6 - Condensate Drainage

7 - Refrigerant Piping Connections

Prefabricated refrigerant piping is available as an accessory.
If this is not used, piping and insulating materials employed
must be compatible with this type of installation.
Indoor unit gas and liquid line connectors are mounted on
annealed copper tubing stubs and may be shaped to suit the
connection arrangements of your choice. Use the knock-outs
provide in the unit casing. Do not bend stubs to tight angles.
The pre-charged outdoor unit does not require charging if
piping length is 5m or less. However, the interconnecting
piping and the indoor unit must be pumped down before

releasing R22 refrigerant into them from the outdoor unit.

1 -  Remove the cap from the service valve.

2 -  Connect the line to a vacuum pump and pump down
      to  5 Pa.
3 -  When pump down is finisned, wait 15 minutes to detect
      potential circuit leakage. Open service valves on the
      outdoor unit.

* Note

 : The expansion device is located in the outdoor unit.

6

Table 2 - Maximum piping lengths

Note :

  Where the difference in elevation is greater than 5 metres,

            install an oil trap every 5 metres.

Unit size

D(m)

L(m)

H(m)

Drain tube on unit is flexible and can be routed to
suit various piping arrangements. The drainage
line must include an elbow trap (U bend). Connect
a plastic condensate pipe with an outside diameter

of 16 mm.

Verification of condensate water drainage :

Fill the drain pan and observe evacuation.

If piping length exceeds 5 metres, add 10g of refrigerant
R22 per extra metre.

35

20

25

22

45

24

30

26

55

24

30

26

Summary of Contents for MOH 55

Page 1: ...MOC MOH MCC MCH MINISPLIT Floor Ceiling 035T70004 001 TECHNICAL GUIDE Cooling only and Heat Pump Systems Models MCC MOC MCH MOH 35 to 55 Infrared remote control...

Page 2: ...e that the power supply has been disconnected ELECTRICAL CONNECTIONS All electrical wiring and connections must comply with local standards Power supply cord used must not be lighter than Polychloropr...

Page 3: ...C MOH Piping Diameter Dimensions and Weights Indoor Outdoor Indoor unit Outdoor unit V Ph Hz Ph kW A A A m h Connection Type V Ph Hz Ph kW A A A m h Type gr Suction Liquid H mm W mm D mm kg 220 240 1...

Page 4: ...nections unit wiring connections 5 1 Unit clearances A minimium of clearance is necessary around the units to ensure proper air circulation and easy access for maintenance Clearance required for indoo...

Page 5: ...ling mounted units installation close to a wall facilitates piping Usetheknockoutsintheunitcasingwhenroutingthepipes Hook the indoor unit on the mounting brackets Check that the unit is level so that...

Page 6: ...into them from the outdoor unit 1 Remove the cap from the service valve 2 Connect the line to a vacuum pump and pump down to 5 Pa 3 When pump down is finisned wait 15 minutes to detect potential circ...

Page 7: ...d the temperature set point entered on the control SYSTEM OPERATION MODE SELECTION ROOM TEMPERATURE SETTING Press the TEMP button up or down to change the setting to the desired room temperature The s...

Page 8: ...d working condition Also make sure that the controlispointeddirectlyattheairconditioningunitwhenyouareusing it that the distance is a maximum of 10 meters and that there are no obstacles between the r...

Page 9: ...it Outdoor unit Outdoor unit 9 10 Service and Maintenance The units are designed to operate for long periods of time with a minimum of maintenance However the following operations must be performed re...

Page 10: ...ty correction factor for temperature Capacity correction factor for indoor fan speed C3 Fan speed Correction factor C3 Indoor unit High 1 Medium 0 90 Low 0 75 Indoor unit 10 0 98 5 1 00 Piping length...

Page 11: ...35 MSC 35 to 55 MSH 35 to 55 MKC 12 to 55 MKH 12 to 55 MAC 18 to 65 MAH 18 to 65 IS IN COMPLIANCE WITH REQUIREMENTS OF MACHINERY DIRECTIVE CEE 89 392 AS MODIFIED WITH DIRECTIVES CEE 91 368 93 44 93 6...

Page 12: ...tem of the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under No circums...

Reviews: