YORK INTERNATIONAL

Condenser fan stage for the system.

Standard control:

Stage 1 = one fan forward
Stage 2 = two fans forward
Stage 3 = N/A

Low Ambient (optional)

Stage 1 = one fan reverse
stage 2 = one fan forward
stage 3 = two fans forward

See unit manual for details.

History Data
The HISTORY key gives the user access to many unit
and system operating parameters at the time of a unit
of system safety shutdown.  When the HISTORY key
is pressed the following screen is displayed.

The user can use the arrow keys to choose a number
from 1 to 6 and ENTER to view any of the 6 history
buffers.  Buffer number 1 is the most recent and buffer
number 6 is the oldest safety shutdown saved.  The UP
and DOWN arrows can be used to scroll forwards and
backwards through the history buffers to view unit data,
unit status, and setpoints at the time of shutdown.

Data Printing
The PRINT key is used to initiate either an operating
data print or a history print if the optional printer
is attached to the RS-232 port in the RCC. When the
print key is pressed, the following message will
appear.

When the OPER DATA key is pressed after the PRINT
key, an operating data printout is initiated and the fol-
lowing message will be displayed for a few
seconds.

When the HISTORY key is pressed after the PRINT
key, a history printout is initiated and the following
message will be displayed for a few seconds.

If the PRINT key is pressed while a print is currently
being performed, the following message is displayed
for a few seconds and then unit status is displayed.

Sample Printout:

D I S P L A Y

S A F E T Y

S H U T -

D O W N

N O .

X

( 1

T O

6 )

P R E S S

O P E R

D A T A

O R

H I S T O R Y

K E Y

T O

P R I N T

P R I N T I N G

O P E R A T I N G

D A T A

P R I N T E R

C U R R E N T L Y

A C T I V E

YORK INTERNATIONAL CORPORATION
  MILLENNIUM LIQUID CHILLER

     UNIT STATUS
    2:04PM 18 JUN 98

SYS 1      NO COOLING LOAD
SYS 2   COMPRESSORS RUNNING 2

OPTIONS

CHILLED LIQUID       WATER
AMBIENT CONTROL     STANDARD
LOCAL/REMOTE MODE     REMOTE
CONTROL MODE   LEAVING LIQUID
LEAD/LAG CONTROL    AUTOMATIC
FAN CONTROL   AMB & DSCH PRESS

UNIT DATA

RETURN LIQUID TEMP   58.2 DEGF
LEAVING LIQUID TEMP  53.0 DEGF
COOLING RANGE 42.0 +/- 2.0 DEGF
AMBIENT AIR TEMP    74.8 DEGF
LEAD SYSTEM        SYS 2
EVAPORATOR PUMP        ON
EVAPORATOR HEATER      OFF
UNIT SOFTWARE VER  C.MMC.01.00
RCC SOFTWARE VER   C.MMC.02.00

SYSTEM 1 DATA

COMPRESSORS STATUS      OFF
RUN TIME   0- 0- 0- 0 D-H-M-S
SUCTION PRESSURE     66 PSIG
DISCHARGE PRESSURE   219 PSIG
LIQUID LINE SOLENOID     OFF
HOT GAS BYPASS VALVE     OFF
CONDENSER FAN STAGES     OFF

SYSTEM 2 DATA

COMPRESSORS STATUS       2
RUN TIME   0- 0- 1-46 D-H-M-S
SUCTION PRESSURE     51 PSIG
DISCHARGE PRESSURE   157 PSIG
LIQUID LINE SOLENOID     ON
CONDENSER FAN STAGES      3

DAILY SCHEDULE

S M T W T F S  *=HOLIDAY
MON START=00:00AM  STOP=00:00AM
TUE START=00:00AM  STOP=00:00AM
WED START=00:00AM  STOP=00:00AM
THU START=00:00AM  STOP=00:00AM
FRI START=00:00AM  STOP=00:00AM
SAT START=00:00AM  STOP=00:00AM
HOL START=00:00AM  STOP=00:00AM

S Y S

X

F A N

S T A G E

X X X

P R I N T I N G

H I S T O R Y

D A T A

Unit Data

Summary of Contents for MILLENNIUM

Page 1: ...MILLENNIUM REMOTE CONTROL CENTER OPERATORS GUIDE 29535A OPERATING INSTRUCTIONS Millennium REMOTE CONTROL CENTER YCAL CHILLERS AND YCUL CONDENSING UNITS New Release Form 150 62 NM3 100 ...

Page 2: ...rd 3 40 Character Display 3 Keypad 3 Status 3 Display Print 3 Entry 3 Setpoints 3 Unit 3 Communications 3 Section 2 Status Messages 4 General Status Messages 4 Fault Status Messages 5 Unit Faults 5 System Faults 6 Section 3 Unit Data 7 Operating Data Displays 7 History Data 8 Data Printing 8 Optional Printer Installation 9 Parts 9 Assembly and Wiring 9 Section 4 Programmable Values 10 Cooling Setp...

Page 3: ... viewing in direct sunlight Keypad An operator keypad allows complete control of the unit from a remote location The keypad offers commands available to access displays program setpoints and ini tiate unit run commands There are 5 divisions to the keypad They are outlined below Status This section consists of the STATUS key and the 40 character display The STATUS key will be used to display the cu...

Page 4: ...con tact is open in series with the flow switch STATUS MESSAGES U N I T S W I T C H O F F S H U T D O W N D A I L Y S C H E D U L E S H U T D O W N R E M O T E C O N T R O L L E D S H U T D O W N F L O W S W I T C H R E M S T O P N O R U N P E R M SYS SWITCH OFF tells that the system switch on the microboard is turned off The system will not be al lowed to run until the switch is turned back on Th...

Page 5: ...he setpoint schedule or load limiting when the chiller is in local control mode Fault Status Messages A number of possible fault messages may appear when the STATUS key is pressed Whenever a fault message appears the safety thresholds on the unit have been exceeded and the entire unit or a single system will be shut down and in some cases locked out Unit Faults The Low Ambient Temp Cutout is a saf...

Page 6: ...ould result in system damage When the 115VAC to the micropanel drops below a specific level a unit fault is initiated to safely shut down the unit Restart is allowed after the unit is fully powered again and the anti recycle timers have finished counting down The Low Battery Warning can only occur at unit power up When the chiller micropanel is suppled power the RTC battery is checked on the chill...

Page 7: ...s sors and will only display such Unit load and unload timers Refer to unit manual for detailed loading and unloading scheme The cooling demand indicates the step of capacity control the chiller control panel is controlling at See the chiller manual for details On two system units this message indicates which sys tem is the lead Chiller evaporator pump contacts and evaporator heater status The num...

Page 8: ... pressed while a print is currently being performed the following message is displayed for a few seconds and then unit status is displayed Sample Printout D I S P L A Y S A F E T Y S H U T D O W N N O X 1 T O 6 P R E S S O P E R D A T A O R H I S T O R Y K E Y T O P R I N T P R I N T I N G O P E R A T I N G D A T A P R I N T E R C U R R E N T L Y A C T I V E YORK INTERNATIONAL CORPORATION MILLENNI...

Page 9: ...d spe cifically for YORK is P N 950915576 The cable to connect the printer can either be locally assembled from FIG 1 PRINTER TO MICROBOARD ELECTRICAL CONNECTIONS LD02722 the parts listed or ordered directly from WEIGH TRONIX under part number 287 040018 PARTS The following parts are required 1 WEIGH TRONIX model 1220 printer 2 2 25 5 7cm wide desk top calculator paper 3 25 ft 7 62m maximum length...

Page 10: ...T I O N S Following are the messages for the programming of the setpoint and range for leaving and return chilled liquid control respectively These are for chillers only Following are the messages for the programming of the setpoint and range for discharge air temp and suction pressure control respectively These are for condens ing units only S E T P O I N T X X X X F R A N G E X X F S E T P O I N...

Page 11: ...pace next to the S is the cursor and will move to the next empty space when the ENTER ADV key is pressed To set the Holiday the cursor is moved to the space following the day of the week of the holiday and the UP arrow key is pressed An will appear in the space signifying that day as a holiday The can be removed by pressing the DOWN arrow key The Holiday schedule must be programmed weekly once the...

Page 12: ...12 YORK INTERNATIONAL LD05175 FIELD WIRING FIG 2 FIELD WIRING Field Wiring ...

Page 13: ...13 YORK INTERNATIONAL FORM 150 62 NM3 LD05175 FIELD WIRING FIG 3 FIELD WIRING 5 ...

Page 14: ...14 YORK INTERNATIONAL This page intentionally left blank ...

Page 15: ...15 YORK INTERNATIONAL FORM 150 62 NM3 This page intentionally left blank ...

Page 16: ...ic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 2000 ALL RIGHTS RESERVED Form 150 62 NM3 100 New Release 717 771 7890 www york com ...

Reviews: