6
AIR BLOWER
YORK Technical Guide Code 035T76009-000
6 - CONDENSATE
DRAINAGE
Condensate drainage is provided on the unit. The
connection is located at the rear. Use a 19 mm
diameter plastic tube.
To ensure correct condensate drainage, the drain line
must be installed with a gradient of at least 2% (2 cm
per meter) and without any upward slopes.
An elbow trap at least 50 mm in height must also be
provided.
If possible, install a U bend fitted with an inspection cap.
Where the condensate lines from several units are
joined together, each individual outlet must be fitted
with an elbow trap.
After routing and connecting condensate lines, pour
water into the collecting pan and check that it drains
correctly.
An auxiliary condensate pump could be installed in
cases where drain lines cannot be routed the correct
gradient.
Condensate drain connection
OUTDOOR UNIT INSTALLATION
OK