background image

11

YORK INTERNATIONAL

FORM 150.62-NM3

Daily Schedule / Holiday
The Daily Schedule can be programmed to control the
start and stop time of the chiller. To set the schedule,
proceed as follows: press the SET SCHEDULE / HOLI-
DAY key. The display will show the following mes-
sage:

The line under the 0 is the cursor. If the start time is
wrong, it may changed by using the UP and DOWN
arrow keys. Once the correct hour is shown, press the
ENTER key. The cursor will then move to the minute
selection. Once the correct minute is shown, press the
ENTER key. The cursor will then move to the AM/PM
selection. This value may be chosen by the UP and
DOWN arrow keys and entered by pressing ENTER.
This process may be followed until the hour, minutes,
and meridian of both the START and STOP points are
set. Once a schedule is entered, the schedule for the
next day will appear. The start and stop time of each
day may beprogrammed differently. If you want to view
the schedule without making a change, simply press
the SET SCHEDULE / HOLIDAY key until the day
you wish to view appears.

If the time is ever changed for Mon-
day, all the other days will change to
the new Monday schedule. This means
if the Monday times are not applicable
for the whole week then the excep-
tional days would need to be repro-
grammed to the desired schedule.

After SUN (Sunday) schedule appears on the display a
subsequent press of the SET SCHEDULE / HOLIDAY
key will display the Holiday schedule. This is a two
part display. The first reads:

The times may be set using the same procedure as de-
scribed above for the days of the week. Pressing the
SET SCHEDULE / HOLIDAY key a second time, the
display will read:

The line below the empty space next to the S is the
cursor and will move to the next empty space when the
ENTER/ADV key is pressed. To set the Holiday, the
cursor is moved to the space following the day of the

week of the holiday and the UP arrow key is pressed.
An * will appear in the space signifying that day as a
holiday. The * can be removed by pressing the DOWN
arrow key.

The Holiday schedule must be programmed weekly –
once the holiday schedule runs, it will revert to the nor-
mal daily schedule.

Load Limiting
The LOAD LIMIT key is used to load limit the unit.
This function modifies Load Limit setpoint found on
the unit. The message displayed when the LOAD LIMIT
key is pressed follows.

Load Limiting can be programmed from 0 to 2 using
the arrow keys. The unit will operate on either this load
limit setpoint or its local value, whichever is lower.

Load Limit 0 = no load limit
Load Limit 1 = 50% load limit - 2/4  compressor units.
Load Limit 1 = 66% load limit - 3/6 compressor units.
Load Limit 2 = 33 % - 3/6 compressor units only.

Refer to chiller unit manual for a detailed explanation
on Load Limiting.

Remote Unit Run

• ON Key

When the ON key is pressed, the unit will be given a
remote run permissive from the RCC. Assuming all
other run permissives are met, the unit will be allowed
to run. The following message will be displayed for a
few seconds after the ON key is pressed. The chiller
must be programmed for Remote mode to use this func-
tion.

When the OFF key is pressed, the unit remote run per-
missive from the RCC will be turned off. The unit will
not be allowed to run in this state. The following mes-
sage will be displayed for a few seconds after the OFF
key is pressed.

M O N

S T A R T

=

0 6 : 0 0

A M

S T O P

=

1 0 : 0 0

P M

H O L

S T A R T

=

0 6 : 0 0

A M

S T O P

=

1 0 : 0 0

P M

S_

M

T

W

T

F

S

H O L I D A Y

N O T E D

B Y

*

L O A D

L I M I T

S T A G E

X

R E M O T E

U N I T

R U N

I S

O N

R E M O T E

U N I T

R U N

I S

O F F

4

Summary of Contents for MILLENNIUM

Page 1: ...MILLENNIUM REMOTE CONTROL CENTER OPERATORS GUIDE 29535A OPERATING INSTRUCTIONS Millennium REMOTE CONTROL CENTER YCAL CHILLERS AND YCUL CONDENSING UNITS New Release Form 150 62 NM3 100 ...

Page 2: ...rd 3 40 Character Display 3 Keypad 3 Status 3 Display Print 3 Entry 3 Setpoints 3 Unit 3 Communications 3 Section 2 Status Messages 4 General Status Messages 4 Fault Status Messages 5 Unit Faults 5 System Faults 6 Section 3 Unit Data 7 Operating Data Displays 7 History Data 8 Data Printing 8 Optional Printer Installation 9 Parts 9 Assembly and Wiring 9 Section 4 Programmable Values 10 Cooling Setp...

