246721-YTG-C-0606
16
Unitary Products Group
TABLE 3: DR CAPACITY RATINGS
Size
Model
Cooling Capacity
ARI Ratings
1
CFM
Sound
Rating
(dB)
2
Nominal
Electric
Heat
Capacity
3
(kW)
Gas Heat Capacity
Gas
Line
Size
(in. OD)
MBH
EER
IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
090
Cooling
Only
90
11.2
11.65
3000
84
-
-
-
-
-
-
Electric
Heat
9, 18, 24,
36
-
-
-
-
-
Gas Heat
-
120
96
80
15-45
3/4
Gas Heat
-
180
144
80
30-60
3/4
120
Cooling
Only
116
11.2
11.40
3480
90
-
-
-
-
-
-
Electric
Heat
18, 24, 36,
54
-
-
-
-
-
Gas Heat
-
180
144
80
20-50
3/4
Gas Heat
-
240
192
80
35-65
3/4
150
Cooling
Only
148
11.1
11.7
3750
86
-
-
-
-
-
-
Electric
Heat
18, 24, 36,
54
-
-
-
-
-
Gas Heat
-
180
144
80
10-40
3/4
Gas Heat
-
240
192
80
25-55
3/4
1.
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
2.
Rated in accordance with ARI 270 standard.
3.
See Table 15.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING
MIN.
MAX.
208/230-3-60
187
252
460-3-60
432
504
575-3-60
540
630
Summary of Contents for PREDATOR MagnaDRY DR090
Page 11: ...246721 YTG C 0606 Unitary Products Group 11 FIGURE 4 DR090 120 REHEAT CONTROLS ...
Page 12: ...246721 YTG C 0606 12 Unitary Products Group FIGURE 5 DR150 REHEAT CONTROLS ...
Page 60: ...246721 YTG C 0606 60 Unitary Products Group FIGURE 41 DR090 AND 120 REHEAT WIRING DIAGRAM ...
Page 61: ...246721 YTG C 0606 Unitary Products Group 61 FIGURE 42 DR150 REHEAT WIRING DIAGRAM ...