P01432Q-rev.1
33
Optional Function
Function
Selection
Item
Unit
Setting Condition (Underlined Part is Factory Setting)
00
01
02
03
04
05
06
07
08
09
10
Automatic COOL/HEAT Operation
b8
-
Not
Available Available
Dual Setpoint
r1
-
Not
Available Available
(A) Cooling/Heating
Changeover Temperature
r2
o
F
(
o
C)
2
(1.0)
3
(1.5)
3*
(2.0)
4
(2.5)
5
(3.0)
1
(0.5)
Setback Temperature Compensation
(Setback is initiated when the card key is removed.)
r3
o
F
(
o
C)
4
(2.5)
5
(3.0)
6
(3.5)
7
(4.0)
8
(4.5)
9
(5.0)
10
(5.5)
1
(0.5)
2
(1.0)
3
(1.5)
3*
(2.0)
Auxiliary Heater Setting
q1
-
Not
Available Available
(B)
Auxiliary Heater ON
Compensation
q2
o
F
(
o
C)
-3
(-1.5)
-3*
(-2.0)
-4
(-2.5)
-5
(-3.0)
-6
(-3.5)
-7
(-4.0)
-8
(-4.5)
-9
(-5.0)
-1
(-0.5)
-2
(-1.0)
Auxiliary Heater OFF
Compensation
q3
o
F
(
o
C)
0
(0.0)
1
(0.5)
(C)
Ambient Temperature Restriction
Setpoint
1
q4
o
F
(
o
C)
-4
(-20.0)
2
(-17.0)
8
(-13.0)
14
(-10.0)
20
(-7.0)
26
(-3.0)
32
(0.0)
-13
(-25.0)
-8
(-22.0)
Ambient Temperature Restriction
Setpoint Compensation
1
q5
o
F
(
o
C)
4
(2.5)
5
(3.0)
6
(3.5)
1
(0.5)
2
(1.0)
3
(1.5)
3*
(2.0)
Auxiliary Heater OFF at Defrosting
Operation
L9
-
Not
Available Available
* Not displayed when fahrenheit (
o
F) is selected to display.
1. Be sure to use only the "00" setting condition when combining this function with a water source unit.
Cooling Sr2
(A)
(B)
(C)
Cooling Setpoint
Sq3
Setpoint
Sq2
Auxiliary Heater ON
Auxiliary Heater OFF
Auxiliary Heater ON Compensation
q4+q5
Ambient Temperature
Restriction Setpoint q4
Normal Operation
Forced Thermo-OFF
Indoor
Temperature
Heating Setpoint
Heating Setpoint-r2
Heating
Cooling