SECTION VIII: TYPICAL WIRING DIAGRAMS
FIGURE 10:
Connection Wiring Diagram
2 STAGE AC UNIT WITH OR WITHOUT
ELECTRIC HEAT - 460-3-60
CONNECTION WIRING DIAGRAM
HI PRESSURE
LOSS
OF
CHARGE
THERMOSTAT
BLK
YEL
BLU
BLU
USE COPPER
CONDUCTORS
ONLY
POWER SUPPLY
460-3-60
CRANKCASE
HEATER
TEMPERATURE
SWITCH
YEL/BLU (15)
BLU
BLU
BLU
YEL (14)
WHT/BLK (20)
YEL (13)
RED (25)
RED (25)
GRN (19)
GRN (19)
YEL/BLK (22)
YEL/BLK (23)
YEL/BLK (24)
PUR/WHT (6)
PUR/WHT (6)
RED/WHT (32)
RED/WHT (32)
BLU/WHT (7)
BLU/WHT (7)
PUR (3)
GRN (5)
GRN (28)
BLU (27)
BLU (16)
WHT (29)
WHT (29)
BLU (30)
WHT (21)
GRY (18)
BLU (17)
WHT/BLK (20)
PUR (4)
RED (31)
BLK (2)
BLK (1)
BLK
BLK
BLK
BLK (33)
BLK/WHT (34)
RED (12)
BRN/WHT (9)
BLK/WHT (10)
RED (11)
GRN (8)
CAPACITOR
CONTACTOR
BLU
24V COMMON
RELAY / SEQUENCER
FIRST STAGE
RELAY / SEQUENCER
SECOND STAGE
460V
24V SEC
75VA
COM
XFMR
COMPR.
3
ID BLWR
MOTOR
1
6 5 4
3 2 1
F
C
OD FAN
MOTOR
1
1
2
3
4
5
6
BLK
BRN
GRN
RED
2 STAGE
BLOWER
CONTROL
MODEL ID
PLUG
C
HUM
O
W1
W2
Y1
Y/Y2
G
R
PWM COM
PWM ENABLE
PWM
HT1
HT2
HT COM
C
24 VAC
R
C
G
HUM
Y1
Y2
W2
W1
6
5
4
3
2
1
P1
P3
3A
FUSE
T1
L1
T2
L2
T3
L3
L1
L3
L2
Blower Control Fault Codes
LAMP OFF
LAMP ON
SLOW RED
RAPID RED
7 RED
8 RED
9 RED
No Power to control
Internal control failure
Control normal operation
Test Mode
Call for heat and cool at the same time
Model ID plug not inserted
Internal fault self corrected, attempting
normal operation.
Flashes Fault Condition
Notes:
FIELD INSTALLED CONTROL
FIELD INSTALLED POWER
24V LOW VOLTAGE
460V LINE VOLTAGE
NOTICE
THIS UNIT IS WIRED
FOR THREE-PHASE POWER.
DO NOT CONNECT TO
A SINGLE PHASE SUPPLY
OPEN ALL DISCONNECTS
BEFORE SERVICING THIS UNIT.
CAUTION
!
5309205-UWD-A-1216
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING
CITY, LOCAL, AND/OR NATIONAL CODES IN EFFECT AT
THE TIME OF UNIT INSTALLATION.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION
WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION. IF ANY OF THE WIRING
AS SUPPLIED WITH UNIT MUST BE REMOVED, IT MUST BE REPLACED
WITH TYPE 105 C 600 VOLT WIRE OR EQUIVALENT AND CLEARLY
RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION
AFTER SERVICING.
3. FACTORY WIRED FOR 460 VOLT THREE PHASE SUPPLY POWER.
4. MOTORS ARE INHERENTLY PROTECTED.
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT
BREAKER SIZE AND MINIMUM CIRCUIT AMPACITY.