SUNLINE TO PREDATOR MAGNUM TRANSITION ROOF CURBS 7 6 5 8 9 4 5 0 1 2 3 0 1 2 6 4 1 4 5 9 1 4 1 0 2 3 4 2 6 8 0 5 8 2 T Y P F R O N T R I G H T S U P P L Y R E T U R N ...

Page 19: ... 6 13 16 21 3 16 19 3 16 17 3 16 7 1 8 14 23 32 16 3 8 18 1 16 19 5 8 63 1 2 27 1 2 18 24 21 12 5 16 LEFT FRONT Bottom Condensate Drain Bottom Power Control and Convenience Outlet Wiring Entries Bottom Gas Supply Entry FIGURE 9 SIDEFLOW DUCT DIMENSIONS Return Air Supply Air 18 1 4 18 1 4 28 1 4 31 11 16 28 1 4 18 1 16 2 31 32 5 5 32 Dot Plugs ...

Page 20: ... 2EE04705424 Side Return Horizontal economizer without barometric relief 2EE047055241 1 Barometric relief must be ordered separately and installed in duct work ERV or End Return Slab Economizer 50 tall cabinet 2EE047052242 2 Barometric relief or fresh air hood not included Must be ordered separately 2EE04705424 Fresh Air Hood 2EE04705424 Fresh Air Damper 2EE04705424 Return Air Damper 2EE04705424 B...

Page 21: ...EE04705424 Fresh Air Hood 2EE04705424 Fresh Air Damper 2EE04705424 Return Air Damper 2PE047032XX Power Exhaust 2EE04705424 Barometric Relief Damper 2EE04705424 Barometric Relief Hood 1EH0408 Barometric Relief Hood 1EH0408 Barometric Relief Damper 2PE047032XX Power Exhaust 2EE04705524 Fresh Air Hood 2EE04705524 Fresh Air Damper 2EE04705524 Return Air Damper Field Installed Duct Work ...

Page 22: ...END RETURN W POWER EXHAUST 2EE04705X24 Slab Economizer 2PE047032XX Power Exhaust 1EH0409 Barometric Relief Damper 1EH0409 Barometric Relief Hood 1EH0409 Fresh Air Hood 2EE04705X24 Slab Economizer 1EH0409 Barometric Relief Hood 1EH0409 Barometric Relief Damper 1EH0409 Fresh Air Hood 2PE047032XX Power Exhaust Field Installed Duct Work ...

Page 23: ...246695 YTG C 0708 Johnson Controls Unitary Products 23 FIGURE 16 COOLING UNIT WITH GAS HEAT WIRING 230 V DIAGRAM ...

Page 24: ...246695 YTG C 0708 24 Johnson Controls Unitary Products FIGURE 17 COOLING UNIT W WO ELECTRIC HEAT WIRING DIAGRAM ...

Page 25: ...246695 YTG C 0708 Johnson Controls Unitary Products 25 FIGURE 18 COOLING UNIT WITH GAS HEAT WIRING 460 575 50 HZ DIAGRAM ...

Page 26: ...vent insulation from entering the air stream Cabinet doors shall be hinged with toolless access for easy servicing and maintenance Full perimeter base rails shall be provided to assure reliable transit of equipment overhead rigging fork truck access and proper sealing on roof curb applications Disposable 2 filters shall be fur nished and be accessible through hinged access door Fan performance mea...

Page 27: ...structed of aluminum coated steel All gas piping shall enter the unit cabinet at a single location through either the side or bottom without any field modifications An integrated control board shall provide timed control of evaporator fan functioning and burner ignition Heating section shall be pro vided with the following minimum protection a Primary and auxiliary high temperature limit switches ...

Page 28: ...r static output and or higher airflow CONVENIENCE OUTLET POWERED NON POW ERED Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors PHASE MONITOR Designed to prevent damage in out of phase condition COIL GUARD Designed to prevent condenser coil damage BAS CONTROLS Include supply air sensor return air sensor dirty filter indicator and ...

Reviews: