background image

YORK INTERNATIONAL

15

FORM 160.52-N1

NOTE: Units shipped dismantled MUST be

re-assembled by, or under the super-
vision of, a YORK representative.
(See Form 160.52-N6)

Form 7 – Split Shells – Shipped as four major assem-

blies. Unit first factory assembled, refriger-
ant piped, wired and leak tested; then dis-
mantled for shipment. Compressor/motor
assembly removed from shells and skidded.

Cooler and condenser shells are separated
at tube sheets and are not skidded. Refriger-
ant lines between shells are flanged and
capped, requiring no welding.

All wiring integral with compressor is left on
it.  All wiring harnesses on shells are removed.
All openings on compressor and shells are
closed and charged with dry nitrogen (2 to 3
PSIG).

Miscellaneous packaging of control center,
tubing, water temperature controls, wiring, oil
isolators, solid state starter (option), etc.; re-
frigerant charge shipped separately.

NOTE: Units shipped dismantled MUST be

re-assembled by, or under the super-
vision of, a YORK representative.
(See Form 160.52-N6)

When more than one chiller is involved, the major parts
of each unit will be marked to prevent mixing of assem-
blies. (Piping and Wiring Drawings to be furnished by
YORK.)

INSPECTION – DAMAGE – SHORTAGE

The unit shipment should be checked on arrival to see
that all major pieces, boxes and crates are received.
Each unit should be checked on the trailer or rail car
when received, before unloading, for any visible signs
of damage. Any damage or signs of possible damage
must be reported to the transportation company imme-
diately for their inspection.

YORK WILL NOT BE RESPONSIBLE FOR ANY
DAMAGE IN SHIPMENT OR AT JOB SITE OR LOSS
OF PARTS. (Refer to Shipping Damage Claims, Form
50.15-NM)

When received at the job site all containers should be
opened and contents checked against the packing list.

Any material shortage should be reported to YORK im-
mediately. (Refer to Shipping Damage Claims, Form
50.15-NM)

CHILLER DATA PLATE

A unit data plate is mounted on the control center as-
sembly of each unit, giving unit model number; design
working pressure; water passes; refrigerant charge; se-
rial numbers; and motor power characteristics and con-
nection diagrams.

Additional information may be found on the motor data
plate. This information should be included when con-
tacting the factory on any problem relating to the motor.

RIGGING

The complete standard chiller is shipped without skids.
(When optional skids are used it may be necessary to
remove the skids so riggers skates can be used under
the unit end sheets to reduce overall height.)

Each unit has four (4) lifting holes (two in each end) in
the end sheets which should be used to lift the unit.
(See Fig. 4)

Care should be taken at all times during rigging and
handling of the chiller to avoid damage to the unit and
its external connections. Lift only using holes shown
in Fig. 4.

Do not lift the unit with slings around motor/com-
pressor assembly or by means of eyebolts in the
tapped holes of the compressor motor assembly.
Do not turn a unit on its side for rigging. Do not rig
vertically.

Use of Slings (See Fig. 4 for proper use of slings in
rigging.)

CAUTION: If necessary to rig the chiller by one end to

permit lifting or dropping through a vertical
passageway, such as an elevator shaft, con-
tact YORK factory shipping for special rig-
ging instructions.

The rigging and operating weights and overall dimen-
sions are given on pages 5 thru 12 as a guide in deter-
mining the clearances required for rigging. (Add 6" to
overall height for optional skidded unit.)

Summary of Contents for Millenium YK D Series

Page 1: ... DRIVE WARNING SYSTEM CONTAINS REFRIGERANT UNDER PRESSURE SERIOUS INJURY COULD RESULT IF PROPER PROCEDURES ARE NOT FOLLOWED WHEN SERVICING SYSTEM ALL SERVICE WORK SHALL BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN IN ACCOR DANCE WITH YORK INSTALLATION OPERATION MANUAL INSTALLATION INSTRUCTIONS MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS Supersedes See Back Form 160 52 N1 1098 28815A ...

Page 2: ...C ED FB FC FD EB EB EC ED FB FC FD H1 H5 FB FC FD EB EC ED FB FC FD GB GC GD CN CY 5CK 5DD GC GD FB FC FD GB GC GD FB FC FA FB FC FD GB GC GD H2 H6 GB GC GD FA FB FC FD GB GC GD CN CZ 5CK 5DD HB HC GB GC GD H3 H8 GB GC GD FB FC FD GB GC GD CN CZ H8 5CK 5CU H8 HB HC GB GC GD CN CB H3 5CK 5CX H3 GF GH GB GC GD HB HC HD J1 HF HH GB GC GD HB HC HD JB JC JD CW DH 5CS 5DH J2 JF JG JH HB HC HD JB JC JD T...

Page 3: ...arings on New Balance Q5800 Motors 16 Foundation 17 Clearance 17 Isolators 22 INSTALLATION 22 Rigging Unit to Final Location 22 Locating and Installing Isolator Pads 22 Checking the Isolation Pad Deflection 22 Leveling the Unit 22 Installing Optional Spring Isolators 22 Piping Connections 22 Cooler and Condenser Water Piping 22 Refrigerant Relief Piping 24 Unit Piping 24 Control Wiring 25 Power Wi...

Page 4: ...4 YORK INTERNATIONAL FIG 1 MODEL YK MILLENNIUM CHILLER 28815A CONTROL CENTER COMPRESSOR COOLER CONDENSER MOTOR FRONT VIEW OIL PUMP CONTROL PANEL ...

Page 5: ... 1 4 8 10 1 4 C 2 1 1 4 2 1 1 4 2 3 D 1 7 1 9 1 9 E 0 6 1 4 0 6 1 4 0 6 1 4 H1 COMPRESSORS COOLER CONDENSER SHELL CODES E E E F F E F F F G G F G G A 6 6 6 9 6 11 7 2 7 6 7 4 1 2 7 8 1 2 B 8 1 8 3 1 2 8 1 8 3 1 2 8 7 1 2 8 3 1 2 8 7 1 2 C 1 9 1 2 1 9 1 2 2 0 2 0 2 0 2 1 1 4 2 1 1 4 D 1 5 1 2 1 7 1 5 1 2 1 7 1 9 1 7 1 9 E 0 5 7 8 0 5 7 8 0 5 7 8 0 5 7 8 0 5 7 8 0 6 1 4 0 6 1 4 H0 COMPRESSORS COOLER...

Page 6: ...COOLER CONDENSER SHELL CODES D D D E E D E E E F F E F F A 1930 1930 1981 1981 2057 2108 2184 B 2451 2464 2451 2464 2527 2462 2527 C 521 521 546 546 546 610 610 D 445 445 445 445 483 445 483 E 143 143 149 149 149 149 149 H1 COMPRESSORS COOLER CONDENSER SHELL CODES E E E F F E F F F G G F G G A 1981 2057 2108 2184 2286 2248 2350 B 2464 2527 2462 2527 2324 2527 2324 C 546 546 610 610 610 641 641 D 4...

Page 7: ...1 3 4 1 11 3 4 1 11 3 4 1 11 3 4 1 11 3 4 1 11 3 4 1 11 3 4 G 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 J3 COMPRESSORS COOLER CONDENSER SHELL CODES H H H J J H A 8 2 1 2 8 6 1 2 8 9 B 9 8 3 4 10 0 3 4 9 8 3 4 C 2 2 1 4 2 2 1 4 2 5 1 2 D 1 11 2 1 1 11 E 14 0 14 0 14 0 F 1 11 3 4 1 11 3 4 1 11 3 4 G 1 2 3 4 1 2 3 4 1 2 3 4 J3 J4 COMPRESSORS COOLER CONDENSER SHELL CODES J J T T ...

Page 8: ...91 2991 2985 C 610 610 667 667 667 749 749 749 D 533 584 533 584 635 584 635 635 E 4267 4267 4267 4267 4267 4267 4267 4877 F 603 603 603 603 603 603 603 603 G 375 375 375 375 375 375 375 375 J3 COMPRESSORS COOLER CONDENSER SHELL CODES H H H J J H A 2502 2604 2667 B 2965 3067 2965 C 667 667 749 D 584 635 584 E 4267 4267 4267 F 603 603 603 G 375 375 375 J3 J4 COMPRESSORS COOLER CONDENSER SHELL CODES...

Page 9: ...CB 17600 8000 21000 9550 1025 470 5250 2388 DDCC 17660 8030 21000 9550 1025 470 5250 2388 D C DDCD 17800 8090 21200 9640 1025 470 5300 2410 DECB 17750 8070 21100 9590 1025 470 5275 2398 DECC 17820 8100 21200 9640 1025 470 5300 2410 DECD 17960 8160 21300 9680 1025 470 5325 2420 DBDB 17420 7920 20800 9450 1150 520 5200 2363 DBDC 17430 7920 20800 9450 1150 520 5200 2363 DBDD 17710 8050 21100 9590 115...

Page 10: ...26400 12000 1585 720 6600 3000 EDFD 21930 9970 26600 12090 1585 720 6650 3023 FCEB 21220 9650 25900 11770 1650 750 6475 2943 FCEC 21430 9740 26200 11910 1650 750 6550 2978 F E FCED 21530 9790 26300 11950 1650 750 6575 2988 FDEB 21470 9760 26200 11910 1650 750 6550 2978 FDEC 21680 9850 26400 12000 1650 750 6600 3000 FDED 21790 9900 26500 12050 1650 750 6625 3013 FBFA 21550 9800 26900 12230 1805 820...

Page 11: ...020 8925 4058 HCGC 29180 13260 36100 16410 2235 1020 9025 4103 HCGD 29450 13390 36400 16550 2235 1020 9100 4138 TABLE 1 SHELL COMPRESSOR WEIGHT LESS MOTOR G H COMPRESSORS Cont d SHIPPING OPERATING REFRIGERANT LOADING PER SHELLS WEIGHT WEIGHT CHARGE ISOLATOR LBS KG LBS KG LBS KG LBS KG GFGB 25900 11748 32050 14538 2415 1095 8013 3634 GFGC 26330 11943 32600 14787 2415 1095 8150 3697 G G GFGD 26540 1...

Page 12: ...TFTD 38010 17241 48330 21922 3995 1812 12083 5481 TGTB 37680 17092 47630 21605 3995 1812 11908 5401 TGTC 38170 17314 48570 22031 3995 1812 12143 5508 T T TGTD 38440 17436 48940 22199 3995 1812 12235 5550 THTB 38110 17287 48440 21972 3995 1812 12110 5493 THTC 38600 17509 49180 22308 3995 1812 12295 5577 THTD 38860 17627 49540 22471 3995 1812 12385 5618 TFVB 41430 18793 52410 23773 4290 1946 13103 5...

Page 13: ...CT 5CM 2635 1195 CU 5CN 2635 1195 CV 5CO 2635 1195 CW 5CP 2930 1329 CX 5CQ 2930 1329 CY 5CR 2930 1329 CZ 5CS 2930 1329 CA 5CT 5750 2608 CB 5CU 5750 2608 DA 5CV 5750 2608 DB 5CW 6800 3084 DB 5CX 6800 3084 5DA 7300 3311 5DB 7300 3311 LOW VOLTAGE MOTOR CODE WEIGHT WEIGHT 60 HZ 50 HZ LBS KGS CH 2670 1211 CJ 5CE 2670 1211 CK 5CF 3100 1406 CL 5CG 3100 1406 CM 5CH 3100 1406 CN 5CI 3100 1406 CP 5CJ 3700 1...

Page 14: ...nents 4 Do not make final power supply connections to the compressor motor or control center 5 Do not charge the compressor with oil 6 Do not charge the unit with refrigerant 7 Do not attempt to start the system 8 Do not run hot water 110 F max or steam through the cooler or condenser at any time SHIPMENT The chiller may be ordered and shipped in any of the following forms Form 1 Factory Assembled...

Page 15: ...to Shipping Damage Claims Form 50 15 NM When received at the job site all containers should be opened and contents checked against the packing list Any material shortage should be reported to YORK im mediately Refer to Shipping Damage Claims Form 50 15 NM CHILLER DATA PLATE A unit data plate is mounted on the control center as sembly of each unit giving unit model number design working pressure wa...

Page 16: ...pening prop erly located may be used The chiller should be lo cated in an indoor location where temperatures range from 40 F to 110 F 4 4 C to 43 3 C MOTORS The YK open motor is air cooled Check state local and other codes for ventilation requirements GREASED BEARINGS ON NEW RELIANCE Q5800 MOTORS Starting in the 4th Quarter of 1997 chillers were shipped with a newly designed Reliance motor in the ...

Page 17: ...hese motors The grease is readily available throughout most of the world from Texaco distributors and in Africa Australia and the Pacific Rim countries from Caltex distributors Other types of grease may be chemically and me chanically incompatible with this Texaco Premium RB grease and are not to be used Add 1 5 cubic inches of Texaco Premium RBgrease every 1800 hours of operation of the motor Do ...

Page 18: ...NAL ALL DIMENSIONS ARE IN INCHES FIG 5 NEOPRENE ISOLATORS STANDARD DIMENSIONS UNIT WEIGHT 53 531 TO 100 464 LBS LD00703 UNIT WEIGHT UP TO 28 835 LBS LD00701 UNIT WEIGHT 28 836 TO 53 530 LBS LD00702 LD00704 See Fig 2 or 3 ...

Page 19: ...2 N1 ALL DIMENSIONS ARE IN MILLIMETERS UNIT WEIGHT UP TO 13 080 Kgs LD00701 R UNIT WEIGHT 13 081 TO 24 281 Kgs LD00702 R UNIT WEIGHT 24 282 TO 45 570 Kgs LD00703 R LD00704 R FIG 5A NEOPRENE ISOLATORS METRIC DIMENSIONS See Fig 2A or 3A ...

Page 20: ...TORS STANDARD DIMENSIONS LD00707 9 SPRING ISOLATORS UNIT WEIGHT 58 350 LBS UP TO 89 340 LBS UNIT WEIGHT 35 010 LBS UP TO 58 349 LBS LD00706 6 SPRING ISOLATORS 4 SPRING ISOLATORS LD00705 UNIT WEIGHT 19 564 LBS UP TO 35 009 LBS See Fig 2 or 3 See Fig 2 or 3 See Fig 2 or 3 ...

Page 21: ... ISOLATORS METRIC DIMENSIONS LD00707 R 9 SPRING ISOLATORS UNIT WEIGHT 26 468 Kgs UP TO 40 525 Kgs UNIT WEIGHT 15 881 Kgs UP TO 26 467 Kgs LD00706 R 6 SPRING ISOLATORS 4 SPRING ISOLATORS LD00705 R UNIT WEIGHT 8 874 Kgs UP TO 15 880 Kgs See Fig 2A or 3A See Fig 2A or 3A See Fig 2A or 3A ...

Page 22: ...till suspended by the rigging the iso lators should be bolted to the unit by inserting the cap screw s through the hole s in the mounting bracket into the tapped hole in the top of the isolator leveling bolt s Then the unit can be lowered onto the floor The leveling bolts should now be rotated one 1 turn at a time in sequence until the unit end sheets are clear of the floor by the dimension shown ...

Page 23: ...and controls etc The strainer should be installed in the entering chilled water line directly upstream of the chiller Water piping circuits should be arranged so that the pumps discharge through the chiller and should be con trolled as necessary to maintain essentially constant chilled and condenser water flows through the unit at all load conditions If pumps discharge through the chiller the stra...

Page 24: ...ler and condenser water heads and piping for leaks Repair leaks as necessary Before initial operation of the unit both water circuits should be thoroughly vented of all air at the high points REFRIGERANT RELIEF PIPING Each unit is equipped with pressure relief valves located on the condenser and on the evaporator for the pur pose of quickly relieving excess pressure of the refrig erant charge to t...

Page 25: ...rnished shall be made without prior approval of the YORK representative POWER WIRING Chiller with Electro Mechanical Starter A 115 volt single phase 60 or 50 Hertz power sup ply of 15 amperes must be furnished to the control cen ter from the control transformer 2 KVA required in cluded with the compressor motor starter DO NOT make final power connections to control center until approved by YORK re...

Page 26: ... tative Insulation of the type specified for the job or minimum thickness to prevent sweating of 30 F surfaces should be furnished by others and applied to the cooler shell end sheets liquid feed line to flow chamber compres sor suction connection and cooler liquid heads and con nections The liquid head flange insulation must be re movable to allow head removal for the tube mainte nance Details of...

Page 27: ...YORK INTERNATIONAL 27 FORM 160 52 N1 ...

Page 28: ...Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1998 ALL RIGHTS RESERVED Form 160 52 N1 1098 Supersedes 160 52 N1 697 160 52 N1 SB1 298 ...

Reviews: