246824-YTG-G-1208
Johnson Controls Unitary Products
53
115°F
125°F
1625
77
72.6
8.1
28.9
26.6
19.6
-
-
-
66.7
8.9
29.0
22.9
17.6
-
-
-
72
66.3
8.1
44.0
37.1
30.2
23.2
-
-
60.6
8.9
41.7
34.8
27.9
21.0
-
-
67
60.1
8.0
59.2
47.6
40.7
33.8
26.8
-
54.5
8.9
54.5
45.1
38.2
31.3
24.4
-
62
54.6
8.0
54.6
54.6
44.9
38.0
31.0
24.1
49.3
8.8
49.3
49.3
39.3
32.3
25.4
18.5
1950
77
74.7
8.1
38.0
29.8
21.7
-
-
-
68.1
8.9
38.6
27.6
19.5
-
-
-
72
68.3
8.0
49.6
41.5
33.4
25.3
-
-
61.9
8.8
47.1
39.1
31.0
22.9
-
-
67
61.9
8.0
61.3
53.2
45.1
37.0
28.8
-
55.7
8.8
55.7
50.5
42.4
34.4
26.3
-
62
56.2
7.9
56.2
56.2
49.8
41.6
33.5
25.4
50.3
8.7
50.3
50.3
43.6
35.5
27.5
19.4
57
60.0
8.0
60.0
60.0
53.1
45.0
36.9
28.8
55.6
8.9
55.6
55.6
48.3
40.2
32.2
24.1
2275
77
76.9
8.1
47.1
33.1
23.8
-
-
-
69.5
8.8
48.2
32.3
21.5
-
-
-
72
70.3
8.0
55.3
46.0
36.7
27.4
-
-
63.2
8.8
52.5
43.3
34.1
24.8
-
-
67
63.7
8.0
63.4
58.8
49.5
40.2
30.9
-
56.8
8.8
56.8
55.9
46.7
37.4
28.2
-
62
57.8
7.9
57.8
57.8
54.6
45.3
36.0
26.7
51.3
8.7
51.3
51.3
48.0
38.7
29.5
20.3
57
61.8
8.0
61.8
61.8
58.3
49.0
39.7
30.4
56.8
8.8
56.8
56.8
53.1
43.9
34.7
25.5
2600
77
79.0
8.0
56.2
36.4
25.9
-
-
-
70.9
8.8
57.8
37.1
23.4
-
-
-
72
72.3
8.0
60.9
50.4
39.9
29.4
-
-
64.4
8.8
57.9
47.5
37.2
26.8
-
-
67
65.5
7.9
65.5
64.3
53.9
43.4
32.9
-
58.0
8.8
58.0
58.0
50.9
40.5
30.1
-
62
59.4
7.9
59.4
59.4
59.4
49.0
38.5
28.0
52.3
8.7
52.3
52.3
52.3
42.0
31.6
21.2
57
63.5
8.0
63.5
63.5
63.5
53.0
42.5
32.1
57.9
8.8
57.9
57.9
57.9
47.6
37.2
26.8
2925
72
73.5
8.0
65.1
53.8
42.6
31.3
-
-
65.1
8.8
62.0
50.8
39.7
28.5
-
-
67
66.6
8.0
66.6
66.0
57.5
46.2
35.0
-
58.6
8.8
58.6
58.6
54.3
43.2
32.0
-
62
60.4
7.9
60.4
60.4
60.4
49.2
37.9
26.6
52.9
8.7
52.9
52.9
52.9
41.7
30.6
19.4
57
64.5
8.0
64.5
64.5
64.5
53.3
42.0
30.8
58.6
8.9
58.6
58.6
58.6
47.4
36.3
25.1
3250
72
74.7
8.1
69.4
57.3
45.3
33.2
-
-
65.8
8.9
65.8
54.1
42.2
30.3
-
-
67
67.7
8.0
67.7
67.7
61.1
49.1
37.0
-
59.2
8.9
59.2
59.2
57.8
45.9
33.9
-
62
61.4
8.0
61.4
61.4
61.4
49.4
37.3
25.3
53.4
8.8
53.4
53.4
53.4
41.5
29.6
17.7
57
65.6
8.0
65.6
65.6
65.6
53.5
41.5
29.5
59.2
8.9
59.2
59.2
59.2
47.3
35.4
23.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65