5300477-UIM-A-0317
Johnson Controls Unitary Products
7
Table 5:
Electrical Data - 460-3-60 - Single Source Power
Model
Compressor
OD
Fan
Motor
Blower
Motor
Electric Heat Option
MCA
1
(Total
Unit)
Max
Fuse
2
or
Breaker
3
Size
(Total
Unit)
MCA1
(Unit
Minus
Heater)
Max
Fuse
2
or
Breaker
3
Size
(Unit
Minus
Heater)
MCA
1
(Heater
Only)
Max
Fuse
2
or
Breaker
3
Size
(Heater
Only)
RLA LRA MCC
FLA
FLA
Heater Kit
4
Heater
kW
Stages
Heater
Amps
PCE6B36
5.7
38.0
8.9
0.87
1.9
none
--
--
--
9.9
15
9.9
15
--
--
6HK06501046
8.8
1
11
13.4
15
9.9
15
13.8
15
6HK06501546
13.2
1
16.6
18.9
20
9.9
15
20.7
25
PCE6B48
6.4
41.0
10.0
0.87
3.3
none
--
--
--
12.2
15
12.2
15
--
--
6HK06501046
8.8
1
11
15.2
20
12.2
15
13.8
15
6HK06501546
13.2
1
16.6
20.7
25
12.2
15
20.7
25
6HK06501846
15.9
1
20
24.1
25
12.2
15
24.9
25
6HK06502046
17.6
1
22.1
26.2
30
12.2
15
27.6
30
PCE6B60
7.6
52.0
11.9
0.87
3.3
none
--
--
--
13.7
20
13.7
20
--
--
6HK06501046
8.8
1
11
15
20
13.7
20
13.8
15
6HK06501546
13.2
1
16.6
20.5
25
13.7
20
20.7
25
6HK06501846
15.9
1
20
23.9
25
13.7
20
24.9
25
6HK06502046
17.6
1
22.1
26
30
13.7
20
27.6
30
6HK06502546
22
1
27.6
31.5
35
13.7
20
34.5
35
NOTES:
Single-source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field-installed single-point power modification.
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.
4. Single Point Connection Kit required.
Table 6:
Electrical Data for 460-3-60 Multi Source Power
Model
Compressor
OD
Fan
Motor
Blower
Motor
Electric Heat Option
MCA
1
Amps
Max Fuse
2
or
Breaker
3
Size
MCA
1
Amps
Max Fuse
2
or
Breaker
3
Size
RLA
LRA MCC
FLA
FLA
Heater Kit
Heater kW Stages Heater Amps
Circuit #1
Unit Minus Heaters
Circuit #2
Heaters
PCE6A36
5.7
38.0
8.9
0.87
1.9
none
--
--
--
9.9
15
--
--
6HK06501046
8.8
1
11.0
9.9
15
13.8
15
6HK06501546
13.2
1
16.6
9.9
15
20.7
25
PCE6B48
6.4
41.0 10.0
0.87
3.3
none
--
--
--
12.2
15
--
--
6HK06501046
8.8
1
11.0
12.2
15
13.8
15
6HK06501546
13.2
1
16.6
12.2
15
20.7
25
6HK06501846
15.9
1
20.0
12.2
15
24.9
25
6HK06502046
17.6
1
22.1
12.2
15
27.6
30
PCE6B60
7.6
52.0 11.9
0.87
3.3
none
--
--
--
13.7
20
--
--
6HK06501046
8.8
1
11.0
13.7
20
13.8
15
6HK06501546
13.2
1
16.6
13.7
20
20.7
25
6HK06501846
15.9
1
20.0
13.7
20
24.9
25
6HK06502046
17.6
1
22.1
13.7
20
27.6
30
6HK06502546
22.0
1
27.6
13.7
20
34.5
35
NOTES:
1. MCA = Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.
Table 7:
Electric Heat Blower Off Delay
Model ID
Blower Off Delay In Seconds
PCE6B36
60
PCE6B48
110
PCE6B60
110