background image

10

AIR BLOWER

YORK Technical Guide Code 035T76009-000

9 - Unit Controller Operation (continued)

FILTER CARE AND FILTER ALARM

To keep your air conditioning unit in peak condition, the
filters should be cleaned regularly, i.e. once a month, or
more frequently depending on conditions. To do this;

- Remove the filters from the unit
- Wash them in soapy water (do not use detergent)
- Dry the filters and put them back in place on the unit.

To clean the unit casing, use a damp cloth.

The control is equipped with a filter Alarm; based on the
hours of operation, and indicated by all of the lights
flashing (see the Diagnostic Chart for details), to remind
you to change the filter. To reset the alarm press the

FILTER button

  on the remote control. If you fail to press

the 

RESET button

, the alarm will automatically reset

after 6 hours of operation.

CLOCK AND TIMER FUNCTIONS

To set the clock press the 

CLOCK button

 for at least 5

seconds, until the 

CLOCK 

symbol flashes. Then use the

TIMER buttons

 to set the desired time. Finally, press

the 

CLOCK button

 again to enter the time that has been

set. The control is equipped with a timer that can set
both start and stop times for the unit. the operational
settings that have been entered on the control will be
the ones that the control follows when it starts.
To use the timer function follow these steps;

START
1. Turn the unit on.
2. Press the 

START button

3. Adjust the clock display to the desired start time
4. Press Enter
The 

START

 symbol will be shown on the display,

indicating that a start time has been programmed.

STOP
1. With the unit on.
2. Press the 

STOP button

3. Adjust the clock display to the desired stop time
4. Press Enter
The 

STOP

 symbol will be shown on the display,

indicating that a stop time has been programmed. Lights
will indicate that the unit timer has been set.

After the unit has either been started or stopped by the
timer, the set time will remain in the program, however
the 

START

 or 

STOP button

 must be pressed again to

reset the timer function.

To cancel either the Start or Stop Timer setting press
the 

CANCEL button

. To check the time that has been

entered either for starting or stopping the unit, press
the appropriate 

START

 - 

STOP button

 and the time will

be displayed. Press the button again to go back to the
clock display.

SLEEP TIMER FUNCTION

Sleep  mode, which can be used in Cool and Heat modes
is a program in the control which is designed to give a
comfortable room environment during sleeping hours.
At the start of sleep mode the unit will operate in cooling
or heating mode continuously until the temperature set
point is reached. It will then run for a further 1 hour period
at this setting. After this, the temperature set point will
automatically be 1°C every hour (cooling) or
lowered – 1°C every hour (heating) until the sleep (shut
off) time is reached.  At this time the unit will shut off.

Sleep mode is set by pressing the 

SLEEP button

 which

will set the shut off time in 30 minute increments, starting
from the time shown on the clock when the 

SLEEP

button

 is first pressed.

In sleep mode the unit will follow the settings that were
entered at the time that Sleep mode was started.  Sleep
mode can be canceled by pressing the 

CANCEL button

at any time.

DIAGNOSTIC INFORMATION
FUNCTION

The control is equipped with a diagnostic information
system to report operation of the unit as well as
operational failures. If your remote control does not
operate properly first check the polarity of the batteries
and that they are in good working condition.  Also make
sure that the control is pointed directly at the air
conditioning unit when you are using it, that the distance
is a maximum of 10 meters, and that there are no
obstacles between the remote control and the air
conditioning unit.

The Diagnostic Information  is reported via different
flashing patterns of the 3 indicator lights on the unit.
The chart below shows the light patterns for the various
operational, protection and failure modes.

This feature is intended to provide information to the
consumer as well as for service of the units.

03_MAL-MAM.p65

20/4/02, 09:43

10

Summary of Contents for MAL-MAM 18

Page 1: ...MINISPLIT AIR BLOWER 035T76009 000 TECHNICAL GUIDE MODELS MAL MAM 18 55 01_MAL MAMCover p65 19 4 02 11 28 1...

Page 2: ...interconnection cord used must not be lighter than Polychloroprene sheated cord 245 IEC 57 or H05RN F Disconnecting device must have a contact separation of at least 3 mm GENERAL PRECAUTIONS Check th...

Page 3: ...76 8 89 13 8 7 97 10 12 1 R 407C 1 170 1 380 1 700 2 500 3 000 102 204 330 330 330 305 305 325 350 350 845 897 962 1 102 1 400 532 567 628 640 640 32 51 53 66 88 Wired or Wireless Control with LCD Dis...

Page 4: ...MAL 35 MAL 45 MAL 55 A 845 897 962 1 102 1 400 B 532 567 628 640 640 C 305 305 325 350 350 D 240 240 268 280 280 E 160 160 160 220 220 F 102 5 128 5 133 161 309 G 110 112 115 230 230 H 125 155 145 78...

Page 5: ...inimum of clearance is necessary around the units to ensure proper air circulation and easy access for maintenance CLEARANCE REQUIRED FOR INDOOR UNITS C B D A E Unit A B C D E 18 400 200 100 250 600 2...

Page 6: ...0 mm in height must also be provided If possible install a U bend fitted with an inspection cap Where the condensate lines from several units are joined together each individual outlet must be fitted...

Page 7: ...pump and down to 5 pa 3 When pump down is finished wait 15 minutes to detect potential circuit leakage Open service valves on the outdoor unit If piping length exceeds 5 meters add 10 g of refrigerant...

Page 8: ...L W O FILTER 230 1 50 Avialable Ext Static Pa Airflow CMH Hi 180 160 140 120 100 80 60 40 20 0 300 00 500 00 700 00 900 00 1100 00 1300 00 1500 00 Me Lo Avialable Ext Static Pa Airflow CMH FAN PERFORM...

Page 9: ...is used to protect against any damage to the unit caused by fluctuation of voltage If voltage is lower than the lower limit for approximately 10 seconds or longer compressor operation will be tempora...

Page 10: ...st be pressed again to reset the timer function To cancel either the Start or Stop Timer setting press the CANCEL button To check the time that has been entered either for starting or stopping the uni...

Page 11: ...al Operation Normal Operation Normal Operation Normal Operation Normal Operation Normal Operation Protection Protection Protection Protection Protection Reset Call Service Technician Reset Call Servic...

Page 12: ...80 415V 3Ph 50Hz 480V 3Ph 60Hz Power supply 380 415V 3Ph 50Hz 480V 3Ph 60Hz N 1 2 3 N 1 2 3 L1 L2 L3 N 1 2 L N 1 2 Indoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Unit size P...

Page 13: ...more often if necessary Each season before start up Each season before start up MAINTENANCE OPERATIONS 1 Clean with a vacuum cleaner or tap gently then wash in warm water 40 C with a mild detergent 2...

Page 14: ...ection factor C2 Capacity correction factor for temperature Indoor unit 10 0 98 5 1 00 R C Standard rating conditions Indoor 27 C DB 19 5 C WB Outdoor 35 C DB 24 C WB Operating temperature limits Cool...

Page 15: ...YORK Technical Guide Code 035T76009 000 AIR BLOWER 15 03_MAL MAM p65 20 4 02 09 43 15...

Page 16: ...to a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under No circumstances should refr...

Reviews: