H Series - Horizontal Discharge Modulating Heat Pump Compatibility Kit (HMH7AK001): 

The

H Series outdoor section is designed for lower airflow when outdoor terminal S1 is energized and

does not function correctly without this kit.

TXV Kits (S1-1TVM*): 

Thermal expansion valves precisely meter refrigerant for optimum

performance over a wide range of conditions. See Table 4 for the TXV part number for each model.

Sound power ratings

Table 7: Sound power - cooling

Octave band sound power level (dB re. 1 pW)

Model number

63

125

250

500

1000

2000

4000

8000

dBA

SQI

HMH72B241S

70

70

63

62

61

55

50

43

65

19.1

HMH72B361S

72

71

67

63

64

58

56

50

68

19.1

HMH72B481S

73

70

67

64

65

60

57

48

69

19.2

HMH72B601S

78

79

71

66

66

62

64

52

73

19.0

Table 8: Sound power - heating

Octave band sound power level (dB re. 1 pW)

Model number

63

125

250

500

1000

2000

4000

8000

dBA

SQI

HMH72B241S

70

72

64

62

61

55

50

42

65

19.1

HMH72B361S

68

71

68

65

66

62

60

56

70

19.1

HMH72B481S

74

72

70

67

67

63

59

53

71

19.2

HMH72B601S

77

77

73

70

68

63

61

52

73

19.0

Mechanical specifications

Manufacture and certifications

• Units shall be manufactured in an ISO 9001 certified facility.
• Units shall be certified by ETL to UL 1995 and performance certified to ANSI/AHRI Standard

210/240.

• Units shall be sound tested according to ANSI/AHRI Standard 270.
• Certified matched system ratings will be available for downloadfrom the AHRI online directory

at www.ahridirectory.org

Unit application

• Units shall be approved for cooling operation between 35ºF and 122°F without modification.
• Units shall be approved for linesets up to an equivalent length of 164 ft for HMH72B241S and

246 ft for HMH72B361S, HMH72B481S, and HMH72B601S without modification.

• Units shall be approved for installation within 8 in. (long side) and 6 in. (short side) of a flat

vertical wall without modification, according to the instructions in the technical literature.

• Units shall be designed to 73 dBA or less to minimize sound pollution.

Unit access

• Units shall be factory leak checked, run tested, and shipped with a holding charge of R-410A

refrigerant.

• Unit cabinet components shall be G90 equivalent steel finished with powder-coat paint rated at

a minimum of 1,000 h under ASTM B117 testing.

YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump

12

Johnson Controls Ducted Systems 

Summary of Contents for HMH7 Series

Page 1: ...tems YORK Technical Guide HMH7 Series 17 SEER Horizontal Discharge Modulating Heat Pump R 410A 2 to 5 Nominal Ton York International Corporation 5005 York Drive Norman OK 73069 2021 03 25 6062825 YTG...

Page 2: ...2 YORK Technical Guide HMH7 Series 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems...

Page 3: ...eld wiring 14 Alternative installation clearances 15 Performance data 2 ton 16 Cooling performance data 2 ton 16 Heating performance data 2 ton 16 Performance data 3 ton 17 Cooling performance data 3...

Page 4: ...4 YORK Technical Guide HMH7 Series 17 SEER Horizontal Discharge Modulating Heat Pump Johnson Controls Ducted Systems...

Page 5: ...ts are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 ft of field supplied lines Figure 1 Installation certification map Due to continuous product improvement specif...

Page 6: ...pressure sensing technology which detects low pressure in cooling mode and high pressure in heating mode to protect the system from damage Intelligent control can also be realized by calculating the...

Page 7: ...19 SEER 2 208 230 1 60 3 208 230 3 60 Voltage 2 4 460 3 60 B R 410A Refrigerant B D R 454B 12 1 ton 18 1 5 ton 24 2 ton 30 2 5 ton 36 3 ton 42 3 5 ton 48 4 ton Capacity 24 60 5 ton 1 1st Generation G...

Page 8: ...n motor nominal CFM 1 825 2 350 3 525 3 525 Coil face area sq ft 6 1 8 3 14 0 14 0 Coil rows deep 2 2 2 2 Coil fins per inch 18 19 17 18 Liquid lineset outdoor field installed 3 8 3 8 3 8 3 8 Vapor li...

Page 9: ...ches and are subject to change without notice Overall length and width include screw heads Figure 2 Dimensions System charge Table 4 System charge table Outdoor unit HMH72B241S HMH72B361S HMH72B481S H...

Page 10: ...rge required for the specific matched indoor unit in the system using System charge 3 Add additional charge for the amount of interconnecting line tubing greater than 15 ft at the rate specified in Ph...

Page 11: ...R energy efficiency ratio is the total cooling output in BTUs at 95 F outdoor ambient divided by the total electric power in watt hours at those conditions SEER seasonal energy efficiency ratio is the...

Page 12: ...certifications Units shall be manufactured in an ISO 9001 certified facility Units shall be certified by ETL to UL 1995 and performance certified to ANSI AHRI Standard 210 240 Units shall be sound te...

Page 13: ...ls Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors approved for vertical shaft applications Outdoor fan motor shall be ECM construction with permanently lu...

Page 14: ...Typical field wiring Figure 4 Typical field wiring HMH72B241S and HMH72B361S YORK Technical Guide HMH7 Series 17 SEER Horizontal Discharge Modulating Heat Pump 14 Johnson Controls Ducted Systems...

Page 15: ...ng HMH72B481S and HMH72B601S Alternative installation clearances Figure 6 Alternative installation clearances 15 YORK Technical Guide HMH7 Series 17 SEER Horizontal Discharge Modulating Heat Pump John...

Page 16: ...18 3 20 2 20 5 19 5 19 9 20 1 21 4 22 3 20 5 21 0 21 9 22 5 24 1 S C 17 8 17 8 14 3 14 1 10 7 19 5 19 1 16 3 15 9 11 3 20 0 20 4 18 3 17 7 11 8 105 kW 2 4 2 4 2 4 2 5 2 5 2 5 2 5 2 5 2 6 2 6 2 6 2 6...

Page 17: ...2 92 2 96 3 00 3 03 3 05 3 06 3 09 3 13 T C 30 3 34 3 34 9 38 1 41 7 34 3 36 0 36 2 39 4 42 9 37 0 37 7 37 5 40 7 44 0 S C 30 3 29 0 25 1 25 1 20 4 34 3 33 4 28 6 28 5 22 7 37 0 37 7 32 0 32 0 25 1 7...

Page 18: ...Cooling performance data 4 ton Table 13 Cooling performance data 4 ton air temperature F entering outdoor unit Outdoor unit model HMH72B481S ID CFM 1200 1500 1800 ID DB F 80 80 75 80 80 80 80 75 80 8...

Page 19: ...ing outdoor unit Entering indoor coil MBH COP kW MBH COP kW MBH COP kW 60 41 6 2 93 4 15 53 5 3 90 4 02 53 4 4 02 3 89 70 51 0 3 30 4 53 52 7 3 51 4 41 54 4 3 73 4 28 60 80 50 1 3 01 4 87 50 8 3 14 4...

Page 20: ...6 54 6 64 6 46 6 58 6 55 6 70 6 81 T C 43 2 45 0 44 3 48 5 49 5 44 5 45 0 44 5 48 1 49 1 46 6 45 0 44 9 47 5 48 5 S C 43 2 41 9 35 4 34 4 28 2 44 5 43 1 37 0 39 7 36 3 46 6 45 0 39 5 47 5 48 5 105 kW...

Page 21: ...0 4 62 34 3 2 14 4 69 37 0 2 28 4 76 60 33 6 2 44 4 04 35 1 2 52 4 07 36 6 2 61 4 11 70 30 9 2 14 4 23 31 6 2 17 4 27 34 6 2 35 4 31 10 80 27 1 1 79 4 45 29 9 1 93 4 53 32 6 2 07 4 62 60 27 8 2 12 3 8...

Page 22: ...Subject to change without notice Published in U S A Copyright 2021 by Johnson Controls All rights reserved Johnson Controls Ducted Systems...

Reviews: