background image

TE - MC9907 - 007

DE - COMMISSIONING DISMANTLING & DISPOSAL

This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!

All work must only be carried out by competent persons using suitable protective clothing and safety precautions.

                                Read the Manual                   Risk of electric shock                      Unit is remotely controlled and

                                                                                may start without warning

  1.

  Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas

       isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
       to unit installation instructions.
 

 2

.  Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be

       re-used, if appropriate, or returned to the manufacturer for disposal.

 Under No circumstances should refrigerant be vented to atmosphere.

 Where

       appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing
       disposal of oily wastes.
  

3.

  Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted

       from position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit
       weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
  

4.

  After removal from position the unit parts may be disposed of according to local laws and regulations.

Summary of Contents for MOH 55

Page 1: ...MOC MOH MCC MCH MINISPLIT Floor Ceiling 035T70004 001 TECHNICAL GUIDE Cooling only and Heat Pump Systems Models MCC MOC MCH MOH 35 to 55 Infrared remote control...

Page 2: ...e that the power supply has been disconnected ELECTRICAL CONNECTIONS All electrical wiring and connections must comply with local standards Power supply cord used must not be lighter than Polychloropr...

Page 3: ...C MOH Piping Diameter Dimensions and Weights Indoor Outdoor Indoor unit Outdoor unit V Ph Hz Ph kW A A A m h Connection Type V Ph Hz Ph kW A A A m h Type gr Suction Liquid H mm W mm D mm kg 220 240 1...

Page 4: ...nections unit wiring connections 5 1 Unit clearances A minimium of clearance is necessary around the units to ensure proper air circulation and easy access for maintenance Clearance required for indoo...

Page 5: ...ling mounted units installation close to a wall facilitates piping Usetheknockoutsintheunitcasingwhenroutingthepipes Hook the indoor unit on the mounting brackets Check that the unit is level so that...

Page 6: ...into them from the outdoor unit 1 Remove the cap from the service valve 2 Connect the line to a vacuum pump and pump down to 5 Pa 3 When pump down is finisned wait 15 minutes to detect potential circ...

Page 7: ...d the temperature set point entered on the control SYSTEM OPERATION MODE SELECTION ROOM TEMPERATURE SETTING Press the TEMP button up or down to change the setting to the desired room temperature The s...

Page 8: ...d working condition Also make sure that the controlispointeddirectlyattheairconditioningunitwhenyouareusing it that the distance is a maximum of 10 meters and that there are no obstacles between the r...

Page 9: ...it Outdoor unit Outdoor unit 9 10 Service and Maintenance The units are designed to operate for long periods of time with a minimum of maintenance However the following operations must be performed re...

Page 10: ...ty correction factor for temperature Capacity correction factor for indoor fan speed C3 Fan speed Correction factor C3 Indoor unit High 1 Medium 0 90 Low 0 75 Indoor unit 10 0 98 5 1 00 Piping length...

Page 11: ...35 MSC 35 to 55 MSH 35 to 55 MKC 12 to 55 MKH 12 to 55 MAC 18 to 65 MAH 18 to 65 IS IN COMPLIANCE WITH REQUIREMENTS OF MACHINERY DIRECTIVE CEE 89 392 AS MODIFIED WITH DIRECTIVES CEE 91 368 93 44 93 6...

Page 12: ...tem of the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under No circums...

Reviews: