246824-YTG-G-1208
Johnson Controls Unitary Products
41
115°F
125°F
2125
77
102.2
10.3
39.0
35.2
25.4
-
-
-
95.6
11.4
36.2
31.0
22.6
-
-
-
72
93.5
10.1
60.2
50.4
40.6
30.8
-
-
86.5
11.1
56.8
47.1
37.5
27.8
-
-
67
84.8
10.0
81.3
65.5
55.8
46.0
36.2
-
77.4
10.9
77.4
62.1
52.4
42.7
33.1
-
62
78.5
9.9
78.5
78.5
63.8
54.0
44.2
34.4
71.8
10.8
71.8
71.8
57.3
47.7
38.0
28.3
2550
77
105.2
10.4
51.2
39.7
28.3
-
-
-
98.0
11.4
49.9
36.6
25.3
-
-
-
72
96.2
10.2
68.1
56.6
45.2
33.7
-
-
88.7
11.2
64.7
53.3
41.9
30.6
-
-
67
87.3
10.0
85.0
73.5
62.0
50.6
39.1
-
79.4
11.0
79.4
70.0
58.6
47.3
35.9
-
62
80.8
9.9
80.8
80.8
71.0
59.6
48.1
36.6
73.6
10.9
73.6
73.6
64.2
52.8
41.5
30.1
57
79.6
10.0
79.6
79.6
69.9
58.5
47.0
35.5
73.3
11.0
73.3
73.3
63.4
52.1
40.7
29.3
2975
77
108.2
10.4
63.4
44.3
31.1
-
-
-
100.5
11.4
63.7
42.3
28.0
-
-
-
72
99.0
10.2
76.0
62.9
49.7
36.6
-
-
90.9
11.2
72.5
59.5
46.4
33.4
-
-
67
89.8
10.0
88.6
81.5
68.3
55.2
42.1
-
81.4
11.0
81.4
77.9
64.8
51.8
38.7
-
62
83.1
9.9
83.1
83.1
78.2
65.1
51.9
38.8
75.4
10.9
75.4
75.4
71.0
58.0
44.9
31.9
57
81.8
10.0
81.8
81.8
77.0
63.9
50.7
37.6
75.1
11.0
75.1
75.1
70.2
57.1
44.1
31.0
3400
77
111.2
10.4
75.7
48.8
34.0
-
-
-
102.9
11.4
77.4
47.9
30.7
-
-
-
72
101.7
10.2
84.0
69.1
54.3
39.5
-
-
93.1
11.2
80.4
65.6
50.9
36.1
-
-
67
92.3
10.0
92.3
89.5
74.6
59.8
45.0
-
83.3
11.0
83.3
83.3
71.1
56.3
41.6
-
62
85.4
9.9
85.4
85.4
85.4
70.6
55.8
41.0
77.3
10.9
77.3
77.3
77.3
63.1
48.4
33.6
57
84.1
10.0
84.1
84.1
84.1
69.3
54.5
39.6
77.0
11.0
77.0
77.0
77.0
62.2
47.5
32.7
3825
72
102.6
10.3
89.7
73.7
57.7
41.8
-
-
93.9
11.3
86.0
70.1
54.1
38.2
-
-
67
93.0
10.1
93.0
91.6
79.3
63.3
47.4
-
84.0
11.1
84.0
84.0
75.6
59.7
43.8
-
62
86.1
10.0
86.1
86.1
86.1
70.1
54.2
38.2
77.9
11.0
77.9
77.9
77.9
62.3
46.4
30.5
57
84.8
10.1
84.8
84.8
84.8
68.8
52.8
36.9
77.6
11.1
77.6
77.6
77.6
61.7
45.8
29.8
4250
72
103.4
10.3
95.4
78.3
61.1
44.0
-
-
94.7
11.4
91.6
74.5
57.4
40.3
-
-
67
93.8
10.1
93.8
93.8
84.0
66.9
49.7
-
84.7
11.1
84.7
84.7
80.2
63.1
46.0
-
62
86.8
10.0
86.8
86.8
86.8
69.7
52.6
35.4
78.6
11.1
78.6
78.6
78.6
61.5
44.4
27.3
57
85.5
10.1
85.5
85.5
85.5
68.3
51.2
34.1
78.2
11.2
78.2
78.2
78.2
61.2
44.1
27.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZR102 (8.5 Ton) Cooling (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65