34
P01432Q-rev.1
8.8 Setback Operation
(1) Press and hold “Menu” and “Back/Help”on the wired controller simultaneously for at least three seconds
during the normal mode (unit stoppage).
The Test Run menu will be displayed.
(2) Select “Input/Output” from the Test Run menu and press “OK”.
(3) Select either "Input 1" or "Input 2" and change the setting to "09".
(4) Build a circuit such as shown below.
(5) Temperature compensation for the setback function can be selected on the wired controller.
Refer to “Function Selection by Wired Controller” section for details.
OK
Test Run Menu
Input/Output
Thermistor Selection
Function Selection
01
/
03
Test Run
Entr
Rtrn
Sel.
Back
Function 5
CN3
1
2
3
1
2
3
1
2
3
CN3
TB1
PSC-5RA
Card Key
No Voltage "a" Contact
When the card key is inserted (i.e.
someone is in the room), then the
contact turns ON.
Indoor Unit
Wired
Controller
OK
Input/Output:01-03
Input 1
00
CN3 1-2
Input 2
00
CN3 2-3
Output1
00
CN7 1-2
Output2
00
CN7 1-3
Output3
00
CN8 1-2
Item
Setting
Connector
Adj.
Entr
Rtrn
Sel.
Back