Page 3: ... viewing in direct sunlight Keypad An operator keypad allows complete control of the unit from a remote location The keypad offers commands available to access displays program setpoints and ini tiate unit run commands There are 5 divisions to the keypad They are outlined below Status This section consists of the STATUS key and the 40 character display The STATUS key will be used to display the cu...

Page 4: ...con tact is open in series with the flow switch STATUS MESSAGES U N I T S W I T C H O F F S H U T D O W N D A I L Y S C H E D U L E S H U T D O W N R E M O T E C O N T R O L L E D S H U T D O W N F L O W S W I T C H R E M S T O P N O R U N P E R M SYS SWITCH OFF tells that the system switch on the microboard is turned off The system will not be al lowed to run until the switch is turned back on Th...

Page 5: ...he setpoint schedule or load limiting when the chiller is in local control mode Fault Status Messages A number of possible fault messages may appear when the STATUS key is pressed Whenever a fault message appears the safety thresholds on the unit have been exceeded and the entire unit or a single system will be shut down and in some cases locked out Unit Faults The Low Ambient Temp Cutout is a saf...

Page 6: ...ould result in system damage When the 115VAC to the micropanel drops below a specific level a unit fault is initiated to safely shut down the unit Restart is allowed after the unit is fully powered again and the anti recycle timers have finished counting down The Low Battery Warning can only occur at unit power up When the chiller micropanel is suppled power the RTC battery is checked on the chill...

Page 7: ...s sors and will only display such Unit load and unload timers Refer to unit manual for detailed loading and unloading scheme The cooling demand indicates the step of capacity control the chiller control panel is controlling at See the chiller manual for details On two system units this message indicates which sys tem is the lead Chiller evaporator pump contacts and evaporator heater status The num...

Page 8: ... pressed while a print is currently being performed the following message is displayed for a few seconds and then unit status is displayed Sample Printout D I S P L A Y S A F E T Y S H U T D O W N N O X 1 T O 6 P R E S S O P E R D A T A O R H I S T O R Y K E Y T O P R I N T P R I N T I N G O P E R A T I N G D A T A P R I N T E R C U R R E N T L Y A C T I V E YORK INTERNATIONAL CORPORATION MILLENNI...

Page 9: ...d spe cifically for YORK is P N 950915576 The cable to connect the printer can either be locally assembled from FIG 1 PRINTER TO MICROBOARD ELECTRICAL CONNECTIONS LD02722 the parts listed or ordered directly from WEIGH TRONIX under part number 287 040018 PARTS The following parts are required 1 WEIGH TRONIX model 1220 printer 2 2 25 5 7cm wide desk top calculator paper 3 25 ft 7 62m maximum length...

Page 10: ...T I O N S Following are the messages for the programming of the setpoint and range for leaving and return chilled liquid control respectively These are for chillers only Following are the messages for the programming of the setpoint and range for discharge air temp and suction pressure control respectively These are for condens ing units only S E T P O I N T X X X X F R A N G E X X F S E T P O I N...

Page 11: ...pace next to the S is the cursor and will move to the next empty space when the ENTER ADV key is pressed To set the Holiday the cursor is moved to the space following the day of the week of the holiday and the UP arrow key is pressed An will appear in the space signifying that day as a holiday The can be removed by pressing the DOWN arrow key The Holiday schedule must be programmed weekly once the...

Page 12: ...12 YORK INTERNATIONAL LD05175 FIELD WIRING FIG 2 FIELD WIRING Field Wiring ...

Page 13: ...13 YORK INTERNATIONAL FORM 150 62 NM3 LD05175 FIELD WIRING FIG 3 FIELD WIRING 5 ...

Page 14: ...14 YORK INTERNATIONAL This page intentionally left blank ...

Page 15: ...15 YORK INTERNATIONAL FORM 150 62 NM3 This page intentionally left blank ...

Page 16: ...ic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 2000 ALL RIGHTS RESERVED Form 150 62 NM3 100 New Release 717 771 7890 www york com ...

Reviews: